800 Home Street
Bronx, NY 10456BBL 2-02671-0011Map
Owner of record: NYC Department Of Education
800 Home Street is a school building built in 1974 in Bronx, 10456. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 50
- ECB violations
- 76
- HPD complaints
- 5
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 50
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Retaining wall none
Failed to file cycle 1 technical report by 12/31/2018 per rcny 103-09
May 1, 2024
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 17, 2021
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Nov 8, 2019
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Nov 8, 2019
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Nov 8, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed
Show 40 more ↓
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 13, 2016
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 13, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 11, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 6, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 2, 2011
Dob violation - resolved - Construction other optional
C-construction other optional
Sep 24, 2009
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 12, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 24, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 6, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 10, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 17, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 20, 2004
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 7, 2003
Dob violation - resolved - Elevator elevatorrequired
2p4704
Dec 17, 2002
Dob violation - active - Elevator elevatorrequired
2p4704
Dec 17, 2002
Dob violation - resolved - Elevator elevatorrequired
2p4704
Feb 15, 2002
Dob violation - resolved - Elevator elevatorrequired
2p4704
Jun 29, 2001
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Elevator elevatorrequired
2p4704
May 15, 2000
Dob violation - resolved - Elevator elevatorrequired
2p4704
Apr 28, 1999
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 1996
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 7, 1992
Dob violation - dismissed - Elevator elevatorrequired
Device #2p4704
May 15, 1991
Vp*-violation unserved ecb- dismissed - Elevator elevatoroptional
1
Apr 25, 1991
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 4, 1990
Dob violation - resolved - Elevator elevatoroptional
1
Jun 29, 1990
Dob violation - dismissed
ECB violations · 76
- Class - 2
Reissue#35693286r failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:in basement the exit signs above gym doors & at sta
Jul 9, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35693285p failure to maintain building wall(s)or appurtenancesnoted:on the roof at staircase a bulkhead exterior wall has vertical cracks in bricks,parapet walls have step-cracks in several locations th
Jul 9, 2026 · Penalty $6,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:fpsc interior doors do not self-close properly at 3rd flr-staircase f.2nd flr-staircase a auditorium doors.classroom doors do not self close properly
Jul 9, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.noted:in subcellar,gas meter room is missing fire-stopping around pipes that go thru cmu blocks above entrance.rem:provi
Jul 9, 2026 · Penalty $1,250
Active - Class - 2
Reissue: 35679074y date of issue: 08-19-25. failure to maintain building wall(s) or appurtenances. at the time of inspection observed and noted at roof level staircase "a" bulkhead has vertical cracks in bulkhe
Aug 19, 2025 · Penalty $6,250
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection observed per bc 1006.1; 27-381. at the time o
Aug 19, 2025 · Penalty $1,250
Active - Class - 2
Reissue#failure to maintain building wall(s)on appurtenances at roof level by staircase a bulkhead has vertical cracks in bricks.re-issue 35672143r.rem:comply with code.
