1434 Longfellow Avenue
Bronx, NY 10460BBL 2-03007-0008Map
Owner of record: NYC Department Of Education
1434 Longfellow Avenue is a school building built in 1969 in Bronx, 10460. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 97
- ECB violations
- 63
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 97
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Retaining wall none
Failed to file cycle 1 technical report by 12/31/2018 per rcny 103-09
May 1, 2024
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 12, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 12, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 12, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 3, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 3, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 3, 2020
Dob violation - resolved
Show 40 more ↓
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 14, 2019
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator - failure to file category 1 2017 inspection/test
Apr 5, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 12, 2018
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 12, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Construction other optional
Work after hours without a variance permit
Sep 22, 2017
Vpw*-violation unserved ecb-work without permit-dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 5, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 5, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 5, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2014 inspection/test
Jun 10, 2015
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 17, 2015
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 19, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 19, 2014
Dob violation - resolved - Elevator elevatorrequired
Nyc department of education
Mar 19, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 13, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 13, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 13, 2013
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2011 inspection/test
Oct 1, 2012
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2010 cat 1 insp/tst
Aug 15, 2012
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 10, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 10, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 10, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 10, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 10, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 20, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 20, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 20, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 26, 2009
Dob violation - resolved
ECB violations · 63
- Class - 2
Reissued ecb#35693362j exit door not self-closing.noted exit door#1 indisrepair and not self closing.rem:repair/replace door.
Jul 15, 2026 · Penalty $1,562
Active - Class - 2
Reissued ecb#35693361h failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1.8 and 27-371.noted prohibited door stoppers installed on most classroom doors th
Jul 15, 2026 · Penalty $3,125
Active - Class - 2
Reissued ecb#35693360x failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors perbc 1006.1;27-381.noted majority approx.80% of emergency lights not wor
Jul 15, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.noted fpsc smokedoor by exit#4 not self closing.rem:repair and/or replace.
Jul 15, 2026 · Penalty $1,250
Active - Class - 2
Reissue ecb #35688602n. failure to maintain building in code-compliantmanner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at all building/floors emergency lights n
Aug 22, 2025 · Penalty $1,250
Active - Class - 2
Exit door not self-closing. noted: at(1st fl) cafeteria, exit 1 doors in disrepair/not closing when tested. remedy: repair/replace doors.
Aug 22, 2025 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware for bc 1008.1.8; 27-371(j). noted: at entire/floors of building with installed kick stoppers throughout various area
Aug 22, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: observedat various locations throughout the 4-story school building, several fireproof self-closing interior doors are not closing properly due to m
Sep 10, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: observed at various locations throughout the 4-story school buil
Sep 10, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building in code compliant manner.illumination for exists,exit discharges & public corridors per bc1006.1;27-381 at time of inspection 5th floor gym two emergency lights not operations in au
Mar 9, 2022 · Penalty $625
Resolve
Show 40 more ↓
- Class - 2
Reissue35548308h doi7/2/19 failure to maintain bldg in codecompliant manner use of prohibited door &or hardware per bc1008.1.8;27-371j@lunchrm&gym&auditorium in exit door prohibited door stopper use.@grndfl lev
Mar 9, 2022 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted: observed kick stops installed on all stairwell fire proof self closing doors throughout
Feb 5, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: no fire stopping per bc 712.3;27-345. noted: observed at basemnt level,within gas meter room,pipes penetrating through concrete ceiling slab w/no fire stopping
Feb 5, 2021 · Penalty $1,250
Resolve - Class - 2
Re-issue#35226172x failure to maintain bldg walls or appurtenances.note:at exit#11-12 sidewalks outside have crackers and eroded separtaion causing tripping hazard.school is 60% wheelchair students.rem:maintain
Feb 5, 2018
Resolve - Class - 2
Failur to maintain bldg in code compliant manner.lack of emergency lighting for exits,exit discharges and public corridors per bc 1006.1;27-542.note:at gym emergency lights not working also at various locations
Feb 5, 2018
Resolve - Class - 2
Work after hours w/o variance permit contrary to 28-105.12.5.noted:at the time of inspection,observed workers installing fence at exterior of building and installation of supported scaffold at court yard withou
Sep 22, 2017 · Penalty $400
Resolve - Class - 2
Reissue #35086088l. failure to maintain bldg wall(s) or appurtenances note: at exp exit #11 and 12 sidewalks outside cracked, eroded and broken. reissue of violation issued 3/18/14 #35086088l.rmdy:maintain
Mar 2, 2017
Resolve - Class - 2
Reissue #35086088l failure to maintain building walls or appurtenants side walks throughout school ground cracked, uneven missing concrete and sepreation causing tripping hazardous school is 60% (wheel chair st
Apr 8, 2016
Resolve - Class - 2
Reissve #35066088l.failure to maintain.@ exit 11 & 12 sidewalks outside cracked eroded,& broken (school has a large handicap population).rem:repair or replace sidewalks immediately.
Mar 6, 2015
Resolve - Class - 2
Reissue#35086086h failure to maintain.@ electric meter room,auditoriumfan room,& 4th fl cure missing fire stopping.rem:provide & maintain fire stopping.
Mar 6, 2015
Resolve - Class - 2
Electric meter room- missing fire stopping. auditorium fan room- 4th floor core missing fire stopping. remedy: maintain bldg as per code.
Mar 18, 2014
Resolve - Class - 2
Elevator cab. small elevator floor- floor tiles worn down to subflooring- subflooring is also worn down. remedy: maintain elevator floor as per code.
Mar 18, 2014
Resolve - Class - 2
Sidewalks (exit 11 & 12) eroded,cracked & broken. remedy: maintain all sidewalks as per code.
