948 Tiffany Street
Bronx, NY 10459BBL 2-02714-0004Map
Owner of record: NYC Department Of Education
948 Tiffany Street is a school building built in 1973 in Bronx, 10459. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 38
- ECB violations
- 83
- HPD complaints
- 62
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 38
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Retaining wall none
Failed to file cycle 1 technical report by 12/31/2018 per rcny 103-09
May 1, 2024
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 22, 2020
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Nov 8, 2019
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Nov 8, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 28, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 29, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed
Show 28 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Mar 11, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Residential elevator periodic inspection/test elevatorrequired
Failure to perform category 5 inspection
Jun 1, 2016
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
Nyc department of education
Feb 20, 2014
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 6, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 31, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 2, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 13, 2008
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - active
ECB violations · 83
- Class - 2
Reissue#35725179p failure to maintain building in code-compliant manner.noted:interior fpsc doors do not self-close properly at 3rd flr-staircase f,smoke door near rm#309d.1st flr-staircase b,auditorium doors.c
Jul 23, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35725178n failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:observed emg lights 4,6,9,11,14 & library were not
Jul 23, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35725177l failure to maintain building in code-compliant manner.noted:observed at playground,retaining wall has vertical cracks approx.16" near post.rem:repair and/or replace.
Jul 23, 2026 · Penalty $3,125
Active - Class - 2
Class 2 item: in-car communication is not connected to a continuously staffed 24-hour answering service, as required by nyc building code appendix k, section k3.3, modifying asme a17.1 s2.27
Feb 2, 2026 · Penalty $625
Active - Class - 2
Re-issue #35692543y. failure to maintain building in code-compliant manner. noted: at electrical room illegal storage, miscellaneous items. remedy: repair and/or replace.
Aug 29, 2025 · Penalty $3,125
Resolve - Class - 2
Re-issue #35693541k. failure to maintain building in code-compliant manner. noted: at fox street side left of 2nd flr window 3' long step crack. tiffany street side playground retaining wall cracks. remedy: rep
Aug 29, 2025 · Penalty $3,125
Active - Class - 2
Reissue #35602540z. failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-37. noted: at 3rd flr library, gym, 2nd flr "stair e", c
Aug 29, 2025 · Penalty $3,125
Active - Class - 2
Re-issue #35693539l. failure to maintain builing in code-compliant manenr. noted: at 4th floor room #409c, bo, 403b, 423h corridor by 305. 2nd flr 203f, 209c, corridor by 223a, 1st flr cafeteria by 105, 145. 4t
Aug 29, 2025 · Penalty $3,125
Active - Class - 2
Unlawful display of artwork in corridors greater than 20% per fdny 2008 code; fc 803.3.2. noted: during inspection observed 1st flr-harvard wing excessive amount of flags hanging from ceiling in hallways. remed
Aug 29, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: inside gym on the ceiling. obsserved water damage and step cracks near gym exit. remedy: repair and/or replace.
Aug 29, 2025 · Penalty $1,250
Resolve
Show 40 more ↓
- Class - 2
Failure to maintain building in code-compliant manner. no firestopping. no firestopping per bc 712.3; 27-345. noted: observed in electrical room there was firestopping missing in several areas. remedy: provide/
Aug 29, 2025 · Penalty $1,250
Resolve - Class - 2
E-issue #35692542m. exit door not self-closing. noted: "stair f" and "exit 3: doors are not closing correctly. remedy: repair and/or replacedoors.
Aug 29, 2025 · Penalty $1,562
Resolve - Class - 1
Cease use items: 1)unsecured in car stop switch. 2)inoperative zone lock restrictor. class 2 items: self resetting escape hatch switches prohibited. replace worn gibs where needed. whellhouse stop switch engage
Dec 16, 2024 · Penalty $1,250
Active - Class - 2
Reissue#35672331y failure to maintain building in code-compliant manner.noted:at 4 floor room#409c,b0,403b,423h corridor by 306 2 fl 203f,209c,corridor by 223a 1 fl cafeteria by 105 and 145 doors are not closin
Nov 7, 2024 · Penalty $1,562
Active - Class - 2
Reissue#35672330m failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 3 floor library gym 2 fl stair e cafeteria by 14
Nov 7, 2024 · Penalty $1,562
Active - Class - 2
Exit door not self-closing.noted at 4 floor smoke stair c 3 fl(5)by 323d,309d 2 fl(5)by 220 stair d,1 fl(5)stair f and exit 3 doors are not closing correctly.rem:repair/replace door.
