980 Prospect Avenue
Bronx, NY 10459BBL 2-02690-0123Map
Owner of record: 980 Prospect Owner, LLC
980 Prospect Avenue is a hotel built in 1907 in Bronx, 10459. The owner of record is 980 Prospect Owner, LLC. HPD has recorded 59 housing violations here, most recently on April 30, 2026.
- HPD violations
- 59
- DOB violations
- 57
- ECB violations
- 83
- HPD complaints
- 181
What to know
No open immediately-hazardous violations among recent records.
Date of the most recent HPD inspection that found a problem.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 59
- ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 30, 2026
Closed — Violation dismissed - CImmediately hazardous
M/d law abate the nuisance consisting of hot water exceed the maximum of 130 degrees in the bathroom located at b-room 235, 2nd story, 1st b-room from north at east
Jan 11, 2026 · Apt 235
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 17, 2025
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Jun 5, 2025
Closed — Violation dismissed - CImmediately hazardous
M/d law abate the nuisance consisting of hot water exceeding 130 degrees at community bathroom, 2nd story
Dec 27, 2024
Closed — Violation dismissed - ANon-hazardous
Post and maintain a proper sign on wall of entrance story showing the registration number assigned by the department and the address of the building. at public hall, 1st story
Oct 18, 2024
Closed — Violation closed - ANon-hazardous
§ 329, m/d law and dept. rules and regs. provide a completed certificate of inspection visits in a proper frame readily accessible for signature, bottom edge of frame between 48-62 inches above floor at (frame missing) at public hall, 1st story
Oct 18, 2024
Closed — Violation closed - CImmediately hazardous
M/d law abate the nuisance consisting of hot water tempreture exceeding the maximum tempreture of 130 degrees f. at community bathroom, 2nd story
Oct 18, 2024
Closed — Violation closed - ANon-hazardous
Post, in a form approved by the commissioner, and maintain a notice in a common area of the building regarding the procedures that should be followed when a gas leak is suspected at public hall, 1st story
Oct 18, 2024
Closed — Violation closed - ANon-hazardous
Post and maintain a proper notice on wall of the entrance story in english and spanish on the availability of the agencys housing information guide. a sample notice can be found at www.nyc.gov/hpd. at public hall, 1st story
Oct 18, 2024
Closed — Violation closed
Show 40 more ↓
- ANon-hazardous
Post a proper notice of smoke detector requirements, in a form approved by the commissioner, at or near the mail box at public hall, 1st story
Oct 18, 2024
Closed — Violation closed - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective (defective spring loaded hinges at door leading to fire escape balcony) at public hall, 1st story
Oct 18, 2024
Closed — Violation closed - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective (defective spring loaded hinges at fire door) at public hall, 2nd story
Oct 18, 2024
Closed — Violation closed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 3, 2024
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 16, 2023
Closed — Violation dismissed - CImmediately hazardous
M/d law abate the nuisance consisting of hot water exceeding the maximum allowable temperature of 130 degrees at community bathroom, 3rd story
Nov 15, 2023
Closed — Violation closed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Mar 17, 2023
Closed — Violation dismissed - CImmediately hazardous
M/d law abate the nuisance consisting of hot water temperature exceed over 130 degrees in the other located at sro 334, 3rd story, 4th single room occupancy from west at north
Nov 11, 2022 · Apt 334
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 3, 2022
Closed — Violation dismissed - CImmediately hazardous
M/d law abate the nuisance consisting of hot water exceeds the maximum of 130 degrees in the entire apartment located at apt 232, 2nd story, 1st apartment from north at east
Mar 27, 2022 · Apt 232
Closed — Violation closed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Feb 18, 2022
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Feb 18, 2022
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 5, 2021
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Apr 5, 2021
Closed — Violation dismissed - CImmediately hazardous
Provide hot water at all hot water fixtures located at b-room 330, 3rd story, 1st b-room from west at north
Aug 7, 2020 · Apt 330
Closed — Violation closed - CImmediately hazardous
Provide hot water at all hot water fixtures at community bathroom, 2nd story
Jun 14, 2020
Closed — Violation dismissed - CImmediately hazardous
Provide ready access to buildings heating system door lock at boiler room
Jun 14, 2020
Closed — Violation closed - CImmediately hazardous
Provide hot water at all hot water fixtures located at b-room 634, 7th story, 3rd b-room from west at north
May 7, 2020 · Apt 634
Closed — Violation closed - CImmediately hazardous
Provide an adequate supply of heat from an approved central heating system, or an approved system of gas or electrical heating in good operating condition for the dwelling unit in the 1st room from north at west located at b-room 625, 6th story, 1st b-room from south at west
Dec 3, 2019 · Apt 625
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Oct 28, 2019
Closed — Violation dismissed - CImmediately hazardous
