Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 74
- ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
May 7, 2026
Open — Nov sent out - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 30, 2026
Open — Nov sent out - CImmediately hazardous
Provide hot water at all hot water fixtures in the entire apartment located at apt 111, 1st story, 10th apartment from south at west
Jan 10, 2026 · Apt 111
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 17, 2025
Open — Info nov sent out - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 17, 2025
Open — Info nov sent out - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Jun 13, 2025
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Jun 12, 2025
Open — Nov sent out - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Jun 5, 2025
Open — Nov sent out - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective hinges in the entrance located at apt d121, 1st story, 20th apartment from north at east
Jan 10, 2025 · Apt D121
Closed — Violation closed - BHazardous
Provide cabinet doors at lower cabinet at sink in the kitchen located at apt d121, 1st story, 20th apartment from north at east
Jan 10, 2025 · Apt D121
Closed — Violation closed
Show 40 more ↓
- CImmediately hazardous
Abate the infestation consisting of mice in the entire apartment located at apt d121, 1st story, 20th apartment from north at east
Jan 10, 2025 · Apt D121
Open — Notice of issuance sent to tenant - BHazardous
Abate the infestation consisting of vermin observed spider at time of inspection in the entire apartment located at apt d121, 1st story, 20th apartment from north at east
Jan 10, 2025 · Apt D121
Closed — Violation closed - BHazardous
Properly repair with similar material the broken or defective porcelain ennamel finish by method of reglazing at bathtub in the bathroom located at apt d121, 1st story, 20th apartment from north at east
Jan 10, 2025 · Apt D121
Closed — Violation closed - CImmediately hazardous
Provide hot water at all hot water fixtures located at b-room a406, 4th story, 5th b-room from south at west
Dec 11, 2024 · Apt A406
Closed — Violation closed - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective hinge at door to entrance located at b-room a406, 4th story, 5th b-room from south at west
Dec 11, 2024 · Apt A406
Closed — Violation closed - ANon-hazardous
Post and maintain a proper sign on wall of entrance story showing the registration number assigned by the department and the address of the building. at public hall
Dec 11, 2024
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 22, 2024
Open — Info nov sent out - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 22, 2024
Open — Info nov sent out - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 22, 2024
Closed — Violation dismissed - CImmediately hazardous
Provide hot water at all hot water fixtures in the 1st room from north located at b-room a110, 1st story, 11th b-room from west at north
Nov 19, 2024 · Apt A110
Closed — Violation closed - CImmediately hazardous
Provide an adequate supply of heat for the apartment in the 1st room from north located at b-room c303, 3rd story, 2nd b-room from east at south
Nov 15, 2024 · Apt C303
Closed — Violation closed - CImmediately hazardous
Provide hot water at all hot water fixtures in the 1st room from north located at b-room c303, 3rd story, 2nd b-room from east at south
Nov 15, 2024 · Apt C303
Closed — Violation closed - CImmediately hazardous
Provide hot water at all hot water fixtures in the entire apartment located at apt d17, 1st story, 17th apartment from north at east
Jun 11, 2024 · Apt D17
Closed — Violation closed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 17, 2024
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 16, 2024
Open — Nov sent out - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 3, 2024
Open — Nov sent out - BHazardous
Properly repair the source and abate the evidence of a water leak at ceiling in the bathroom located at apt a205, 2nd story, 4th apartment from south at west
Jan 22, 2024 · Apt A205
Closed — Violation closed - BHazardous
Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling in the bathroom located at apt a205, 2nd story, 4th apartment from south at west
Jan 22, 2024 · Apt A205
Open — Nov sent out - CImmediately hazardous
Provide hot water at all hot water fixtures in the entire apartment located at apt a205, 2nd story, 4th apartment from south at west
Jan 22, 2024 · Apt A205
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 16, 2023
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 16, 2023
Open — Info nov sent out - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 16, 2023
Open — Info nov sent out - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Mar 31, 2023
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Mar 29, 2023
Open — Nov sent out - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Mar 17, 2023
Open — Nov sent out - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 3, 2022
Open — Info nov sent out - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 3, 2022
Open — Info nov sent out - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Mar 8, 2022
Open — Nov sent out - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Mar 8, 2022
Open — Info nov sent out - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Feb 17, 2022
Open — Nov sent out - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Feb 17, 2022
Open — Info nov sent out - BHazardous
Properly repair the source and abate the evidence of a water leak at the ceiling in the 1st room from east located at apt d417, 4th story, 10th apartment from north at east
Nov 1, 2021 · Apt D417
Closed — Violation dismissed - CImmediately hazardous
Abate the infestation consisting of roaches in the entire apartment located at apt d417, 4th story, 10th apartment from north at east
Nov 1, 2021 · Apt D417