Aug 27, 2024 · Penalty $3,125
Active - Class - 2
Reissue#35644540m failure to maintain building in a code-compliant manner.at time of inspection observed at main entrance courtyard,concretepavement with uneven areas throughout.some repairs have been made howe
Jan 20, 2023 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.at time of inspection observed emergency lights not operational when tested
Jan 20, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner:no firestopping per bc 712.3;27-345.at time of inspection at cellar level gas meter room/ sprinkler pump room observed several penetration in walls around p
Jan 20, 2023 · Penalty $1,250
Resolve
Show 40 more ↓
- Class - 2
Failure to maintain building in code-compliant manner:use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).at time of inspectionthroughout the entire school observed approx.40 doors including classr
Jan 20, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building walls or appurtenances.at time of inspection at roof level by staircase a bulkhead observed a vertical crack inparapet wall,running along entire height of the parapet wall.rem:maint
Jan 20, 2023 · Penalty $1,250
Active - Class - 2
Reissue# 35644539p failure to maintain building in code-compliant manner.at time of inspection observed several fireproof self closing doorsnot closing properly.at 4th floor double doors by stairwell f.at 3rd f
Jan 20, 2023 · Penalty $1,562
Resolve - Class - 2
Reissued #35548303z.failure to maintain building in code compliant manner.noted:at time of inspection observed at main entrance courtyard concrete pavement has uneven areas throughout walkway handicap ram has m
Mar 4, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue #35548305m failure to maintain building in code compliant manner.noted:at time of inspection observed two fireproof doors not self closing.at 1st floor stairway e exit 9 in disrepair door is rubbing on
Mar 4, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35475665l failure to maintain bldg in code compliant manner. noted: observed at main entrance courtyard,concrete pavement has uneven areas throughout walkway,handicap ramp has missing chunks of concrete
Feb 4, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in code compliant: illumination for exits,exit discharges & publiic corridors per bc 1006.1;27-381. noted: observed existing emergency light packages w/back-up batteries at gy,masium,by
Feb 4, 2021 · Penalty $625
Resolve - Class - 2
Reissue#35475667p failure to maintain bldg in code compliant manner. use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted: observed at various locations on all floors of bldg,kick stops install
Feb 4, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: noted observed fire proof self closing door at 1st fl stairway e,exit 9 is in disrepair,door is rubbing on the floor & does not close & door frame is corroded
Feb 4, 2021 · Penalty $625
Resolve - Class - 1
No door lock monitoring installed in controller as mandated in 3.10.12 of appendix k3 of the 2014 nycdob. this feature is installed to ensure passenger safety. remedy: install dlm, file application, file and pe
Feb 13, 2020 · Penalty $1,250
Resolve - Class - 2
Reissue #35384082x failure to maintain building in code compliant manner lack of emergency lighting for eixts eixt discharges and public corridors per bc 1006.1=27-542.note observed defective emegrnecy lighting
Feb 11, 2020 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code compliant manner use of prohibited door and or hardware per bc 1008.1.8;27-371(j) note observed at all 4 floors of the bdlg and at various locations there are kickstops inst
Feb 11, 2020 · Penalty $625
Resolve - Class - 2
Reissue #35384083h failure to maintain buidling in code compiant manner note observed at exp #1 courtyard/bldg main entrance concrete wlakway has several uneven areas and or missing chunks of concrete creating
Feb 11, 2020 · Penalty $1,562
Resolve - Class - 2
Exit door not self closing note observed at ground level exit #23 door is not self closing when tested during inspection repair/replace door
Feb 11, 2020 · Penalty $625
Resolve - Class - 2
Reissue #35312018z failure to maintain building in code compliant manner lock of emergency lighting for exits ,exit discharges an dpublic corridence per bc 1006.1;27-542 noted:at time of inspection i observed d
Feb 6, 2019
Resolve - Class - 2
Reissue #35312017r failure to maintain building in code compliant manner noted:at time of inspection i observed at epxosure #1 at front of building main entrance concrete walkway uneven missing chucks main entr
Feb 6, 2019
Resolve - Class - 2
Re-issue# 35229032h. failure to maintain bldg in code compliant manner: lack of emergency lighting for exits, exit discharges & public corridors per bc 1006.1; 27-542. noted: defective emergency lighting observ
Jan 26, 2018
Resolve - Class - 2
Re-issue# 35229034l. exit door not self-closing. noted: @ 4th flr stairway (g), @ 3rd flr stairway (a), @ auditorium entrance, doors are not self-closing. rem: repair/replace door.
Jan 26, 2018
Resolve - Class - 2
Re-issue# 35229033j. failure to maintain bldg in code-compliant manner. noted: @ exp#1 @ bldg front court concrete walkway uneven, missing chunks of concrete, tripping hazard throughout front. rem: repair &/or
Jan 26, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: lack of emergency lighting for exits, exit discharges & public corridors per bc1006.1; 27-542. noted: defective emergency lighting was observed @ 4th flr, 3rd
Feb 22, 2017
Resolve - Class - 2
Reissue# 35148286n. for:failure to maintain bldg in code compliant manner. noted: @ front main entrance concrete walkway uneven, missing chunks of concrete, tripping hazard throughout front. rem: repair &/or re
Feb 22, 2017
Resolve - Class - 2
Sec: exit door not self closing. noted: not self closing door was observed @ (1) exit #6, (2) 4th flr, staircase y-g. rem: repair/replace door.