Provide hot water at all hot water fixtures in the 1st room from north located at b-room 431, 4th story, 2nd b-room from west at north
May 13, 2019 · Apt 431
Closed — Violation closed - CImmediately hazardous
Provide hot water at all hot water fixtures in the room located at b-room 321, 3rd story, 5th b-room from south at west
Feb 13, 2019 · Apt 321
Closed — Violation closed - CImmediately hazardous
M/d law abate the nuisance consisting of scalding hot water exceeding 130 degress at community bathroom, 2nd story
Feb 6, 2019
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 14, 2017
Closed — Violation dismissed - ANon-hazardous
Refit the lower and upper window sashes to close properly, 1st window from south at west located at b-room 425, 4th story, 3rd b-room from east at south
Mar 15, 2017 · Apt 425
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Oct 31, 2016
Closed — Violation dismissed - BHazardous
Properly repair the broken or defective improperly counterbalanced lower window sash in the room located at b-room 422, 4th story, 2nd b-room from south at west
Apr 25, 2016 · Apt 422
Closed — Violation closed - BHazardous
Repair the broken or defective plastered surfaces and paint in a uniform color the east wall in the room located at b-room 542, 5th story, 4th b-room from north at east
Apr 25, 2016 · Apt 542
Closed — Violation closed - BHazardous
Arrange and make self-closing the doors at entrance in the room located at b-room 524, 5th story, 2nd b-room from south at west , section at south
Oct 19, 2015 · Apt 524
Closed — Violation closed - BHazardous
Arrange and make self-closing the doors at entrance in the room located at b-room 530, 5th story, 1st b-room from west at north , section at north
Oct 19, 2015 · Apt 530
Closed — Violation closed - BHazardous
Arrange and make self-closing the doors at entrance in the room located at b-room 540, 5th story, 2nd b-room from north at east , section at north
Oct 19, 2015 · Apt 540
Closed — Violation closed - BHazardous
Arrange and make self-closing the doors at entrance in the room located at b-room 611, 6th story, 1st b-room from north at east , section at south
Oct 19, 2015 · Apt 611
Closed — Violation closed - BHazardous
Arrange and make self-closing the doors at entrance in the room located at b-room 430, 4th story, 1st b-room from west at north , section at north
Oct 19, 2015 · Apt 430
Closed — Violation closed - BHazardous
Arrange and make self-closing the doors at entrance in the room located at b-room 313, 3rd story, 2nd b-room from north at east , section at south
Oct 19, 2015 · Apt 313
Closed — Violation closed - BHazardous
Arrange and make self-closing the doors at entrance in the room located at b-room 631, 6th story, 2nd b-room from west at north , section at north
Oct 19, 2015 · Apt 631
Closed — Violation closed - BHazardous
Arrange and make self-closing the doors at entrance in the room located at b-room 630, 6th story, 1st b-room from west at north , section at north
Oct 19, 2015 · Apt 630
Closed — Violation closed - BHazardous
Repair the broken or defective plastered surfaces and paint in a uniform color the ceiling at shower at community bathroom, 4th story, section at south
Apr 22, 2015
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Feb 5, 2015
Closed — Violation dismissed - CImmediately hazardous
Provide an adequate supply of heat from an approved central heating system, or an approved system of gas or electrical heating in good operating condition for the dwelling unit in the room located at b-room 225, 2nd story, 4th b-room from east at south , section at south
Nov 19, 2014 · Apt 225
Closed — Violation dismissed - CImmediately hazardous
Provide an adequate supply of heat from an approved central heating system, or an approved system of gas or electrical heating in good operating condition for the dwelling unit in the room located at b-room 321, 3rd story, 4th b-room from south at west , section at south
Nov 19, 2014 · Apt 321
Closed — Violation dismissed
DOB building violations · 57
- Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 22, 2025
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 4, 2023
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 4, 2023
Dob violation - dismissed - No report and / or late filing (facade) facade required
Failed to file fisp cycle 9b technical report by 2/21/2023
Feb 22, 2023
Dob violation - active - Failure to post energy grade/score none
Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3
Dec 1, 2021
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 11, 2020
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Sep 2, 2020
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Feb 19, 2020
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
May 29, 2019
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
May 2, 2019
Dob violation - dismissed
Show 40 more ↓
- Elevator annual inspection / test elevatorrequired
Violation issued to elevator - failure to file category 1 2017 inspection/test
Apr 5, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 2, 2019
Dob violation - resolved - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
May 2, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 2, 2018
Dob violation - resolved - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Mar 7, 2018
Dob violation - dismissed - Construction other optional
Owner failed to submit acceptable 6&7 cycles exterior walls and appurtenance critical examination technical report filed by a register design prof.as req'd by ac28-302 & dob rules and regulations.remedy: submit acceptable exterior walls & appurtenance critical examination technical report by registered professional to dept of buildings immed
