346 Powers Avenue
Bronx, NY 10454BBL 2-02572-0006Map
Owner of record: NYC Department Of Homeless Services
346 Powers Avenue is a care facility built in 1988 in Bronx, 10454. It has 325 residential units across 3 floors. The owner of record is NYC Department Of Homeless Services. HPD has recorded 2 housing violations here, most recently on December 1, 2015.
- HPD violations
- 2
- DOB violations
- 17
- ECB violations
- 47
- HPD complaints
- 6
What to know
No open immediately-hazardous violations among recent records.
Date of the most recent HPD inspection that found a problem.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 2
- CImmediately hazardous
Correct the lead-based paint hazard - presumed lead paint that is peeling or on a deteriorated subsurface using work practices set forth in 28 rcny ?11-06(b)(2) ceiling, west wall in the 1st room from east located at apt 131, 1st story, 2nd apartment from west at north
Dec 1, 2015 · Apt 131
Closed — Violation closed - CImmediately hazardous
Provide an adequate supply of heat from an approved central heating system, or an approved system of gas or electrical heating in good operating condition for the dwelling unit in the entire apartment located at apt 131, 1st story, 2nd apartment from west at north
Nov 26, 2015 · Apt 131
Closed — Violation closed
DOB building violations · 17
- Elevator elevatorrequired
E-elevator elevatorrequired
Mar 2, 2020
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 18, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 1, 2016
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2013 inspection report
Mar 3, 2015
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2013 inspection report
Mar 3, 2015
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 31, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 19, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 27, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 28, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 18, 2008
Dob violation - resolved
Show 7 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Jul 20, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 3, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 3, 2006
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 20, 2005
Dob violation - resolved - Elevator elevatorrequired
2p5505
May 3, 1999
Dob violation - resolved
ECB violations · 47
- Class - 1
No dlm was installed on this controller as mandated by the 2014 nycbc section 3.10.12. in car phone not working. basement brail tag is labeled as the eagles floor with the star. but the fireman service key stat
Apr 5, 2024 · Penalty $3,125
Active - Class - 2
Observed lights installed to close to the sprinkler heads. as per 314.5 of the fire code sprinkler heads shall not be obstructed., repair and/or replace
Feb 5, 2024 · Penalty $625
Active - Class - 2
Observed in the boiler room located in the basement/cellar 2 cabinets being stored behind on of the boilers. as per 315.2.3 of the fire code equipment rooms. combustible material shall not be stored in boiler r
Feb 5, 2024 · Penalty $625
Active - Class - 2
Emergency exits doors do not function/open properly throughout building., repair and/or replace
Dec 29, 2023 · Penalty $625
Active - Class - 2
Hole penetration found throughout building., provide/maintain fire stopping
Dec 29, 2023 · Penalty $1,250
Active - Class - 2
Emergency exits corridors are blocked, daycare, ground level., provide proper corridor width
Dec 29, 2023 · Penalty $625
Active - Class - 2
No emergency lighting in hallways, corridors, and staircases throughout building., repair and/or replace lighting
Dec 29, 2023 · Penalty $1,250
Active - Class - 1
Class 1 item: no door lock monitoring installed on this controller as mandated by 3.10.12 of appendix k3 of the 2014 nyc building code. this is a feature which ensures passenger safety. file application, instal
Dec 28, 2023 · Penalty $3,125
Active - Class - 2
At cellar, first floor, 2nd floor 3rd floor, public corridor (staircase), open public spaces, utility rooms. emergency lighting is required to illuminate and identify hallways, stairwells and exits to facilitat
Aug 8, 2022
Resolve - Class - 2
Found exposed wires on combustion air fan, cover to combustion air fan not properly secured, safety relief valve leaking,
Aug 8, 2022 · Penalty $625
Active
Show 37 more ↓
- Class - 2
As per one weil mclain 1288 in cellar boiler room; motor covering and belt guard for combustion air fan not in place-electrical wires exposed at combustion air fan motor.