Nov 7, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:at electrical room illegal storage miscellaneous items.rem:repair and/or replace
Nov 7, 2024 · Penalty $625
Resolve - Class - 2
Reissue#35672329p failure to maintain building in code-compliant manner.noted:at fox street side left side it 2nd floor window 3'long stop crack tiffany street side playground retaining wall cracks exits 4 fl w
Nov 7, 2024 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code-compliant manner; illumination for exits, exit discharges and public corridors per bc 1006.1;27-381. noted: at auditorium, emergency exit lighitng #11 and 13 found inoperati
Jul 13, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: at 3rd floor, room #303h and 309a door do not close properly. remedy: repair/replace
Jul 13, 2023 · Penalty $625
Resolve - Class - 2
Reissue #35658034r failure to maintain building wall(s) or appurtenances. noted: at fox street side left side of 2nd window approx. 3' long step crack. also at tiffany street side, at the corner by the flagpole
Jul 13, 2023 · Penalty $3,125
Active - Class - 2
Reissue38577411z failure to maintain bldg wall(s) or appurtenances.atomy insp i observed on foxst side above exit for facade above 2fl up toroof has several step cracks&missing mortar v35577411z issued7/19/21 f
Jun 28, 2022 · Penalty $3,125
Active - Class - 2
Reissue#35498101h failure to maintain bldg walls or appurtenances. noted: during inspection observed on fox street above exit#2-the facade above the 2nd fl upto the roof has several step cracks & missing mortar
Jul 19, 2021 · Penalty $3,125
Active - Class - 2
Reissued#35498103l failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: during inspection observed on 3rd fl-library emergenc
Jul 19, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35498102j exit door not self closing. noted: during inspectionobserved the doors as followed: 409 corridor,423 corridor,3rd fl-stairf & e,309 corridor & fox street main entrance(#1-exit)doors are not
Jul 19, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35447689h exit door not self closing. noted: on the 4th fl 409 & 423 3rd floor stair#3 & on the 2nd floor 209 these doors are not opening & closing properly. remedy: repair/replace door.
Jun 4, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue#35447688x failure to maintain buidling in code compliant manner illumination for exits,exit discharges and publci corridors per bc 1006.27-381 noted on the third floor library none of the emergency ligh
Jun 4, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue#35447690p failure to maintain building wall(s) or appurtenances noted on fox street side above eixt #2 on teh fourth floor the bricks are cracks maintain exteiror buidling wall
Jun 4, 2020 · Penalty $3,125
Active - Class - 2
Reissue#35335102n failure to maintain bldg walls or appurtenances. note: at exp#1(fox street)by exit#2 at 4th fl,bldg wall has cracks in bricks. remedy: maintain exterior bldg wall.
