Violations at 1096 Boston Road
Bronx, NY 10456 · BBL 2-02634-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
The newest 50 of 89 DOB violations. The city keeps the complete history.
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Retaining wall none
Failed to file cycle 1 technical report by 12/31/2018 per rcny 103-09
May 1, 2024
Dob violation - active - Retaining wall none
Failed to file cycle 1 technical report by 12/31/2018 per rcny 103-09
May 1, 2024
Dob violation - active - Retaining wall none
Failed to file cycle 1 technical report by 12/31/2018 per rcny 103-09
May 1, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - No report and / or late filing (facade) facade required
Failed to file fisp cycle 9a technical report by 02/21/2022
Feb 22, 2022
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Facade safety program facade required
Fisp-facade safety program facade required
Jul 23, 2018
Dob violation - active - No report and / or late filing (facade) facade required
Failed to file fisp cycle 8a technical report by 02/21/2017
May 31, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 30, 2018
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 30, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Residential elevator periodic inspection/test elevatorrequired
Failure to perform category 5 inspection
Jun 1, 2016
Dob violation - dismissed - Residential elevator periodic inspection/test elevatorrequired
Failure to perform category 5 inspection
Jun 1, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 25, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 25, 2015
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
Nyc department of education
Mar 12, 2014
Dob violation - resolved - Elevator elevatorrequired
Nyc department of education
Mar 12, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 8, 2013
Dob violation - resolved - No report and / or late filing (facade) facade required
Failed to file fisp cycle 7a technical report by 02/21/2012
Jan 31, 2013
Dob violation - dismissed - Facade facade optional
Unsafe local law 11/98 report filed
Apr 26, 2012
Dob violation - dismissed - Facade facade optional
Unsafe local law 11/98 report filed
Apr 26, 2012
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 1, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 1, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 25, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 25, 2011
Dob violation - resolved - Emergency power none
Ll2604e-emergency power none
Mar 31, 2008
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 11, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 11, 2008
Dob violation - resolved - Facade facade required
L1198-local law 11/98 - facade facade required
Jun 25, 2007
Dob violation - active - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 2, 2007
Dob violation - dismissed - Construction other optional
C-construction other optional
Mar 2, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed
ECB violations
The newest 50 of 123 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner.noted:at bulkhead level on 8th floor tower leading to bulkhead and 7th fl staircase has missing fireproofing monokote in several locations on steel beams ob
Jul 9, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:storage ofcombustible material boxes and jantorial equipment in electrical switch gear room which is not allowed at basement level observed upon inspe
Jul 9, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:at the main entrance at exposure#1 and 4 at ramp access with missing concrete creating a divot and raised concrete spray painted causing a potential a
Jul 9, 2026 · Penalty $1,250
Active - Class - 2
Reissue on ecb#35693395x failure to maintain building in code-compliant manner.noted:cracked or missing wire mesh panels and/or vision panels on stairwells and vision panels on smoke doors on 5th fl to 4th fl s
Jul 9, 2026 · Penalty $3,125
Active - Class - 2
Reissue on ecb#3569336h failure to maintain building in code-compliantmanner.noted:at cellar level in boiler room has missing terra cotta ceiling block missing exposing steel beams making it exposed and not fir
Jul 9, 2026 · Penalty $3,125
Active - Class - 2
Reissue on ecb#35693397j failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:emergency illuminated discharges exit and ex
Jul 9, 2026 · Penalty $3,125
Active - Class - 2
Reissue on ecb#35693398l failure to maintain building in code compliant manner.noted:fire rated classrooms and smoke doors not self closing due to binding,missing and or faulty hardware on classrooms 505,504,40
Jul 9, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner: corridor doors on all floors are not closing properly. all woods throughout corridorsand exit to stairway not closing properly. remedy: comply with code.
Aug 20, 2025 · Penalty $1,250
Active - Class - 2
Reissue: 35679066y-failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381 emergency lights not working throughout entire school
Aug 20, 2025 · Penalty $3,125
Active - Class - 2
Reissue: 35679067x-failure to maintain building in code-compliant manner. cellar level ceiling in disrepair. terra cotta ceiling. remedy: comply with code.
Aug 20, 2025 · Penalty $3,125
Active - Class - 2
Reissue: 35679068h-failure to maintain building in code-compliant manner: glass panels are missing on door and in stairwells throughout entire. remedy: comply with code.