Closed — Violation dismissed - CImmediately hazardous
Abate the infestation consisting of mice in the entire apartment located at apt d417, 4th story, 10th apartment from north at east
Nov 1, 2021 · Apt D417
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 16, 2021
Open — Nov sent out - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Apr 16, 2021
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 5, 2021
Open — Nov sent out - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Apr 5, 2021
Open — Info nov sent out - CImmediately hazardous
Provide an adequate supply of heat from an approved central heating system, or an approved system of gas or electrical heating in good operating condition for the dwelling unit in the entire apartment located at apt b123, 1st story, 3rd apartment from south at west
Dec 3, 2019 · Apt B123
Open — Nov sent out - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 4, 2019
Closed — Violation dismissed
DOB building violations · 56
- Failure to post energy grade/score none
Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3
Dec 1, 2024
Dob violation - active - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2023)
Jun 23, 2024
Dob violation - active - Failure to post energy grade/score none
Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3
Dec 1, 2023
Dob violation - active - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2022)
Apr 22, 2023
Dob violation - active - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2021)
Aug 21, 2022
Dob violation - active - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2020)
Aug 20, 2022
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Feb 2, 2022
Dob violation - active - Failure to post energy grade/score none
Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3
Apr 29, 2021
Dob violation - active - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2019)
Jun 29, 2020
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Feb 19, 2020
Dob violation - active
Show 40 more ↓
- Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 9, 2020
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 30, 2019
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 9, 2019
Dob violation - resolved - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Aug 7, 2019
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Apr 3, 2019
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Mar 6, 2019
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Mar 6, 2019
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 28, 2018
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 31, 2018
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 3, 2018
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Aug 22, 2018
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Aug 9, 2018
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Aug 9, 2018
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Aug 9, 2018
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Aug 9, 2018
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jun 13, 2018
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jun 13, 2018
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jun 13, 2018
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jun 13, 2018
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
May 2, 2018
Dob violation - active - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 in 2017
Mar 27, 2018
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Mar 21, 2018
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Mar 21, 2018
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Aug 9, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Nov 2, 2016
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Aug 2, 2016
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Jun 2, 2016
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Feb 2, 2016
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Nov 2, 2015
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Aug 2, 2015
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
May 2, 2015
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
May 1, 2014
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2010 inspection report
Dec 13, 2011
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed
ECB violations · 102
- Class - 1
Improper exit / access door side gates have no push bar/emergency exit door, comply with code
Jun 1, 2026 · Penalty $25,000
Active - Class - 2
Failure to certify corrections for violation number 39146737j, file a certificate of correction
Jun 1, 2026 · Penalty $6,250
Active - Class - 2
Failure to comply with the commissioner's order to file a certificate of correction with the department of buildings for violation #039146774z, file a certificate of correction; file a certificate of correction
Apr 27, 2026 · Penalty $6,250
Active - Class - 1
Class 1 recurring condition agg1 c/u: no dlm installed. records show a history of non-compliance by the owner. remedy: install an approved dlm system per code. email the elevator division at [email protected]
Apr 27, 2026 · Penalty $12,500
Active - Class - 1
Failure to maintain building in code-compliant manner: improper exit/exit access doorway arrangement per bc 1014.2 (2008 code); 27-361; bc 1015.2 (2014 code); bc 1016.1 (2022 code). observed no 2nd means of egr
May 1, 2025 · Penalty $12,500
Active - Class - 1
Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed hole penetrations at mechanical rooms on first floor. potential fire haz
May 1, 2025 · Penalty $12,500
Active - Class - 2
Exit door not self-closing. observed non self closing doors throughout building. potential fire hazard., repair/replace door
May 1, 2025 · Penalty $3,125
Active - Class - 2
I found 6 hydrotherm hot water boiler in a modular system.boiler have no manufacture plate/ as per dob records boilers are not register, maintain boiler; correct all violating ondition / submit certificate of c