Aug 23, 2019 · Penalty $3,125
Active - Class - 2
Exit door not self-closing. note: at 4th fl(door frame #403)hallway,at3rd fl(door frame#309 & 323). hallway,at 2nd fl(exit#3)staircase c,at 1st fl(exit#3)staircase'd'doors not self closing due to defective/miss
Aug 23, 2019 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. note: at staircase a bulkhead leaks from ceiling on left hand side facing staircase. also at staircase a between roof & 4th fl staircase landing,right side of
Aug 23, 2019 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: illumination for exits;exit discharges & public corridors per bc1006.1;27-381. note: at library emergency lights not working when tested,also at auditorium(fro
Aug 23, 2019 · Penalty $625
Resolve - Class - 2
Failure to comply with the commissioner's order contained in summons/violation #35173511p issued 03/23/17 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. no certificate of correct
Sep 12, 2018
Resolve - Class - 2
Reissue #35216600y date of issue 11.03.2016 failure to maintain bldgwall(s) or appurtenances (exterior) on fox street side main entrance. observed step cracks in bricks at 4th fl level near exit 2 at school
May 25, 2018
Active - Class - 2
Failure to maintain building in code compliant manner: illumination gfor exits, exit discharges and public corridors per bc 1006.1; 27-381at first fl exit 5 one place, stair f/e at 3rd floor one exit sign,
May 25, 2018
Resolve - Class - 2
Exit door not self closin. at 2nd floor, room no. 207 gymnasium 2 exitdoors, at 4th floor near room no. 409 one exit door. exit 5 first flr inside one exit dooe, outside one door, near room no. 209e one exit
May 25, 2018
Resolve - Class - 2
Reissue# 35216601x. failure to maintain bldg wall(s) or appurtenances. noted: @ time of insp observed a concrete masonry unit wall in alley between school & adjoining property 998 tiffany street has collapsed &
Jun 15, 2017
Resolve - Class - 2
Reissue#35086056r failure to maintain bldg walls or appurtenances. noted: concrete masonry unit wall in alley between school & adjoining property(998 tiffany st)has collapsed & part of the wall still remains in
Nov 3, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.(interior)noted: at 3rd fl,corridor fireproof self closing doors 323 & 309 has damaged &/or defective door closers. doors are not closing properly. on floor 2,
Nov 3, 2016
Resolve - Class - 2
Failure to maintain bldg walls or appurtenances.(exterior)noted: on fox street side main entrance,observed step cracks in bricks at 4th fl level near exit 2. at school yard near fox street some bricks at 4th fl
Nov 3, 2016
Active - Class - 2
Failure to maintain bldg walls or appurtenances.@ gymnasium roof leaksapprox 12sf @ south east corner.rem comply w/ nov,maintain waterproof integrity of roof
Jul 28, 2015
Resolve - Class - 2
Reissue-35019465h the brick fence wall is leaning inward located adj to fox st.noted:brick wall is apporx.12'-0 high & being held in place by 2 x 4 wood shoring.opposite brick fence-@ corner of bldg concrete sl
Mar 11, 2014
Resolve - Class - 2
Egress blocked by gym equipment room 211.rem:maintain excercise room as per code
Mar 11, 2014
Resolve - Class - 2
Electrical meter room smoke detector covered with black tape.rem:maintain bldg as per code
Mar 11, 2014
Resolve - Class - 2
Reissue-35019464x glazed wall tiles are loose located @:1st fl adj to stairway a.3rd fl adj.to room 318. 1 fl.room 118-missing mortor.rem:maintain bldg as per code.
Mar 11, 2014
Resolve - Class - 2
The following areas are blocked/use for storage:1-roof landing a & b storage of gym equipment.2-girls locker room 215-used as storage.fans,office copies,t.v. boxes throughout.3-room 211-bathroom-all storage of
Mar 11, 2014
Resolve - Class - 2
Westchester ave side of health center(clinic)and/or rear exterior sid e of auditorium cmu has collapsed into alletway.rem:maintain exterior walls as per code.
Mar 11, 2014
Resolve - Class - 2
Defective doors.4 fl.cross corridor near room 409a. 4fl.cross corridor3 fl.cross corridor.rem:maintain doors as per code.
Mar 11, 2014
Resolve - Class - 2
The brick facade has a vertical cracked located on the 3rd fl level next to fox st approx 6'feet long. remedy: repair &/or replace crack facade.
May 14, 2013
Resolve - Class - 2
Reissue: 34980662r the ceiling plaster is spalling located in the 2nd fl gymnasium. remedy: replace/repair plaster.