Jul 29, 2022 · Penalty $625
Active - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor
Jul 27, 2022 · Penalty $3,125
Active - Class - 2
At first floor, exit doors show failure to close & open properly., repair/replace door
May 9, 2022 · Penalty $625
Active - Class - 2
Requirement of emergency lights & signal at starircase h, i, from 3rd fl to cellar, repair and/or replace lighting
May 9, 2022
Resolve - Class - 2
I observed throughout building sprinkler heads are installed to close to light fixtures, also boiler #2 has an active leak on copper piping., repair and/or replace
May 9, 2022 · Penalty $625
Active - Class - 2
Covers missing for electrical connection boxes at two solenoid gas valves.
Sep 20, 2021 · Penalty $625
Resolve - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor
Aug 13, 2021 · Penalty $1,250
Active - Class - 1
Failure to comply, comply with commissioner's order; comply with code
Mar 19, 2019
Resolve - Class - 1
Failure to ground electrical systems i obser the grounding electrode conductor disconnected at the watermain.rem:provide grounding electrodeconductor
Jan 16, 2019
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner.no fire stopping per712.3;27-345.fire stop missing in the gas meter room & the boiler room.rem:provide/maintain fire stopping.
May 21, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. multiple exhaust fan units not working. units are located on roof. note: approx 10 units not working. rem: repair &/or replace.
May 21, 2018
Active - Class - 2
Failure to maintain bldg in code-compliant manner. observed on 05/21/18 at above address in cellar gas meter room do not have ventilation. rmdy: repair and/or replace.
May 21, 2018
Resolve - Class - 2
B254,50a,50b,50c. as per class 2 (b254) 28-301.1 failure to maintain 50a-heating pump over boiler is leaking; 50b-exposed electrical wires from connection boxes light fixtures; 50c-boiler room doors not self
Apr 10, 2018 · Penalty $3,125
Active - Class - 1
Unpainted gas piping not protected from corrosian.observed on 12/05/2017 @ above address gas piping to hvac on the 2nd floor roof not painted.photos taken.rem:comply with summons.
Dec 5, 2017
Resolve - Class - 2
Failure to maintain building walls or appurtenances.noted: observed on the exterior of stair "h" roof bulkhead,detached/missing flwashing at upper and lower areas.(southeast of roof).maintain exterior building
Dec 5, 2017
Resolve - Class - 2
Electrical work without a permit. observed in hallways near central stairwells on north and south sides on 2nd floors new conduit approximately 2" in diameter connected to a new circuit breaker panel, this cond
Oct 10, 2017
Resolve - Class - 2
Failure to maintain building in code-compliant manner. observed on 10/10/2017 at above address no inspector's test valve or test gauge on upper most floor. rem: repair and/or replace.
Oct 10, 2017
Resolve - Class - 1
Failure to install grounding electrode conductor in accordance with section. observed grounding conductors in domestic water meter, room larger than #4 awg installed without a raceway to protect against harm or
Oct 10, 2017
Resolve - Class - 2
Failure to use approved conductors and/or equipment. observed on rooftops on north and south side installation of flood lights with rubber type cards connected to junction boxes, no raceway installed to protect
Oct 10, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. observed on 6-1-17 in basement of above address copper pipe going through wall w/o sleeves. remedy: repair & or replace.
Jun 1, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. no fire stopping per bc 712.3;27-345. noted: observed on cellar level at various locations & rooms-gas piping,electrial conduits penetrating through concrete
Jun 1, 2017
Resolve - Class - 2
Exit door not self closing. noted: observed on 1st fl south bldg exit door leading to parking lot is racked,knowing on adjacent door not allowing to door to close properly,at exit'i'exterior exit gate is racked
Jun 1, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: noted: observed defective door/gate hardware-exterior exit gates at yard leading to jackson ave have defective panic bars/push bars not allowing the exit gate
Jun 1, 2017
Resolve - Class - 1
Unapproved/unsafe/unsuitable electrical equipment observed no tamper resistant outlets throughout hulls as well as no emergency lighting w/back up battery also noted no labeling on panels to identify branch cir
Jun 1, 2017
Resolve - Class - 1
Electrical work w/out a permit.observed multiple split a.c units on 2nd fl rooftop these units are not covered under any appl active or closed.rem:comply w/code /obtain permit.