May 1, 2025 · Penalty $6,250
Active - Class - 1
Inspection sweep inspection perform on device, class 1 recurring violation issued, for no dlm, installed in controller, remedy; file application with the nycdob, then install device then contact nycdob, for ins
Apr 29, 2025 · Penalty $12,500
Active - Class - 2
Failure to comply with commissioner's order contained in summons#39034271k issued on 1/5/2021,and failure to file a certificate of correction pursuant to 28.201.1 and 1rcny 102-01(d)(2).an acceptable certificat
Mar 19, 2024 · Penalty $1,280
Active
Show 40 more ↓
- Class - 2
Failure to comply with commissioner's order contained in summons#39034272m issued on 1/5/2021,and failure to file a certificate of correction pursuant to 28.201.1 and 1rcny 102-01(d)(2).an acceptable certificat
Mar 19, 2024 · Penalty $1,280
Active - Class - 2
I observed in the multi-purpose room the use of flexible cords passing through the wall to supply power to the wall mounted t.v. as per ec 400.8 no flexible cord shall pass through the fixed walls of a building
Dec 1, 2023 · Penalty $4,000
Active - Class - 2
I observed in the room labeled fire sprinkler the hot water pump for the boiler system not in proper working spewing water onto the floor of the boiler and electrical rooms. as per pc102.3 all equipment shall b
Dec 1, 2023 · Penalty $3,125
Active - Class - 2
I observed on the rooftop the exhaust fans in a non-working order, no automatic controls noted or shown by maintenance staff and bathroom switch controls inoperable. also noted automatic lighting controls for e
Dec 1, 2023 · Penalty $4,000
Active - Class - 1
42-m-5= no door lock monitoring installed on this controller as mandated by 3.10.12 of the appendix k3 of the nyc bc. this mandate was issued since jan 1, 2020 and no compliance been recorded making it a recurr
Oct 5, 2023 · Penalty $12,500
Active - Class - 2
Excessive leak on the pump in the boiler room located on the main floor on the a&b side of the facility. as per 102.4 additions, alterations or repairs. additions, alterations, renovations or repairs to install
Apr 7, 2023 · Penalty $625
Active - Class - 2
As per one seven-module hydrotherm boiler in 1st fl. boiler room. serial no. r-2017-3710. model no. mr-2100b. boiler not registered as per commissioner's order. violation no. 039047957h. apply for proper permit
Apr 5, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building in code compliant manner.observed at timeof inspection active leak in boiler room located on ground floor level(building a-b)remedy:repair and/or replace.
Apr 5, 2023 · Penalty $625
Active - Class - 2
Exit door not self-closing.observed at time of inspection,emergency doors to roof do not self-close located on 4th floor leading to roof level(building a-b&c-d)remedy:repair/replace doors.
Apr 5, 2023 · Penalty $312
Active - Class - 2
As per one, six-module hydrotherm boiler w/o rating plate in c/d side of the building. failure to register boiler as per commissioner's order. apply for proper permits. register boiler and call for an inspectio
Apr 5, 2023 · Penalty $625
Active - Class - 1
42m7 dlm not installed in controller as mandated by 3.10.12 of app k3 of nyc code on jan 1,2020 this is a safety device that ensures egress passage safety.remedy file application obtain permit and installed dlm
Apr 5, 2023 · Penalty $3,125
Active - Class - 2
Unsafe electrical equipment/wiring in use.i observed on 3,2,1fl dorming tiers emergen/exit lights that arent op,either they didnt have power,hanging,bulb was burnt out&batteries were in need of replacement,this
May 17, 2022 · Penalty $2,030
Active - Class - 2
Failure to maintain building in code-compliant manner. i observed excessive combustible storage in the water meter room consisting of push blower(gas powered) lawn mower(gas powered),also wood dresser blocking
Feb 14, 2022 · Penalty $3,125
Active - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor
Nov 8, 2021 · Penalty $1,250
Active - Class - 2
As per one, seven module, hydro therm boiler. boiler not registered. register boiler. call for an inspection.
Sep 22, 2021 · Penalty $625
Active - Class - 2
As per one six module, modular hydro therm boiler. boiler not registered-pressure relief valve for boiler number one rated above the maximum operating working pressure of boiler. register boiler. call for inspe
Sep 22, 2021 · Penalty $625
Active - Class - 1
Failure to comply w/the commissioner's order contained in summons/violation #35325204p issued on 3/20/18 & to file a certificate of correction pursuant to 28-201.1 & 1rcny 102-01.work w/out permit.permit #22068
Aug 24, 2021 · Penalty $6,250
Active - Class - 1
Failure to comply w/the comm's order contained in summons/vio#35325204p issued on 03/20/18 & to file a cert of correction pursuant to 28-201.1 & 1rcny 102-01. remedy: comply w/comm's order &/or file a cert of c
Jun 11, 2021 · Penalty $6,250
Active - Class - 2
Failure to comply with commissioners order to file a certificate of correction with dept of buildings under violation #39034271k
Mar 15, 2021
Resolve - Class - 2
Failure to comply with the commissioners order to file a certificate of correction withdept of buildings under violation #3905472m
Mar 15, 2021
Resolve - Class - 1
Failure to comply w/the comm's order contained in summons/vio#35325204p issued on 03/20/18 & to file a cert of correction pursuant to 28-201.1 & 1rcny 102-01. work w/o permit. 2 hot water storage tanks have bee
Mar 3, 2021 · Penalty $6,250
Active - Class - 2
Found bank of ý6 ¨hydrotherm boilers not registered with this dept. there was a permit taken out #220689075. no inspection were done and never sign off
Jan 5, 2021 · Penalty $3,125
Active - Class - 2
Found bank of ý7¨ hydrotherm boilers that are not registered with this dept job # 220662888 was file and no inspection were done and not sign off.