Mar 18, 2014
Resolve - Class - 2
Auditorium fan room- 4th floor near auditorium remote pnl- no railings behind mechanical equipment- drop at deepest point may be 15'-0"feet. remedy: make safe & install railings as per code.
Mar 18, 2014
Resolve - Class - 2
Sec. 27-765. interior blowers/ventilation turned off, not running intorooms w/no windows. remedy: turn on blowers.
Apr 18, 2013
Resolve - Class - 2
Reissue 34987318j. defective corridor door throughout 4th flr dragging. remedy: repair/replace doors.
Apr 18, 2013
Resolve - Class - 2
Defective/missing panic bar 4 flr stair c. remedy: replace bar.
Apr 18, 2013
Resolve - Class - 2
27-369:excessive combustible in corridors at 1st flr paper art work & decorations hanging wall to wall 2nd flr art work & decoration hangingfrom electric conduits. rem:remove all noted items.
Jul 20, 2012
Resolve - Class - 2
Doors not self closing at 4th flr smoke doors racked to frame & jam onflr throughot various fire doors with installed kick stops prevent proper door operations. rem:maintain all fire proof doors self closing.
Jul 20, 2012
Resolve - Class - 3
Cracked concrete tread and riser at rear yard exterior stair 7th riserand tread up from bottom portion of riser & tread dislodged exposing rebar rem: repair step
Jul 26, 2011
Resolve - Class - 3
Perimeter irom fence displaced damaged at north lot line an appx 6'w x5'h section of iron fence dislodged bent rem; replace damaged section of fence
Jul 26, 2011
Resolve - Class - 3
Door check closer missing at 4th story west auditorium entry door rem; replace missing hardware
Jul 26, 2011
Resolve - Class - 2
Stored furniture obstructing exit passage way stairway f from auditorium east exit way rem: remove stored furniture maintain exit passageways free from obstructions
Jul 26, 2011
Resolve - Class - 2
35q03,39q03,60q03,67m07,68m07,69m07.(35q03)install covers for electrical boxes in shaftway.(39q03)install covers for light top of car.(67m07)provide missing telephone in car.
Jan 12, 2011
Resolve - Class - 2
Reissue:34743933k 4th fl auditorium rear exit right doors not closing. cafeteria double doors racked. 1st fl exit "e" door not closing. rem:repair/replace doors.
Jul 28, 2010
Resolve - Class - 2
Reissue: 34743930p,34466386h water penetration,roof leaking in to classrooms 409 & 415. rem:repair leaking roof.
Jul 28, 2010
Resolve - Class - 2
Reissue - no fresh air vent in gas meter room at cellar level.remedy:provide fresh air ventilation.
Apr 30, 2009
Resolve - Class - 2
Failure to maintain exterior reissue.on inspection exterior brick facade allowing rain water into bldg causing damage in auditorium on 1fl at exit "f" from exit door marked #6 in gym.remedy:waterproof exterior
Apr 30, 2009
Resolve - Class - 2
Failure to maintain exterior. reissue. water penetration in roof leaking in classrooms 409 & 415.remedy:maintain exterior stop leak.
Apr 30, 2009
Resolve - Class - 2
No "exit" sign provided to corridor from platform utility room to stairwell. remedy:provide "exit" sign.
Apr 30, 2009
Resolve - Class - 2
Chairs have been stored in exit 7 from auditorium storage area to stwy"f" corridor.remedy:remove chairs out of corridors.
Apr 30, 2009
Resolve - Class - 2
Gym door check missing, exit "e" no door saddle & cafeteria double door racked to ramp.remedy:repair doors and replace saddle.
Apr 30, 2009
Resolve - Hazardous
Reissue: 34586025z. gas meter room does not have fresh air ventilation on cellar level. remedy: provide fresh air ventilation.
Feb 7, 2008
Resolve - Hazardous
Exterior brick facade has become porous & allowing rain water into the bldg causing interior damages in the auditorium on the 1st flr at ext 'f'. remedy: water proof exterior brick facade.
Feb 7, 2008
Resolve - Hazardous
Failure to provide/maintain fire stopping where required. noted: no fire stopping applied around pipe penetration through wall & ceiling located in the gas meter room on cellar level. leaving open gaps.
Feb 7, 2008
Resolve - Hazardous
Failure to maintain-interior gas meter room-basement has no fresh air vent. remedy: provide fresh air intake
Jul 20, 2007
Resolve - Hazardous
Doors racked @ staircase a/d @ 1fl. remedy: repair doors.
Jun 1, 2006
Resolve - Hazardous
Parapet mortor cracked missing spalling at interior courtyard remedy:repair masowary parapet wall.
Jan 28, 2005
Resolve - Hazardous
Water penetration from roof above classroom #409e remedy:repair roof.
Jan 28, 2005
Resolve - Hazardous
Failure to provide required means of egress for every floor location basement level rear exit this is a total handicap school rear wheel chair ramp wheel chair ramp leads to rear countryard with two sets of
Jan 12, 2004
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1969
- Floors
- 4
- Residential units
- —
- Building area
- 184,800 ft²
- Lot area
- 120,336 ft²
- Zoning
- R7-1
- Community board
- 203
- Council district
- 17
- Block / lot
- 3007 / 8
- Assessed value
- $18,666,900
- Landmark / historic district
- No
Questions about 1434 Longfellow Avenue
Who owns 1434 Longfellow Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 1434 Longfellow Avenue have violations?
NYC HPD has no housing violations on record for this property.
Is 1434 Longfellow Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 1434 Longfellow Avenue built?
City records list 1969 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.