Jan 17, 2018
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Dec 27, 2017
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 15, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jun 15, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 25, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 2, 2015
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 18, 2014
Dob violation - resolved - No report and / or late filing (facade) facade required
Failed to file fisp cycle 7b technical report by 08/21/2012
Aug 30, 2013
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 5, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 13, 2012
Dob violation - resolved - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jul 27, 2011
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 3, 2011
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Vcat1-elevator annual inspection / test elevatorrequired
Oct 8, 2010
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 13, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 9, 2009
Dob violation - resolved - Emergency power none
Ll2604e-emergency power none
Mar 31, 2008
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 17, 2008
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Facade facade optional
Ll1198-local law 11/98 - facade facade optional
Nov 30, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 19, 2007
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 8, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 20, 2005
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 26, 2004
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 2, 2003
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Facade facade required
L1198-local law 11/98 - facade facade required
Aug 8, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Elevator elevatorrequired
2p3089
Feb 20, 2002
Dob violation - resolved
ECB violations · 83
- Class - 1
Failure to maintain elevator in building code compliant as per bc 3001.2 & 27-987. upon an follow up inspection the elevator is found out of service for more than 3 weeks creating a hazardous condition for huma
Sep 25, 2026 · Penalty $6,250
Active - Class - 1
Failure to maintain elevator in building code compliant as per bc3001.2 & 27-987. upon an inspection the elevator is found to be out of sevice this is a recurring condition, creating a hazardous condition for h
Sep 15, 2026 · Penalty $3,125
Active - Class - 1
Failure to maintain elevator in building code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon an inspection the elevator is found to be out of service, this a recurring condition, cr
Sep 4, 2026 · Penalty $3,125
Active - Class - 1
Class 1 rts: failure to maintain building in code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon inspection, the device is found to be out of service, creating a hazardous condition
Aug 18, 2026 · Penalty $1,250
Active - Class - 1
Class 1: excessive oil leakage from the driving machine has contaminated the hoistway selector vanes and associated equipment. driving machine brake lining is worn with excessive brake dust accumulation through
Jul 21, 2026 · Penalty $1,250
Resolve - Class - 1
Class 1 cease use: door zone restrictor defective. code: asme a17.1/csa b44 sec. 2.12.5. remedy: repair/replace and verify operation. controller fuse bypassed. code: asme a17.1/csa b44 sec. 8.6.1.2.2. remedy: r
Apr 17, 2026 · Penalty $1,250
Resolve - Class - 2
I found a h.b. smith 28 8 boiler were the domestic hot water was going up 200 degrees on the temperature gauge/water is to hot/ correct all violating conditions/ submit a certificate of correction
Jan 15, 2026 · Penalty $1,250
Active - Class - 2
Exit door not self-closing. observed non self closing doors throughout building. potential fire hazard., repair/replace door
Apr 23, 2025 · Penalty $625
Active - Class - 1
Failure to maintain building in code-compliant manner. observed partition wall leaning inward towards building at roof level. also has a 3 foot crack on top of 6th floor window. potential hazards., repair and/r
Apr 23, 2025 · Penalty $1,250
Active - Class - 2
Class 2 item: communication in car inoperative. replace worn counter weight rollers as needed. adjust car door to properly open and close. adjust bottom basement hoistwy door. clean oil from machine room floor
Apr 22, 2025 · Penalty $625
Active
Show 40 more ↓
- Class - 1
Responding to a 311 elevator complaint, upon inspection, cease use violation issued for. car door restrictor , altered not to make it work, remedy; repair then contact nycdob, for restore to service re inspecti
Jan 31, 2025 · Penalty $3,125
Resolve - Class - 1
Failure to maintain building in code compliant manner. a previously issued cease use order is currently still in effect. repair the cease use items and service the elevator equipment as per bc3001.2 & 27-987. u
Dec 30, 2024 · Penalty $1,250
Resolve - Class - 1
Cease use items: 1)inoperative zone lock restrictor. 2) right brake pin walking out. 125% brake test and sealing and tagging of all adjustments required at time of reinspection. class 2 items: provide designate
Nov 25, 2024 · Penalty $1,250
Active - Class - 2
At time of my inspection i observed a sidewalk shed at a occupied 6 story building. upon reviewing department of building records i noticed that permit is expired since 2020 and no renewed permit was submitted.