Jan 5, 2021 · Penalty $3,125
Active - Class - 1
Failure to comply with the commissioners order contained in summons/violation#35325204p issued on 3/20/18 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01.b101:work wihtout a permit
Aug 24, 2020 · Penalty $6,250
Active - Class - 1
Failure to maintain building in a code complaint manenr observed an automatci fire sprinkler system installed throughout th eproperty however no fire department connection in installed for the automatic fire sp
Jan 27, 2020 · Penalty $1,563
Resolve - Class - 1
Failure to comply w/the comm's order contained in summons/vio#35325204p issued on 03/22/18 & to file a c of c pursuant to 28-201.1 & 1rcny 102-01. remedy: comply w/comm's order &/or file a c of c.
Dec 20, 2019 · Penalty $6,250
Active - Class - 1
Failure to maintain bldg in a code compliant manner. observed an automatic fire sprinkler system installed throughout the property however no fire dept connections installed for the automatic fire sprinkler sys
Nov 26, 2019 · Penalty $3,125
Resolve - Class - 1
Failure to comply w/the comm's order contained in summons/vio#35325204p issued on 03/22/18 & to file a c of c pursuant to 28-201.1 & 1rcny 102-01. work w/o permit. remedy: comply w/comm's order &/or file a c of
Oct 29, 2019 · Penalty $12,500
Resolve - Class - 1
Failure to comply w/ the commissioner's order contained in summons/violation#35325204p issued on 3/22/18 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. for work w/o permit. remed
Oct 23, 2019 · Penalty $2,530
Active - Class - 2
Residential gas used on commercial laundry equipment., repair and/or replace
Oct 8, 2019 · Penalty $625
Resolve - Class - 1
Failure to maintain bldg in a code compliant manner. observed at exp#1,2,3&4 no fire dept connection installed for an automatic fire sprinkler system althrough the property has an automatic fire sprinkler syste
Sep 30, 2019 · Penalty $3,125
Resolve - Class - 2
Failure to comply w/the comm's order contained in summons/vio#35434233r issued on 08-01-19 & to file a c of c pursuant to 28-201.1 & 1rcny 102-01. remedy: comply w/comm's order &/or file a c of c.
Sep 23, 2019 · Penalty $1,250
Resolve - Class - 1
Failure to comply wth the commissioner;s order contained in summons/violation#35426816z issued on 03/22/18 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01.remedly:comply with commi
Sep 16, 2019 · Penalty $2,500
Resolve - Class - 2
Failure to comply with the commissioner's order contained in summons/violation#32098061k issued on 11/8/18 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01(d)(2). an acceptible
Sep 10, 2019 · Penalty $1,250
Resolve - Class - 2
Failure to comply with the commissioner's order contained in summons/violation#32098060z issued on 11/9/18 and to file a certificate of cor rection pursuant to 28-201.1 and 1rcny 102-01(d)(2). an acceptible
Sep 10, 2019 · Penalty $1,250
Resolve - Class - 1
Failure to comply w/the comm's order contained in summons/vio#35325204p issued on 03/22/18 & to file a c of c pursuant to 28-201.1 & 1rcny 102-01. remedy: comply w/comm's order &/or file a c of c.
Sep 6, 2019 · Penalty $6,250
Active - Class - 1
Failure to maintain building in code-compliant manner. observed on 8/01/2019 @above address @exp 1,2,3,4, no fire dept connection installed for an automatic fire sprinkler system as required.rem: repair and or
Aug 1, 2019 · Penalty $3,125
Resolve - Class - 1
Failure to comply with the commissioners order contained in summons/violatin #35325211n issued on 03-22-2018 and to file a certificate of correcction pursuant to 28-201.1 and 1rcny 102-01.for work without a per
Jul 25, 2019 · Penalty $2,500
Active - Class - 1
Failure to comply w/the comm's order contained in summons/vio#35395564m issued on 04/08/19 & to file a c of c pursuant to 28-201.1 & 1rcny 102-01. remedy: comply w/comm's order &/or file a c of c.
