Violations at 756 East 158 Street

Bronx, NY 10455 · BBL 2-02655-0030 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

45 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 16, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 28, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Residential elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Jun 1, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 16, 2016

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2014 inspection/test

    Jun 10, 2015

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 28, 2015

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2012 inspection report

    May 15, 2014

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2012 inspection report

    May 15, 2014

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2012 inspection report

    May 15, 2014

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 14, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 8, 2013

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 29, 2013

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2011 inspection/test

    Oct 1, 2012

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2010 cat 1 insp/tst

    Aug 15, 2012

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 17, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 10, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 4, 2010

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 30, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 6, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 10, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 25, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 7, 2003

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed

ECB violations

The newest 50 of 55 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building wall(s)or appurtenances.noted:above exit on e 158 st,flashing on ceiling throughout the whole front end is in disrepair.rem:maintain exterior building walls.

    Jun 25, 2026 · Penalty $2,500

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:fpsc interior doors do not self-close properly when tested at 1st flr-staircase b.classroom doors do not self-close properly when tested at 4th flr rm

    Jun 25, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing. noted: at(3rd fl) 309a classroom(2nd fl) stairs g, f, e(1st fl) stair b exits 3, 8, 7 doors are indisrepair/not closing when tested. remedy: repair/replace door.

    Aug 8, 2025 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.lack of fire stopping per bc712.3;27-345.note at cellar level in electrical room no fire stopping around pipes penetrating through walls.remedy:provide and

    Apr 4, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Exit door not self closing. noted: observed exterior exit door at exit#4 do not self close,door is very hard to open,door frame are rusted at bottom/near ground. remedy: repair/replace door.

    Apr 28, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: noted: observed fire proof self closing doors at 3rd fl-across from door 309,3rd fl stair'b'are not closing properly. remedy: repair &/or replace.

    Apr 28, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted: observed at all floors,key cylinders installed on every fpsc doors panic/push bar hardwa

    Apr 28, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg walls or appurtenances. noted: observed horizontal cracks/step cracks throughout exterior brick wals at east elevation next to playground above exit door,south elevation above exit#5,

    Apr 28, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Reissie #35235161p failure to mainain buidling walls or appurtenances noted at time of inspection i observed at corner of east 156th street and westchester ave cement pavement cracked and (bulking) approximate

    Apr 16, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    Re-issue #35322580p.failure to maintain building walls or appurtenances.noted:at time of inspection,i observed @the corner of e 156th street(of)westchester ave.,cement pavement cracks & buckling approx.80 sq ft

    Apr 26, 2019

    Resolve
  • Class - 2

    Reissue violation #35208092r issued 9/20/16. failure to maintain building wall(s) or appurtenances. note: at corner of east 156th street and westchester avenue. cement pavement cracked and buckling approximatel

    Mar 16, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s)or appurtenances @corner of east 156thstreet &westchester ave cement pavement cracked &buckling approx 80 square ft cracked &bucking also on forest ave in front of school &yard t

    May 2, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s) or appurtenances.noted:@corner of east 156th street and westchester ave,cement pavement cracked and buckling,approx 80 square feet cracked and buckling.also on foreest ave, in f

    Sep 20, 2016

    Resolve
  • Class - 2

    Failure to provide power for emergency exit lighting.noted:observed @cellar illuminating emergency exit light inoperable.emergency exit light located above doorway to room b13.also inoperable emergency exit lig

    Sep 20, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.re-issue nov #35120262x issued on 2/11/15 for failure to maintain bldg in code-compliant manner.excessive combustible throughout all walls @all stories.also ban

    Sep 20, 2016

    Resolve
  • Class - 2

    Excessive combustibles @all flrs excessive combustibles throughout all walls & banners hanging on ceilings & all corridors.also banners hanging on pipes & fire systems.rem:remove all items & banners do not exce

    Feb 11, 2015

    Resolve
  • Class - 2

    Defective metal ceiling @kitchen ceiling tiles which is made of metal missing uneven & defective more than half of ceiling. remedy: replace immediatly.

    Feb 11, 2015

    Resolve
  • Class - 2

    Front entrance defect @front entrance to the exterior rightside black cable wires sagging hanging. remedy:remove or replace.

    Feb 11, 2015

    Resolve
  • Class - 2

    Front exterior entrance- exit 1 over hang bird infested due to missing10'-0"closure and/or j.channel. rem maintian building as per code.

    Feb 20, 2014

    Resolve
  • Class - 2

    Front entrance (to the exterior right side) black cable/telephone wire sagging and/or defective in placement. rem remove or replace as per code.

    Feb 20, 2014

    Resolve
  • Class - 2

    Kitchen ceiling defective- metal ceiling tiles,clips missing. missing tiles, 50% of ceiling loose and/or sagging. rem repair and/or replace ceiling tiles do not hang signs from ceiling.

    Feb 20, 2014

    Resolve
  • Class - 2

    Rear stage(auditorium) verticle crack in center column (cmu) approx 20'-0" hight. rem: repair and/or replace cmu.

    Feb 20, 2014

    Resolve
  • Class - 2

    Reissue vio #34987942n pipe penetrations not fire stopped at cellar electrical room. rmdy: provide/maintain fire stopping.