Jun 1, 2017
Resolve - Class - 2
Failure to maintain bldg walls or appurtenances. noted: observed on the roof of the south bldg,missing & detached roof flashing around the exterior for stair'h'bulkhead,top & bottom section of northside.
Jun 1, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: lack of emergency lighting for exits,exit discharges & public corridors per bc 1006.1;27-542. noted: at time of inspection i observed no emergency light packag
Jun 1, 2017
Resolve - Class - 2
Fail to maintain bldg in code compliant manner. re: installation/maintenance of plumbing materials/equipment per pc 102.3;27-902. fence couplings installed throughout basement. remedy: remove all non-complying
Jun 1, 2017
Resolve - Class - 1
Sec. 401.1 misc violations gas piping not labeled. observed on 6-1-17 in basement of above address gas piping throughout basement not labeled. remedy: comply w/summons.
Jun 1, 2017
Resolve - Class - 2
Failure to maintain building in code compliant manner. no fire stopping per bc 712.3;27-345. at basement various areas and rooms are missingfire stopping in ceiling and walls such as hallway electric panel room
Aug 31, 2016
Resolve - Class - 2
Failure to maintain building in code-compliant manner:fresh air vent for gas meter room does not exist. at basement in gas meter room, ther eis no fresh air vent installed. rmdy: comply with nov.
Aug 31, 2016
Resolve - Class - 2
Failure to maintain building in code compliant manner.observed on 8/31/16 at 11:30am in basement.throughout installed illegal caps on waste lines.law of rainage system pc 702.1 27-911.no pictures.rmdy:remove/re
Aug 31, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. observed on 8/31/16through dob record.no annual boiler inspection. boiler 171072md file for 2016. file complete boiler inspt service equipment/rmdy: file for i
Aug 31, 2016
Resolve - Class - 1
Electrical work w/o a permit. noted: at time of inspection,at approx. 12pm licensed electrician,license #12221,did not have a permit on filefor electrical work in progress changing of all stove outlets and coun
Nov 20, 2014 · Penalty $1,630
Resolve - Class - 1
New building occupied without a valid cert of occupancy. building occupied by nyc dept of homeless services. cert of occupancy # 73030 expired 11/13/99. remedy: obtain a valid cert of occupancy.
Oct 31, 2014
Resolve - Non-hazardous
New building occupied without a valid certificate of occupancy n.b # 52/88 note: t c ofo #73030 expired 11/13/99 remedy: obtain a valid certificate of occupancy
Apr 17, 2000 · Penalty $2,500
Resolve - Non-hazardous
New bldg #52/88 occupied w/o a valid c of o. c of o #71553 expired 6/11/98. remedy: discontinue illegal occupancy or obtain a valid c ofo.
Jul 7, 1999
Resolve
Complaints
- Heat/hot water
Apartment only
Oct 18, 2015 · Apt 319N
Close - Heat/hot water
Entire building
Jan 29, 2015 · Apt 252
Close - Heat/hot water
Entire building
Jan 14, 2015 · Apt 211
Close - Heating
Heat related
Dec 5, 2010 · Apt 5
Close - Heating
Heat related
Dec 4, 2010 · Apt BLDG
Close - Nonconst
Vermin
Aug 26, 2003 · Apt BLDG
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Care facility (N2)
- Year built
- 1988
- Floors
- 3
- Residential units
- 325
- Building area
- 145,332 ft²
- Lot area
- 47,307 ft²
- Zoning
- R6
- Community board
- 201
- Council district
- 8
- Block / lot
- 2572 / 6
- Assessed value
- $6,194,700
- Landmark / historic district
- No
Questions about 346 Powers Avenue
Who owns 346 Powers Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Homeless Services.
Does 346 Powers Avenue have violations?
Yes. NYC HPD has recorded 2 housing violations at this property.
Is 346 Powers Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 346 Powers Avenue built?
City records list 1988 as the year it was built.
How many apartments are in 346 Powers Avenue?
It has 325 residential units.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.