Violations at 2147 Washington Avenue

Bronx, NY 10457 · BBL 2-03037-0079 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

13 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Elevator elevatorrequired

    Nyc department of education

    Jun 27, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 15, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 10, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 9, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 18, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 30, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 15, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 25, 2005

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 23, 2002

    Dob violation - resolved

ECB violations

The newest 50 of 66 ECB violations. The city keeps the complete history.

  • Class - 2

    Reissue: 35693232l date of issue: 08/26/2025. failure to maintain building in code-compliant manner. fpsc door, corridors exit doors are notclosing properly due to defective hardware at 4th fl. st. way 'c' 3rd

    May 20, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35693233n date of issue: 08/26/2025. failure to maintain building in code-compliant manner. at the time of inspection observed and noted broken window glass panel at exp #1 at 3rd floor level above mai

    May 20, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35693234p date of issue: 08/26/2025. failure to maintain building in code-compliant manner. at the time of inspection observed and noted spalling and crumbling interior plaster due to water leaks at ma

    May 20, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35693235 date of issue: 08/26/2025. failure to maintain building in code-compliant manner. at the time of inspection observed and noted masonry fence at exp-4 have spalled/loose brick pillar by exp #4

    May 20, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue:35593236z date of issue: 08/26/2025. failure to maintain building in code-compliant manner. at the time of inspection observed and noted exp #3 4 steps down to asphalt play yard were missing handrails w

    May 20, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35693237k date of issue: 08/26/2025. failure to maintain building in code-compliant manner. at the time of inspection observed and noted at cellar level boiler room the masonry smoke stack had an appro

    May 20, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.noted at cellar level boiler room,the masonry smoke stack had an approx.15 ft verticalcrack,with separation of bricks present.rem:repair and/or replace.

    Aug 26, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:exp#3(4)steps down to asphalt play yard were missing handrails with distance span greater than 66".also existing handrails were loose along bottom anc

    Aug 26, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted masonry fence at exp#2 have spalled/loose brick forces along the brick pillars.also brick fence pillar by exit#4 was out of plumb,leaning approx.5 wit

    Aug 26, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted spalling and crumbling interior plaster due to water leaks at main entrance vestibule around windows and at gymnasium ceiling. remedy: repair and/or

    Aug 26, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted broken window glass panel at exp #1, 3rd fl level above main entrance. remedy: repair and/or replace.

    Aug 26, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. interior fpsc smoke doors have defective magnetic door catches at: 4th fl stair c, 3rd fl stair d, 2nd fl stair d and c, 1st fl stair d and cafeteria entra

    Aug 26, 2025 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing properly at the time of inspection.at 1st floor cafeteria(neer exit 5)2 exit door to cafeteria,one exit door at exit 5 exit to outside & at 1st fl gym(neer exit 7)one exit door not se

    Sep 26, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.at thetime of inspection noted & observed that at 2nd floor(neer room no.205

    Sep 26, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:no firestopping per bc712.3;27-345.pipes&conduits penetrating thru walls into book storagerm&other areas w/no firestopping provided.provide/maintain firestopping

    May 20, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Reissued35557811j exit door not selfclosing.noted:observed stair exit door@3fl staird&rms428,328 boys&girls restrms dont close properly,doors racked&knocks on door frames jamb,also@rm314 door in disrepair&missi

    May 20, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Re issued #35473272l. exit door not self closing.noted:at 2nd floor room at 204, and 205, boys and girls toilet doors are not self closing properly due to defective hardware.remedy:repair/replace door.

    May 27, 2021 · Penalty $1,562

    Resolve
  • Class - 1

    Class 1 no dlm installed in this controller, as mandated by 3.10.12 of appendix k3 of the 2014 nycbc remedy; file application install dlm and perform and file test with nycdob

    Aug 3, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Bc 715.4.8 exit doors not slef closing @time of inspection observed @4th, 3rd floor exit door by the stair (d) doors are not self close.also204, 428, 205, 328, boys & girls tiolet door not slef close.rem:repair

    May 26, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code complaint manner. re-issue #35434556l failure to maintain bldg in code complaint anner retaining wall hand rail loose @ school yard also has some crack on the wall.rem: repair &

    May 26, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner re-ssue ecb #35434557n failure to maintain bldg in code compliant manner water damaged staining ceiling in various location.rem: repair and/or replace.

    May 26, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Respondent failed to allow annual inspection by nycdob. remedy; arrange for department to conduct annual inspection by emailing [email protected]

    Feb 8, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue :35329529l failure to maintain building in code complaint amnner water damaged staining at ceiling in vairous locations repair and/or replace

    Jun 24, 2019

    Resolve
  • Class - 2

    Re-issuel35329529l failure to maintain building in code complaint manner -retaining wall handrail loose @ school yard repair and.or replace

    Jun 24, 2019

    Resolve
  • Class - 2

    28-301.1 unlawful display of artwork in corridors greter than 20% perfdny 2008 code; fc 803.3.2 note on the 3rd and 4th floors banner han ging from ceiling obstructing the seightline to exit lights.rmdy:compl

    Apr 29, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.1; 27-542 noted: at basement level emergency lighting in disrepair

    Apr 24, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner note in school yard outside gymn retaining wall and step seating area having sprouledconcrete throughout, on retaining wall handrail is loose. rmdy:repair

    Apr 24, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner noted at class rooms 312,412,118,112,130,124 water damage/staining at ceiling in various locations also noted: at gym storage room cieling exposed/opening

    Apr 24, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner use of prohibited door and or hardware per bc 1008.18; 27-371(j)note at 2nd, 1st and cafe passageway door in public corridors having key locks. rmdy: compl

    Apr 24, 2018

    Resolve
  • Class - 2

    Exit door not self closing. noted at stairway c6 4th floor, d2 3rd floor door not closing hitting james. rmdy: repair and/or replace door.