May 14, 2013
Resolve
Complaints
- Electric
Power outage
Mar 31, 2026 · Apt 5L
Close - Unsanitary condition
Pests
Feb 28, 2026 · Apt 5L
Close - Electric
No lighting
Feb 28, 2026 · Apt 5L
Close - Unsanitary condition
Mold
Feb 28, 2026 · Apt 5L
Close - Water leak
Slow leak
Feb 28, 2026 · Apt 5L
Close - Door/window
Door
Feb 28, 2026 · Apt 5L
Close - Safety
Smoke detector
Feb 28, 2026 · Apt 5L
Close - Paint/plaster
Door/frame
Feb 28, 2026 · Apt 5L
Close - Safety
Carbon monoxide detector
Feb 28, 2026 · Apt 5L
Close - General
Bell/buzzer/intercom
Feb 28, 2026 · Apt 5L
Close
Show 40 more ↓
- Appliance
Electric/gas range
Feb 28, 2026 · Apt 5L
Close - Unsanitary condition
Pests
Feb 27, 2026 · Apt 5L
Close - Door/window
Door frame
Feb 17, 2026 · Apt APT5L
Close - Appliance
Electric/gas range
Feb 17, 2026 · Apt APT5L
Close - Paint/plaster
Ceiling
Feb 17, 2026 · Apt APT5L
Close - Door/window
Window frame
Feb 17, 2026 · Apt APT5L
Close - General
Bell/buzzer/intercom
Feb 17, 2026 · Apt APT5L
Close - Unsanitary condition
Pests
Feb 17, 2026 · Apt APT5L
Close - Unsanitary condition
Pests
Jan 2, 2026 · Apt 5L
Close - Heat/hot water
Apartment only
Oct 11, 2025 · Apt 5L
Close - Heat/hot water
Entire building
Sep 22, 2025 · Apt 1
Close - Unsanitary condition
Garbage/recycling storage
Sep 22, 2025 · Apt 1
Close - General
Janitor/super
Sep 22, 2025 · Apt 1
Close - Electric
Power outage
Aug 31, 2025 · Apt 5L
Close - Door/window
Window frame
Aug 27, 2025 · Apt 5L
Close - Heat/hot water
Apartment only
Aug 27, 2025 · Apt 5L
Close - Door/window
Door
Aug 27, 2025 · Apt 5L
Close - General
Bell/buzzer/intercom
Aug 27, 2025 · Apt 5L
Close - Electric
Lighting
Aug 27, 2025 · Apt 5L
Close - Door/window
Door frame
Aug 27, 2025 · Apt 5L
Close - General
Ventilation system
Aug 27, 2025 · Apt 5L
Close - Electric
Outlet/switch
Aug 27, 2025 · Apt 5L
Close - Door/window
Door
Aug 27, 2025 · Apt 5L
Close - Unsanitary condition
Garbage/recycling storage
Aug 18, 2025 · Apt BLDG
Close - Heat/hot water
Apartment only
Jul 30, 2025 · Apt 5L
Close - Electric
Outlet/switch
Jul 7, 2025 · Apt 6T
Close - General
Cabinet
Jul 7, 2025 · Apt 6T
Close - Electric
Outlet/switch
Jul 6, 2025 · Apt 6T
Close - General
Cabinet
Jul 6, 2025 · Apt 6T
Close - General
Cabinet
Jun 26, 2025 · Apt 6T
Close - Electric
Outlet/switch
Jun 26, 2025 · Apt 6T
Close - Unsanitary condition
Garbage/recycling storage
Jan 9, 2025 · Apt 5L
Close - General
Bell/buzzer/intercom
Jan 9, 2025 · Apt 5L
Close - Unsanitary condition
Mold
Jan 9, 2025 · Apt 5L
Close - Unsanitary condition
Pests
Jan 9, 2025 · Apt 5L
Close - Unsanitary condition
Garbage/recycling storage
Dec 14, 2024 · Apt 5L
Close - Unsanitary condition
Pests
Dec 14, 2024 · Apt 5L
Close - Unsanitary condition
Garbage/recycling storage
Dec 14, 2024 · Apt 5L
Close - Unsanitary condition
Mold
Dec 5, 2024 · Apt 5L
Close - Unsanitary condition
Pests
Dec 5, 2024 · Apt 5L
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1973
- Floors
- 5
- Residential units
- —
- Building area
- 220,180 ft²
- Lot area
- 112,000 ft²
- Zoning
- R7-1
- Community board
- 202
- Council district
- 17
- Block / lot
- 2714 / 4
- Assessed value
- $18,391,050
- Landmark / historic district
- No
Questions about 948 Tiffany Street
Who owns 948 Tiffany Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 948 Tiffany Street have violations?
NYC HPD has no housing violations on record for this property.
Is 948 Tiffany Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 948 Tiffany Street built?
City records list 1973 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.