Violations at 756 East 158 Street
Bronx, NY 10455 · BBL 2-02655-0030 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
45 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 16, 2018
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 28, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Residential elevator periodic inspection/test elevatorrequired
Failure to perform category 5 inspection
Jun 1, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 16, 2016
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2014 inspection/test
Jun 10, 2015
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 28, 2015
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2012 inspection report
May 15, 2014
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2012 inspection report
May 15, 2014
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2012 inspection report
May 15, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 14, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 8, 2013
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 29, 2013
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2011 inspection/test
Oct 1, 2012
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2010 cat 1 insp/tst
Aug 15, 2012
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 17, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 10, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 4, 2010
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 12, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 30, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 6, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 10, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 25, 2004
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 7, 2003
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed
ECB violations
The newest 50 of 55 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building wall(s)or appurtenances.noted:above exit on e 158 st,flashing on ceiling throughout the whole front end is in disrepair.rem:maintain exterior building walls.
Jun 25, 2026 · Penalty $2,500
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:fpsc interior doors do not self-close properly when tested at 1st flr-staircase b.classroom doors do not self-close properly when tested at 4th flr rm
Jun 25, 2026 · Penalty $1,250
Active - Class - 2
Exit door not self-closing. noted: at(3rd fl) 309a classroom(2nd fl) stairs g, f, e(1st fl) stair b exits 3, 8, 7 doors are indisrepair/not closing when tested. remedy: repair/replace door.
Aug 8, 2025 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.lack of fire stopping per bc712.3;27-345.note at cellar level in electrical room no fire stopping around pipes penetrating through walls.remedy:provide and
Apr 4, 2022 · Penalty $1,250
Resolve - Class - 2
Exit door not self closing. noted: observed exterior exit door at exit#4 do not self close,door is very hard to open,door frame are rusted at bottom/near ground. remedy: repair/replace door.
Apr 28, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: noted: observed fire proof self closing doors at 3rd fl-across from door 309,3rd fl stair'b'are not closing properly. remedy: repair &/or replace.
Apr 28, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted: observed at all floors,key cylinders installed on every fpsc doors panic/push bar hardwa
Apr 28, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg walls or appurtenances. noted: observed horizontal cracks/step cracks throughout exterior brick wals at east elevation next to playground above exit door,south elevation above exit#5,
Apr 28, 2021 · Penalty $1,250
Resolve - Class - 2
Reissie #35235161p failure to mainain buidling walls or appurtenances noted at time of inspection i observed at corner of east 156th street and westchester ave cement pavement cracked and (bulking) approximate
Apr 16, 2020 · Penalty $3,125
Resolve - Class - 2
Re-issue #35322580p.failure to maintain building walls or appurtenances.noted:at time of inspection,i observed @the corner of e 156th street(of)westchester ave.,cement pavement cracks & buckling approx.80 sq ft
Apr 26, 2019
Resolve - Class - 2
Reissue violation #35208092r issued 9/20/16. failure to maintain building wall(s) or appurtenances. note: at corner of east 156th street and westchester avenue. cement pavement cracked and buckling approximatel
Mar 16, 2018
Resolve - Class - 2
Failure to maintain bldg wall(s)or appurtenances @corner of east 156thstreet &westchester ave cement pavement cracked &buckling approx 80 square ft cracked &bucking also on forest ave in front of school &yard t
May 2, 2017
Resolve - Class - 2
Failure to maintain bldg wall(s) or appurtenances.noted:@corner of east 156th street and westchester ave,cement pavement cracked and buckling,approx 80 square feet cracked and buckling.also on foreest ave, in f
Sep 20, 2016
Resolve - Class - 2
Failure to provide power for emergency exit lighting.noted:observed @cellar illuminating emergency exit light inoperable.emergency exit light located above doorway to room b13.also inoperable emergency exit lig
Sep 20, 2016
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner.re-issue nov #35120262x issued on 2/11/15 for failure to maintain bldg in code-compliant manner.excessive combustible throughout all walls @all stories.also ban
Sep 20, 2016
Resolve - Class - 2
Excessive combustibles @all flrs excessive combustibles throughout all walls & banners hanging on ceilings & all corridors.also banners hanging on pipes & fire systems.rem:remove all items & banners do not exce
Feb 11, 2015
Resolve - Class - 2
Defective metal ceiling @kitchen ceiling tiles which is made of metal missing uneven & defective more than half of ceiling. remedy: replace immediatly.
Feb 11, 2015
Resolve - Class - 2
Front entrance defect @front entrance to the exterior rightside black cable wires sagging hanging. remedy:remove or replace.
Feb 11, 2015
Resolve - Class - 2
Front exterior entrance- exit 1 over hang bird infested due to missing10'-0"closure and/or j.channel. rem maintian building as per code.
Feb 20, 2014
Resolve - Class - 2
Front entrance (to the exterior right side) black cable/telephone wire sagging and/or defective in placement. rem remove or replace as per code.
Feb 20, 2014
Resolve - Class - 2
Kitchen ceiling defective- metal ceiling tiles,clips missing. missing tiles, 50% of ceiling loose and/or sagging. rem repair and/or replace ceiling tiles do not hang signs from ceiling.