Aug 30, 2024 · Penalty $1,250
Active - Class - 2
Failure to submit an acceptable required cycle 9b report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control #907733. remedy: submit acceptable requ
Apr 11, 2024 · Penalty $1,250
Active - Class - 2
At the time of my inspection. i observed a few infractions. in the basement. open defective wiring are in used, fluorescent lights are not secured, the wiring are not continuous in to the lights, splice boxes a
Dec 22, 2022 · Penalty $2,000
Resolve - Class - 1
Door zone restrictor not working tampered with disabled(cu). machine brake defective brake pin walk all the way out missing cutter pin(cu). governor missing the seal. repair machine room light. seal machine oil
Aug 9, 2022 · Penalty $1,250
Resolve - Class - 2
Found exposed wires, dirty glass gauge, oil leak on oil line at burner, corroded water pipe above burner, clean out doors on side of boiler need to be resealed, body drain missing on safety relief valve.
Aug 9, 2022 · Penalty $625
Active - Class - 2
I observed on the first floor in a rear storage area a bathroom and in the basement near the boiler room a convenience outlet not of the gfci type as required within 6 feet of a sink., install gfc1 protection
Aug 9, 2022 · Penalty $10,000
Active - Class - 1
I observed in a basement storage room along the 164th street side an electrical panel made inaccessible by shelving and supplies. all electrical panels shall have a clearance for access in case of normal or eme
Aug 9, 2022 · Penalty $8,000
Active - Class - 2
I observed in the elevator motor switch the improper fusing of the conductors, the #4 conductors have an ampacity less than the 100 amp fuses that are installed as the overcurrent protection of the conductors.,
Aug 9, 2022 · Penalty $10,000
Active - Class - 1
I observed the raceway and junction boxes/lights for the sidewalk shed not connected or secured properly and without proper grounding as required., comply with ec; provide proper grounding and gfci protection.
Aug 9, 2022 · Penalty $8,000
Active - Class - 2
I observed under the sidewalk shed and on the second floor the power supply for the lights not mechanically connected to the junction box with the conductors exposed and energized. failure to connect the racewa
Aug 9, 2022 · Penalty $6,000
Active - Class - 2
Failure to obtain a temporary construction(sidewalk shed) permit to remain install and use of temp equipment. observed sws erected at exposure#1&4. did not find active permit in bis and dob now. permit in dob n
Jun 14, 2022 · Penalty $1,250
Active - Class - 2
Exit door not self closing.observed:fire proof self-closing door,from 6th fl to 1st fl,near rooms #40 & cellar level.interior exit door do not allow easy escape from the bldg doors do not meet technical & safe
Apr 29, 2022 · Penalty $625
Active - Class - 2
Failure to maintain bldg in code-compliant manner no fire stopping perbc 712.3;27-345.observed:at cellar level,several holes in the wall/ceiling due to pipes penetration,& loss of bricks/mortar in the rooms &
Apr 29, 2022 · Penalty $1,250
Resolve - Class - 2
Failure to maintain bldg n code compliant manner.observed:at roof level,waterproofing mantle or membrane shows material lifting failures,cracks,openings in entire roof area.remedy:repair &/or replace.
Apr 29, 2022 · Penalty $625
Active - Class - 2
Failure to maintain bldg in code-compliant manner.observed:at cellar level,ceiling/walls,opening were created exposing,rebars & metallic structure to support 1st fl slab structure.remedy:repair &/or replace.
Apr 29, 2022 · Penalty $500
Active - Class - 2
Failure to maintain bldg wall(s) or appurtenances.observed:at roof level,parapet walls,cracked on 2 sides,facade & interior side. remedy:maintain exterior bldg wall.