Feb 22, 2017
Resolve - Class - 2
Failure to maintain building in code compliant manner. at front main entrance concrete walkway uneven missing chnks of concrete, tripping hazardous throughout front. remedy: comply with notice of violation
Apr 1, 2016
Resolve - Class - 2
Lockers partially block egress in girls locker room. remedy: remove obstructions.
Feb 26, 2014
Resolve - Class - 2
Re-issue # 35016857n. defective kitchen hood, not working at time of inspection 1st floor (exhaust fan not working). remedy: repair &/or replace.
Feb 26, 2014
Resolve - Class - 2
Boys & girls gym locker rooms use as storage, desks,chairs,computers,t.v. etc. remedy: maintain locker rooms as per code.
Feb 26, 2014
Resolve - Class - 2
Roof exhaust #18 kitchen exhaust not secured. remedy: immediately secure roof exhaust.
Feb 26, 2014
Resolve - Class - 2
Missing fire stopping c-1 electric meter room. remedy: maintain electric room as per code.
Feb 26, 2014
Resolve - Class - 2
Defective kitchen hood,not working at time of inspection 1fl (exhaust fan not working) remedy: repair hood exhaust fan.
May 13, 2013
Resolve - Class - 2
Severely cracked/partial collapse of concrete pavement outside exit 8 around drywell hollow space noted trip hazard. remedy: make safe.
May 13, 2013
Resolve - Class - 2
Missing fire stop. at electric service room #c1, approx 1 1/2' x 2 1/2' section of cmu fire wall missing w/conduit penetration. remedy: sealhole in fire wall, maintain fire stop.
Jul 5, 2012
Resolve - Class - 2
Reissue 34863515y corridor smoke doors near room 320 not closing.rem:replace doors.
Jul 19, 2011
Resolve - Class - 2
Ceiling tiles displaced/damaged.rem:@ various locations throughout kitchen ceiling tiles damaged/displaced.rem:repair &/or replace defects noted.
Jul 19, 2011
Resolve - Class - 2
Reissue: 34743415k corridor smoke doors near room 320 not closing. 2ndfl corridor smoke doors near room 220 & 201 are locked. corridor doors near room 223 not closing. 1st fl cafeteria doors near room 102 not
Jul 20, 2010
Resolve - Class - 2
Stwy'a' between cellar & basement level vertical cracks in concrete block wall approx 9 feet long & 1 inch wide. remedy: repair cracks in wall.
Jul 20, 2010
Resolve - Class - 2
Holes in walls of gas meter room at cellar level. remedy: provide/maintain fire stopping.
Jul 20, 2010
Resolve - Class - 2
Gas meter room at cellar level is being used for storage of paint,doors,sheet rock,boxes ect. remedy: remove storage items from gas meter room.
Jul 20, 2010
Resolve - Class - 2
Reissue: 34628221z no fresh air vent in gas meter room. remedy: provide fresh air vent for gas meter room.
Jul 20, 2010
Resolve - Class - 2
On 3fl stairwell "c" missing door check 2floor corridor doors near rooms 320 and 301 n door check.remedy:repair & replace door checks.
Mar 17, 2009
Resolve - Class - 2
Gas meter vent has conduit stored in blocking fresh air into gas meterroom.remedy:remove electrical conduit.
Mar 17, 2009
Resolve
Complaints
- Heat/hot water
Apartment only
Nov 23, 2020 · Apt 2T
Close - Electric
Outlet/switch
Nov 23, 2020 · Apt 2T
Close - Safety
Window guard broken/missing
Nov 23, 2020 · Apt 2T
Close - Appliance
Refrigerator
Nov 23, 2020 · Apt 2T
Close - Unsanitary condition
Pests
Nov 23, 2020 · Apt 2T
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1974
- Floors
- 4
- Residential units
- —
- Building area
- 182,000 ft²
- Lot area
- 150,480 ft²
- Zoning
- R6
- Community board
- 203
- Council district
- 17
- Block / lot
- 2671 / 11
- Assessed value
- $17,975,250
- Landmark / historic district
- No
Questions about 800 Home Street
Who owns 800 Home Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 800 Home Street have violations?
NYC HPD has no housing violations on record for this property.
Is 800 Home Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 800 Home Street built?
City records list 1974 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.