Feb 20, 2014
Resolve - Class - 2
Rear stage(auditorium) verticle crack in center column (cmu) approx 20'-0" hight. rem: repair and/or replace cmu.
Feb 20, 2014
Resolve - Class - 2
Reissue vio #34987942n pipe penetrations not fire stopped at cellar electrical room. rmdy: provide/maintain fire stopping.
May 29, 2013
Resolve - Class - 2
4 cars parked on sidewalk in front of bldg rem: discontinue illegal use
Aug 8, 2012
Resolve - Class - 2
At cellar lvl electrical room holes in wall above door and at pipe penatrations rem: provide maintain fire stopping
Aug 8, 2012
Resolve - Class - 2
3rd floor stwy b door not closing rem: repair replace doors
Aug 8, 2012
Resolve - Class - 2
4th floor corridors complex door have plexi vision panels rem: provide approved vision panels
Aug 8, 2012
Resolve - Class - 2
Reissue 34910299h no fresh air vent in gas meter room rem: provide fresh air vent
Aug 8, 2012
Resolve - Class - 2
Reissue#34839791k.the gas meter room is lacking fresh air ventilation located @ the cellar level.rem:provide/maintain fresh air ventilation
May 26, 2011
Resolve - Class - 2
Interior door closers are defective(loose & not working properly)located @ smoke doors leading to the complex by room 217w & library exit door on the 2nd flr level.rem:repair &/or replace exit doors
May 26, 2011
Resolve - Class - 2
Numerous cracks in play yard pavement some very long & deep present a trip hazard. remedy: repair play yard pavement
Mar 4, 2010
Resolve - Class - 2
No fresh air rear in gas meter room. remedy: provide fresh vent
Mar 4, 2010
Resolve - Class - 2
Gas meter room is being used to store bags of oil absorbent & a door. remedy: remove storage items from gas meter room.
Mar 4, 2010
Resolve - Class - 2
Sec 28-301.1 misc viol: 2nd fl library 2nd exit door partially blockedby table, computer work station & botes. remedy: remove obstruction
Mar 4, 2010
Resolve - Class - 2
4th fl stwy "e" door check is broken. 2nd fl stwy "b" & "f" door checks are broken. 1st stwy "e" & auditorium stage exit loft doors door check are broken. remedy: repair/replace doors
Mar 4, 2010
Resolve - Class - 1
In gym of above premises 2 metal light fixture covers are hanging fromceiling. 1 of the 2 is in danger of falling. remedy: repair/remove metal covers forthwith
Mar 4, 2010
Resolve - Class - 2
Reissue 34639657n. 2 basketball backboards in gym have lose wall anchors at top. remedy: repair or remove backboards.
Mar 4, 2010
Resolve - Class - 2
12q3.13i11.29l10.60q3.77q3.29l10 repair door operator so that it doesn't no slam when it close and open fully 77x10 repair light under car 77q3 install guard for light under car
Nov 13, 2009
Resolve - Class - 2
Reissue 34576707r water penetration through roof at fan room on 4th flr & gym roof. remedy: repair roof.
Feb 4, 2009
Resolve - Class - 3
Reissue vertical crack in block wall at gym next to wall divider. remedy: repair wall.
Feb 4, 2009
Resolve - Non-hazardous
All light in class room cover's are broken and lose or hanging down 75% of class room's. remedy: repair/or replace light cover's.
Mar 18, 2008
Resolve - Non-hazardous
2 vertical crack in block wall 1st location step crack in gym block wall next to wall divider 2nd location bulk head stair d. remedy: repair defect at above locations.
Mar 18, 2008
Resolve - Non-hazardous
Two gym basketball backboard attached to block wall(anchors) at top are lose and not holding to wall. remedy: remove backboard or repair lose (anchors)that hold up top of back board frame.
Mar 18, 2008
Resolve - Non-hazardous
Lunch room kitchen drop tin ceiling is defected throughout lose and not plum and out of track to hold tin ceiling in a tight fit from falling. remedy: repair tin drop ceiling in lunch room kitchen or replace.
Mar 18, 2008
Resolve - Non-hazardous
Reissue: vi 34523476j rain-water is penetrating into building and causing interior damage in the interior finish location of water peneterction above fan room on 4th flr. remedy: stop water penetration at above
Mar 18, 2008
Resolve - Non-hazardous
Reissue #34523476j. roofing has become porous & allowing rain water to enter the bldg in the fan rm on the 3 & 4 fls. remedy: repair roof.
May 23, 2007
Resolve - Hazardous
Reissue: 34466145r. roofing is hot water tight and allowing water to enter the building and causing damage to the interior finish located above the fan room on the fourth floor. remedy: repair roof.
Apr 28, 2006
Resolve - Non-hazardous
Failure to maintain building. defect noted: roof fan room corner blockwall has water penetration from roof down to floor. remedy: maintain building. make all necessary repairs.
Jan 14, 2005
Resolve - Non-hazardous
Failure to provide panic wardware where required by law noted:first floor auditorium stage exit door has no panis bar.(capacity over 300 persons). remedy:provide panic hardware.
Jan 14, 2005
Resolve - Hazardous
9a-illegal weld on thread pipering on boiler in back of boiler-need 'r1'form to show certificate of weld.
Jul 10, 2001
Resolve