    Apr 24, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner note at roof levels roofing material is compromised water has gotten under materialcausing leaks to rooms 412,312,130,124,118 and air handlers ii,4,5,6

    Apr 24, 2018

    Resolve
  • Class - 1

    Cu05z10,30x10,100x10. 05a10-cease use item. door zone restrictor has been altered and rendered inoperative. repair and contact nycdob at [email protected]; 39-repair t.o.c. light; 100-repair in car fan

    Dec 12, 2017

    Resolve
  • Class - 2

    Reissue#35146800h failure to maintain bldg in code compliant manner. at roof bulkhead stairs c&d water damaged plaster around roof access hatness. remedy: repair or replace.

    Jun 5, 2017

    Resolve
  • Class - 2

    Reissue#35101638j failure to maintain bldg in code compliant manner nofire stopping bc 712.3;27-345 at cellar electric room fire stopping missing. remedy: provide maintain fire stopping.

    Jun 5, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner:no fire stopping perbc 712.3;27-345 re-issue nov #35101638j issued on 6/25/2014 for missing fire stopping.@cellar electrical room,no fire stopping over door w/o

    Sep 28, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.re-issue nov #35146800h issued on 7/8/15 for failure to maintain bldg in code-compliant manner. @roof bulkheads stairs c&d water damaged plasters around roof ac

    Sep 28, 2016

    Resolve
  • Class - 2

    Re-issue nov 35101634m.failure to maintain building in code-compliant manner:use of prohibited door and/or hardware at bulkhead c&d lockabledead bolts installed. remedy:provide code compliant hardware.

    Jul 8, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner @roof bulk heads stairs c & d water damaged plaster around roof access hatches.

    Jul 8, 2015

    Resolve
  • Class - 2

    Missing fire stopping. at cellar electric room, no fire stopping over door near ceiling with conduit penetration. remedy: provide/maintain fire stopping.

    Jun 25, 2014

    Resolve
  • Class - 2

    Combustible posting in fire stair. at stair 'd' 2nd,3rd,4th floor landings, bulletin boards installed with combustible postings. remedy: remove items.

    Jun 25, 2014

    Resolve
  • Class - 2

    Hanging combustible banners. at 1st floor corridor, numerous banners hanging from conduits wall & wall. remedy: remove banners from conduits.

    Jun 25, 2014

    Resolve
  • Class - 2

    Partial obstruction. at center corridor, all floors, combustible storage - furniture - aquariums, book selves, paper goods, reducing width 50%. remedy: remove all items, maintain corridor width clear.

    Jun 25, 2014

    Resolve
  • Class - 2

    Prohibited hardware. at bulkhead "c","d", lockable dead bolts installed where code permits hook & eye allowed. remedy: remove prohibited hardware.

    Jun 25, 2014

    Resolve
  • Class - 2

    Re-issue # 34987266r. damaged plaster surfaces. at stair "d" 2nd,3rd,4th floors & bulkhead, bulkhead "c", damaged ceilings & walls at various locations. remedy: repair all ceilings & walls.

    Jun 25, 2014

    Resolve
  • Class - 2

    Water penetration into 4 fl electrical room from condition from roof a/c units. rmdy: seal penetration/ insulate pipes.

    May 30, 2013

    Resolve
  • Class - 2

    Water damaged plaster wall(s)& ceiling(s). at stair d 2nd story 3rd story,4th story & bulkhead. at stair c bulkhead (around roof access hatch). at library above windows. rem:repair defects noted.

    Jul 26, 2012

    Resolve
  • Class - 2

    Re issue vio #34926353x;34926354h water penetrating bldg envelope. at stair d 1st thru 4th stories, 1st story gymnasium,library,stair d&c bulkheads. rem:repair defects noted maintain weatherproof integrity of b

    Jul 26, 2012

    Resolve
  • Class - 2

    Re issue #34926355j public corridors partially obstructed. at stair d,c bulkheads (stored class rm furn). at 2nd,3rd,4th stry corridors,aquarium tanks,book shelves,classroom furniture. rem:remove stored items m

    Jul 26, 2012

    Resolve
  • Class - 2

    Storage in public corridor partially obstructed egress as per 1016.1 at stair d and c bulkheads combustibles stored at landings, at 4th and2nd stories combustibles stored in public corridors partially obstruct

    Aug 26, 2011

    Resolve
  • Class - 2

    Water penetration thru facade around windows. stair d 1st thru 4th strstair d 1st thru 4th stories, 1st story gymnasium. remedy: repair defects noted maintain weather proof integrity of building.

    Aug 26, 2011

    Resolve