Aug 20, 2025 · Penalty $3,125
Active - Class - 2
Reissue#35672131j failure to maintain building in code-compliant manner.wire mesh glass panel are missing throughout.rem:comply with code.
Aug 16, 2024 · Penalty $1,562
Active - Class - 2
Reissue#35672132l failure to maintain building in code-compliant manner.cellar level ceiling in disrepair throught.rem:comply with code.
Aug 16, 2024 · Penalty $1,562
Active - Class - 2
Reissue#35672135r failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381 emergency lights not working throughout entire school.rem
Aug 16, 2024 · Penalty $1,562
Active - Class - 2
Reissue#35672137k failure to maintain building in code-compliant manner.recreation/parking lot has cracks greater than 1" at several areas.rem:comply with code.
Aug 16, 2024 · Penalty $1,562
Resolve - Class - 2
8 story with facade operation. i observed the pipe scaffold exposure 1 debris netting, not secure/maintained to the scaffold. netting shall be securely attached to the scaffold and shall be enclose at all open
Mar 10, 2024 · Penalty $2,500
Resolve - Class - 2
Failure to file acceptable amended cycle 6, 7a, and 8a report indicating correction of unsafe conditions described in initial facades reportrequired by 28-302.5 for control #807699. remedy: file acceptable repo
Jan 16, 2024 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner.at time of inspection at exterior/outdoor recreational area & faculty parking lot,several cracks greater than 1 inch and uneven asphalt pavement condition p
Jan 19, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.at time of inspection observed at cellar level electrical room,excessive amounts of storage.items such as garbage bins,slab sink,toilet bowl and desks locat
Jan 19, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.at time of inspection observed emergency lights not operable when tested.at
Jan 19, 2023 · Penalty $625
Active - Class - 2
Exit doors not self closing.at time of inspection observed at 1st floor gym exit door 7 and auditarium exit door 5 not closing properly.additionally exit doors 8,9 & 10 are getting stuck on door saddle and not
Jan 19, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.at time of inspection observed fireproof self closing doors not closing properly.at 5th floor hallway doors by staircase e,double doors by rm 515.at 4th flo
Jan 19, 2023 · Penalty $625
Resolve - Class - 2
Reissue#35644535h failure to maintain building in code-compliant manner.at time of inspection observed at cellar level boiler room ceiling has spalling/missing plaster exposing structural steel beam.violation 3
Jan 19, 2023 · Penalty $1,562
Active - Class - 2
Reissue#35644536j failure to maintain building in code-compliant manner.at time of inspection observed missing wire mesh glass panels.at staircase a,e,f & g throughout various floors.at exit 1 door and classroo
Jan 19, 2023 · Penalty $1,562
Active - Class - 2
Reissue#35644537l failure to maintain building in code-compliant manner;no firestopping per bc 712.3;27-345.at time of inspection observed at cellar level boiler room,holes & opennings around pipe penetrations
Jan 19, 2023 · Penalty $3,125
Resolve - Class - 2
Failure to submit an acceptable required cycle 9a report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control#907699.rem:submit acceptable required t
Dec 2, 2022 · Penalty $1,250
Active - Class - 2
Reissued #35540246p failure to maintain building in code compliant manner no fire stopping per bc 712-3; 27-345.noted:at time of inspection observed at cellar level boiler room has holes & openings ground pipe
Mar 3, 2022 · Penalty $3,125
Resolve - Class - 2
Reissue#35540247r failure to maintain bldg in code compliant manner. noted: at time of my inspection,i observed missing wire mesh glass panels. at stairwell a,e,f,&g in stairway & on stair fpsc door. violation
Mar 3, 2022 · Penalty $1,562
Resolve - Class - 2
Reissued #35540248z failure to maintain building in code compliant manner.noted:at time of inspection observed at cellar level boiler room ceiling has spalling and missing plaster exposing structural steel beam
Mar 3, 2022 · Penalty $1,562
Active - Class - 1
97x17-class 1 rts repair wheel chair lift & restore to service immedately call nyc dob elevation division for reinspection.
May 6, 2021 · Penalty $1,250
Active - Class - 1
42m7-no door lock monitoring installed in controller as mandated by 3.10.12 of apendix k3 of 2014 nyc building code.remedy:file application & install.