Apr 29, 2022 · Penalty $500
Active - Class - 2
Work w/out a permit.observed:at cellar level,fire alarm room,a wall was built in cmu blocks,creating an additional room.also,metal structure(beams/columns)was installed to support part of the 1st fl slab.activi
Apr 29, 2022 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner.noted:observed throughout basement ceiling's concrete slab is deteriorated exposing steel beams throughout at various locations also holes in concrete where
Jul 30, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain building wall(s) or appurtenances.noted:obsereved horizontal and vertical cracks at roof's parapet wall (roof side)at various locations.remedy:maintain exterior building wall.
Jul 30, 2021 · Penalty $1,250
Active - Class - 1
Door zone restrictor not working tampered with disabled(cu). clean oil off top of car. seal front head hoist machine. front cable guard missing. machine room room door lock damaged.
Jul 16, 2021 · Penalty $1,280
Resolve - Class - 1
Cease use 3 items 1, lobby hoist way door open wide when car running ,2 car stop for one minute before coming fully in the 6th floor door zone, on six floor car floor to landing sill not level , in car fan not
Aug 10, 2020 · Penalty $1,250
Resolve - Class - 2
Failure to comply w/the comm's order contained in summons/vio#35265118r issued on 02/09/18,& to file a cert to correction pursuant to 28.201.1 & 1rcny 102-01(d)(2). remedy: file a cert of correction.
Jun 29, 2020 · Penalty $1,250
Resolve - Class - 1
Door zone restrictor not working tampered with disabled (cu). dlm tag missing on the controller . clean top of car oil leak. replace operator cover.
Mar 16, 2020 · Penalty $1,250
Resolve - Class - 2
Noted: observed throughout cellar, ceiling has spalling and missing cement exposing steel re -enforcement bars, beams and window lintels., repair and/or replace
Nov 21, 2019 · Penalty $625
Resolve - Class - 1
I observed throughout the hallways on every floor, light fixtures that are not properly connected ( no mechanical connection between conduit/cable and electrical box/fixture) exposed energized conductors @ the
Nov 21, 2019 · Penalty $800
Active - Class - 2
Noted: observed throughout cellar, pipes penetrations and openings with no fire stopping provided at various locations throughout. , provide/maintain fire stopping
Nov 21, 2019 · Penalty $1,250
Resolve - Class - 3
I observed in the basement, new electrical armored cable and emt conuit that has been installed to remove a previous violation, however an electrical permit was not filed with the department of buildings coveri
Nov 21, 2019 · Penalty $400
Resolve - Class - 2
Noted: occupancy contrary to certificate of occupancy ##8081, entire first floor occupied as offices and copy room over the allowable 10% for accessory occupancies as per bc 508, 508.2.1 , discontinue illegal o
Nov 21, 2019 · Penalty $3,125
Active - Class - 2
Noted: observed horizontal and vertical cracks throughout parapet wall exposure #3,#4 and various locations throughout parapet. , maintain exterior building wall
Nov 21, 2019 · Penalty $3,125
Active - Class - 2
Failure to maintain bldg in code compliant manner. illumination for exits,exit discharges & public corridors per bc1006.1;27-381. noted: existing emergency light packages were not operational when tested at 6th
May 13, 2019 · Penalty $312
Active - Class - 2
52.m.15,75.l.10,45.m.13,39.x.10,70.o.02;52-m=provide and tag device 75-l=repair right hand buffer 45-m=provide adjustment screw led seal 39-x=repair car top light 70-o=clean hoist way pit.
May 3, 2019 · Penalty $625
Resolve - Class - 2
Guards for gage glass missing-no shut off valve on fuel oil line-no body drain on safety valve-hw piping corroded-fire stopping needed for ceiling;correct all violating conditions, submit a certificate of corre
May 3, 2019 · Penalty $625
Resolve - Class - 2
70o02,75i10,68b07,68m07,59b07,40o02,61t04,26d06,39o02,27i10,52u07,53u07,39x10,11m07. 70-dirty pit; 75-buffer spring damage; 68-missing mainlog book; 68-mcp missing; 59-brake maint tag insuff; 40-dirty machine
Mar 6, 2019 · Penalty $625
Resolve - Class - 1
Cu1l10;cu5m7;cu5a10; 41l10;45m7;59bb7,99bb7. 1l10-emergency stop swit ch defective unable to pull frozen; 5m7-car doro missing vision glass 5a10-door zone restrictor not working; this is a safety feature to en
Feb 26, 2019 · Penalty $1,250
Resolve - Class - 2
50a,50b,50c,50d-as per class 2(b254) 28-301.1. failure to maintain. 50a)exposed electrical wires. 50b)hot water piping corroded. 50c)no shut-off valve on fuel oil supply line. 50d)fresh air intake blocked with
May 2, 2018 · Penalty $625
Resolve - Class - 1
Failure to maintain exterior building facade and appurtenances. as noted: exposure #1 and 4 cracks at parapet level, spalled bricks, cracked stones, spalled stones all exposures, exposure 4 cracks in store grou
Feb 9, 2018 · Penalty $5,000
Active - Class - 1
5x10,59m7,71x7,39o2,70o2-5x10)door restrictor inoperative, repair. this device is to ensure the safety of its passengers.59m7)brake assembly missing cotter pin, provide. 71x7)pit lighting inoperative, provide.