    May 29, 2013

    Resolve
  • Class - 2

    4 cars parked on sidewalk in front of bldg rem: discontinue illegal use

    Aug 8, 2012

    Resolve
  • Class - 2

    At cellar lvl electrical room holes in wall above door and at pipe penatrations rem: provide maintain fire stopping

    Aug 8, 2012

    Resolve
  • Class - 2

    3rd floor stwy b door not closing rem: repair replace doors

    Aug 8, 2012

    Resolve
  • Class - 2

    4th floor corridors complex door have plexi vision panels rem: provide approved vision panels

    Aug 8, 2012

    Resolve
  • Class - 2

    Reissue 34910299h no fresh air vent in gas meter room rem: provide fresh air vent

    Aug 8, 2012

    Resolve
  • Class - 2

    Reissue#34839791k.the gas meter room is lacking fresh air ventilation located @ the cellar level.rem:provide/maintain fresh air ventilation

    May 26, 2011

    Resolve
  • Class - 2

    Interior door closers are defective(loose & not working properly)located @ smoke doors leading to the complex by room 217w & library exit door on the 2nd flr level.rem:repair &/or replace exit doors

    May 26, 2011

    Resolve
  • Class - 2

    Numerous cracks in play yard pavement some very long & deep present a trip hazard. remedy: repair play yard pavement

    Mar 4, 2010

    Resolve
  • Class - 2

    No fresh air rear in gas meter room. remedy: provide fresh vent

    Mar 4, 2010

    Resolve
  • Class - 2

    Gas meter room is being used to store bags of oil absorbent & a door. remedy: remove storage items from gas meter room.

    Mar 4, 2010

    Resolve
  • Class - 2

    Sec 28-301.1 misc viol: 2nd fl library 2nd exit door partially blockedby table, computer work station & botes. remedy: remove obstruction

    Mar 4, 2010

    Resolve
  • Class - 2

    4th fl stwy "e" door check is broken. 2nd fl stwy "b" & "f" door checks are broken. 1st stwy "e" & auditorium stage exit loft doors door check are broken. remedy: repair/replace doors

    Mar 4, 2010

    Resolve
  • Class - 1

    In gym of above premises 2 metal light fixture covers are hanging fromceiling. 1 of the 2 is in danger of falling. remedy: repair/remove metal covers forthwith

    Mar 4, 2010

    Resolve
  • Class - 2

    Reissue 34639657n. 2 basketball backboards in gym have lose wall anchors at top. remedy: repair or remove backboards.

    Mar 4, 2010

    Resolve
  • Class - 2

    12q3.13i11.29l10.60q3.77q3.29l10 repair door operator so that it doesn't no slam when it close and open fully 77x10 repair light under car 77q3 install guard for light under car

    Nov 13, 2009

    Resolve
  • Class - 2

    Reissue 34576707r water penetration through roof at fan room on 4th flr & gym roof. remedy: repair roof.

    Feb 4, 2009

    Resolve
  • Class - 3

    Reissue vertical crack in block wall at gym next to wall divider. remedy: repair wall.

    Feb 4, 2009

    Resolve
  • Non-hazardous

    All light in class room cover's are broken and lose or hanging down 75% of class room's. remedy: repair/or replace light cover's.

    Mar 18, 2008

    Resolve
  • Non-hazardous

    2 vertical crack in block wall 1st location step crack in gym block wall next to wall divider 2nd location bulk head stair d. remedy: repair defect at above locations.

    Mar 18, 2008

    Resolve
  • Non-hazardous

    Two gym basketball backboard attached to block wall(anchors) at top are lose and not holding to wall. remedy: remove backboard or repair lose (anchors)that hold up top of back board frame.

    Mar 18, 2008

    Resolve
  • Non-hazardous

    Lunch room kitchen drop tin ceiling is defected throughout lose and not plum and out of track to hold tin ceiling in a tight fit from falling. remedy: repair tin drop ceiling in lunch room kitchen or replace.

    Mar 18, 2008

    Resolve
  • Non-hazardous

    Reissue: vi 34523476j rain-water is penetrating into building and causing interior damage in the interior finish location of water peneterction above fan room on 4th flr. remedy: stop water penetration at above

    Mar 18, 2008

    Resolve
  • Non-hazardous

    Reissue #34523476j. roofing has become porous & allowing rain water to enter the bldg in the fan rm on the 3 & 4 fls. remedy: repair roof.

    May 23, 2007

    Resolve
  • Hazardous

    Reissue: 34466145r. roofing is hot water tight and allowing water to enter the building and causing damage to the interior finish located above the fan room on the fourth floor. remedy: repair roof.

    Apr 28, 2006

    Resolve
  • Non-hazardous

    Failure to maintain building. defect noted: roof fan room corner blockwall has water penetration from roof down to floor. remedy: maintain building. make all necessary repairs.

    Jan 14, 2005

    Resolve
  • Non-hazardous

    Failure to provide panic wardware where required by law noted:first floor auditorium stage exit door has no panis bar.(capacity over 300 persons). remedy:provide panic hardware.

    Jan 14, 2005

    Resolve
  • Hazardous

    9a-illegal weld on thread pipering on boiler in back of boiler-need 'r1'form to show certificate of weld.

    Jul 10, 2001

    Resolve