May 6, 2021 · Penalty $1,250
Resolve - Class - 1
42m7-no door lock monitoring installed in controller as mandated by 3.10.12 of apendix k3 of 2014 nyc building code.remedy:file application&install.
May 6, 2021 · Penalty $1,250
Resolve - Class - 2
Exit door not selfclosing noted:observed exterior exit doors@exit8,9,10 don't selfclose properly,exit9&10 doors are difficult to open&stay ajar due to rubbing on saddle&exit8 door remains completely open&doesn'
Feb 3, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner:noted:observed@cellar level,boilerrm ceiling has spalling&missing plaster exposing structural steel beams@various locations,also missing pieces of ceiling drywa
Feb 3, 2021 · Penalty $625
Active - Class - 2
Failure to maintain bldg in code-compliant manner:noted:observed missing wiremesh glass panels@stairwell a,e,f&g in stairway&on stair fpsc doors.repair &/or replace.
Feb 3, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35475659p noted:observed@cellar level boilerrm has holes/openings,pipe penetrations@various locations thruout ceiling w/no fire stopping provided.provide/maintain fire-stopping.
Feb 3, 2021 · Penalty $3,125
Resolve - Class - 2
Reissue#35475660m failure to maintain bldg in code-compliant manner:use of prohibited door &/or hardware per bc1008.1.8,27-371(j) noted:observed@various locations thruout each fl classrm doors,kickstops install
Feb 3, 2021 · Penalty $1,562
Resolve - Class - 2
Found exposed wiring, water column corroded, hand hole corroded, leaking safety relief valves, must be replaced. boiler room to be fire rated seal shaft way near oil tank.
May 13, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner:use of prohibited dor and/or hardware per bc 1008.1.8;27-371(j).note:observed at various locations through out the entire building/all floors at minimum 20
Feb 7, 2020 · Penalty $625
Resolve - Class - 2
Re-issue#35386486l.failure to maintain building in code-compliant manner:no fire stopping per bc 712.3;27-345.note:observed at cellar level boiler room ceiling is missing fire stopping at various location throu
Feb 7, 2020 · Penalty $3,125
Resolve - Class - 2
Re-issue#35386487n.failure to maintain building in code-compliant manner.note:observed throughout staircase e,f & a numerous wired glass panels missing at several landings & between stairway.remedy:repair and/o
Feb 7, 2020 · Penalty $1,562
Resolve - Class - 2
Exit door not selfclosing - staircase e exit door doesn't self close. wood wxit door has broken door closer - exit door has brokeb hinge. remedy: repair &/or replace.
Feb 26, 2019
Resolve - Class - 2
Reissue # 35312005j. failure to maintain bldg in code compliant mannermissing wire glass on staircase f & e throughout. remedy: repair &/0r replace.
Feb 26, 2019
Resolve - Class - 2
Reissue # 35312012h. failure to maintain bldg in code compliant mannerno firestopping per bc 712.3; 27-345 - boiler room ceiling missing firestopping throughout. remedy: provide/maintain firestopping.
Feb 26, 2019
Resolve - Class - 2
Failure to submit acceptable 8th round report of critical examination documenting condition of exterior walls and appurtenances required by 28-302.4 for control #807699.rem:submit required technical report.
May 18, 2018
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner: no fire stopping per bc 712.3; 27-345. noted: missing fire stopping observed @ boiler room ceiling through openings @ ceiling throughout. rem: provide/maintain
Jan 25, 2018
Resolve - Class - 2
Exit door not self-closing. noted: not self-closing door observed between classrooms # t3 & t4 @ transportable school. rem: repair/replace door.
Jan 25, 2018
Resolve - Class - 2
Exit door not self-closing. noted: not self closing door observed @ 1st flr exit# 2 from gymnasium, @ main entrance of cafeteria. rem: repair/replace door.
Jan 25, 2018
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner: lack of emergency lighting for exits, exit discharges & public corridors per bc 1006.1; 27-542. noted: defective emergency lighting observed on classroom t1,t2
Jan 25, 2018
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner: lack of emergency lighting for exits, exit discharges & public corridors per bc 1006.1; 27-542. noted: defective emergency lighting observed @ gymnasium. rem:
Jan 25, 2018
Resolve