Dec 11, 2017 · Penalty $1,000
Resolve
Complaints
- Heat/hot water
Entire building
Apr 27, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Mar 20, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Feb 9, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 30, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 22, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 9, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Jun 27, 2025 · Apt 224
Close - Heat/hot water
Entire building
Dec 26, 2024 · Apt 325
Close - Heat/hot water
Entire building
Dec 24, 2024 · Apt 214
Close - Heat/hot water
Entire building
Dec 3, 2024 · Apt 214
Close
Show 40 more ↓
- Heat/hot water
Entire building
Oct 29, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 18, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
May 24, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
May 11, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Apr 12, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Apr 12, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Feb 28, 2024 · Apt 234
Close - Heat/hot water
Entire building
Feb 13, 2024 · Apt 625
Close - Heat/hot water
Entire building
Feb 1, 2024 · Apt 625
Close - Heat/hot water
Entire building
Feb 1, 2024 · Apt 311
Close - Heat/hot water
Entire building
Jan 31, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 30, 2024 · Apt 341
Close - Heat/hot water
Entire building
Nov 9, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 23, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 10, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 10, 2023 · Apt 619
Close - Heat/hot water
Entire building
Oct 10, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 9, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 9, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Mar 22, 2023 · Apt 324
Close - Heat/hot water
Entire building
Mar 19, 2023 · Apt 324
Close - Heat/hot water
Entire building
Mar 7, 2023 · Apt 324
Close - Heat/hot water
Entire building
Dec 28, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Nov 11, 2022 · Apt 334
Close - Heat/hot water
Entire building
May 1, 2022 · Apt 525
Close - Heat/hot water
Entire building
Apr 27, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Mar 27, 2022 · Apt 525
Close - Heat/hot water
Entire building
Feb 7, 2022 · Apt 323
Close - Heat/hot water
Entire building
Feb 6, 2022 · Apt 625
Close - Heat/hot water
Entire building
Jan 31, 2022 · Apt 625
Close - Heat/hot water
Entire building
Jan 31, 2022 · Apt 525
Close - Heat/hot water
Entire building
Jan 27, 2022 · Apt 230
Close - Heat/hot water
Entire building
Jan 23, 2022 · Apt 630
Close - Heat/hot water
Entire building
Dec 28, 2021 · Apt 240
Close - Heat/hot water
Entire building
Oct 29, 2021 · Apt 534
Close - Heat/hot water
Entire building
May 7, 2021 · Apt 422
Close - Heat/hot water
Entire building
Apr 4, 2021 · Apt 524
Close - Electric
Power outage
Dec 22, 2020 · Apt 512
Close - Electric
Power outage
Dec 21, 2020 · Apt 512
Close - Electric
Power outage
Dec 21, 2020 · Apt 512
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Hotel (HR)
- Year built
- 1907
- Floors
- 6
- Residential units
- —
- Building area
- 23,674 ft²
- Lot area
- 5,592 ft²
- Zoning
- R7-1
- Community board
- 202
- Council district
- 17
- Block / lot
- 2690 / 123
- Assessed value
- $3,714,300
- Landmark / historic district
- No
HPD registration #203928, last renewed Jul 20, 2026.
Questions about 980 Prospect Avenue
Who owns 980 Prospect Avenue?
The owner of record in NYC Department of City Planning PLUTO data is 980 Prospect Owner, LLC.
Does 980 Prospect Avenue have violations?
Yes. NYC HPD has recorded 59 housing violations at this property.
Is 980 Prospect Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 980 Prospect Avenue built?
City records list 1907 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.