Jul 5, 2019 · Penalty $2,500
Resolve - Class - 1
Failure to maintain building in code-compliant manner. observed at exposure 1,2,3,4 no fire dept connection installed for an automatic fire sprinkler systems required. remedy: repair and or replace.
May 17, 2019 · Penalty $625
Resolve
Complaints
- Heat/hot water
Entire building
Apr 17, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Feb 10, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Feb 8, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 29, 2026 · Apt BLDG
Close - Heat/hot water
Apartment only
Jan 24, 2026 · Apt C110
Close - Heat/hot water
Entire building
Jan 9, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Dec 30, 2025 · Apt A103
Close - Heat/hot water
Apartment only
Dec 11, 2025 · Apt A402
Close - Heat/hot water
Entire building
Nov 11, 2025 · Apt BLDG
Close - Heat/hot water
Entire building
Jul 17, 2025 · Apt BLDG
Close
Show 40 more ↓
- Plumbing
Bathtub/shower
May 27, 2025 · Apt D230
Close - Plumbing
Basin/sink
May 27, 2025 · Apt D230
Close - Door/window
Window frame
May 24, 2025 · Apt D230
Close - Safety
Smoke detector
May 24, 2025 · Apt D230
Close - Safety
Carbon monoxide detector
May 24, 2025 · Apt D230
Close - Unsanitary condition
Sewage
May 24, 2025 · Apt D230
Close - Plumbing
Bathtub/shower
May 24, 2025 · Apt D230
Close - Plumbing
Bathtub/shower
May 22, 2025 · Apt D230
Close - Heat/hot water
Entire building
Jan 8, 2025 · Apt BLDG
Close - Heat/hot water
Entire building
Dec 27, 2024 · Apt B218
Close - Paint/plaster
Wall
Dec 10, 2024 · Apt D121
Close - Heat/hot water
Entire building
Dec 9, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Nov 19, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Nov 15, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 18, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 18, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 3, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Jun 18, 2024 · Apt C108
Close - Heat/hot water
Entire building
Jun 11, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
May 14, 2024 · Apt A310
Close - Heat/hot water
Entire building
May 6, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Feb 4, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 19, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 8, 2024 · Apt D330
Close - Heat/hot water
Entire building
Jun 30, 2023 · Apt C114
Close - Water leak
Heavy flow
May 21, 2023 · Apt A205
Close - Heat/hot water
Entire building
Mar 5, 2023 · Apt BLDG
Close - Heat/hot water
Apartment only
Mar 4, 2023 · Apt A106
Close - Heat/hot water
Entire building
Jan 20, 2023 · Apt D228
Close - Plumbing
Bathtub/shower
Jan 17, 2023 · Apt C403
Close - Appliance
Electric/gas range
Jan 17, 2023 · Apt C403
Close - Heat/hot water
Entire building
Dec 22, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Dec 22, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Dec 16, 2022 · Apt D415
Close - Heat/hot water
Entire building
Dec 10, 2022 · Apt D421
Close - Heat/hot water
Entire building
Nov 17, 2022 · Apt D424
Close - Heat/hot water
Entire building
Nov 15, 2022 · Apt A104
Close - Unsanitary condition
Mold
Aug 22, 2022 · Apt B420
Close - Plumbing
Basin/sink
Aug 22, 2022 · Apt B420
Close - Unsanitary condition
Mold
Aug 21, 2022 · Apt D417
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Care facility (N2)
- Year built
- 1990
- Floors
- 4
- Residential units
- 214
- Building area
- 117,000 ft²
- Lot area
- 77,896 ft²
- Zoning
- R7-1
- Community board
- 204
- Council district
- 16
- Block / lot
- 2787 / 1
- Assessed value
- $17,171,100
- Landmark / historic district
- No
HPD registration #228592, last renewed Jul 11, 2025.
Questions about 1450 Morris Avenue
Who owns 1450 Morris Avenue?
The owner of record in NYC Department of City Planning PLUTO data is H E L P -Bronx.
Does 1450 Morris Avenue have violations?
Yes. NYC HPD has recorded 74 housing violations at this property.
Is 1450 Morris Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 1450 Morris Avenue built?
City records list 1990 as the year it was built.
How many apartments are in 1450 Morris Avenue?
It has 214 residential units and 215 units in total.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.