75 West 168 Street
Bronx, NY 10452BBL 2-02517-0001Map
Owner of record: Rc Ch Sacred Heart
75 West 168 Street is a school building built in 1950 in Bronx, 10452. The owner of record is Rc Ch Sacred Heart. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 56
- ECB violations
- 37
- HPD complaints
- 14
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 56
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 22, 2025
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 22, 2025
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 22, 2025
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 22, 2025
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 30, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed
Show 40 more ↓
- Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Apr 27, 2022
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Apr 27, 2022
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Aug 2, 2021
Dob violation - active - Construction other optional
Ftm exterior facade and appurtenances. exp 1 west elevation observed horizontal cracking on third floor, broken window sill on second floor exposure 2 north elevation. observed vertical cracking in parapet, step cracking in chimney. remedy: maintain exterior building and appurtenances
Jun 18, 2021
Dob violation - active - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Jun 2, 2021
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 25, 2020
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Jan 17, 2020
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator - failure to file category 1 2017 inspection/test
Apr 5, 2019
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Aug 9, 2018
Dob violation - dismissed - Plumbing none
The dob intends to revoke all approvals and permits under plumbing job #240172941 due to suspension of license.stop all plumbing work immedia tely except to make site safe
Oct 7, 2017
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 25, 2017
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 25, 2017
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 25, 2017
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2014 inspection report
Oct 1, 2015
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2014 inspection report
Oct 1, 2015
Dob violation - active - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2014 inspection report
Oct 1, 2015
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2013 inspection report
Mar 3, 2015
Dob violation - active - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Jan 1, 2012
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Vcat1-elevator annual inspection / test elevatorrequired
Oct 8, 2010
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 10, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 10, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - active - Elevator elevatoroptional
Ll16-local law 16/84 - elevator elevatoroptional
Oct 12, 1989
Dob violation - dismissed - Elevator elevatoroptional
Ll16-local law 16/84 - elevator elevatoroptional
Oct 12, 1989
Dob violation - dismissed
ECB violations · 37
- Class - 2
Electrical work does not conform to approved submittal documents/amendments. observed on 2nd, 3rd fl electrical closet new 12 / 24 panels installed with new overcurrent protection. permit # x01442199 does not c
Oct 1, 2026 · Penalty $1,250
Active - Class - 2
Failure to provide arc-fault circuit interrupter (afci) protection in dwelling units. observed in electrical panels for the 2nd, 3rd fl's no arc fault protection for new a/c lines for all clients rooms. arc fau
Oct 1, 2026 · Penalty $2,400
Active - Class - 2
Observed throughout the building no sinks in bathrooms and on first floor hot water heaters vent is not sealed properly which is contrary to code sections 403.1 and fgc 503.3, repair and/or replace
Oct 27, 2025
Resolve - Class - 1
Rts class 1: failure to maintain building in code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon inspection, the device is found to be out of service, creating a hazardous condition
Oct 16, 2025 · Penalty $3,125
Active - Class - 1
Rts class 1: failure to maintain building in code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon inspection, the device is found to be out of service, creating a hazardous condition
Oct 16, 2025 · Penalty $6,250
Active - Class - 1
: failure to maintain building in code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon inspection, the device is found to be out of service, creating a hazardous condition per 1rcny
Jan 13, 2025 · Penalty $1,250
Active - Class - 1
Unsafe storage of combustible material and equipment. observed unsafe combustible material (boxes, paint, constructing material, clothes, cleaning products)underneath staircase adjacent to boiler room. in case
Nov 25, 2024 · Penalty $2,500
Resolve - Class - 1
I observed the electrical closet on the 2nd floor not dedicated to electrical distribution, i noted the installation of data equipment and wiring. as per ec 110.25 no equipment except what's accepted shall be i
Nov 25, 2024
Resolve - Class - 1
Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed hole penetrations at first floor in front of boiler room, gas meter corr
Nov 25, 2024 · Penalty $2,500
Resolve - Class - 2
Exit door not self-closing. observed non self closing doors at electrical rooms throughout building. in an emergency all mechanical room doors must be self closing., repair/replace door
Nov 25, 2024 · Penalty $312
Resolve
Show 27 more ↓
- Class - 1
I observed the electrical equipment in the 1st floor office without fire rated doors as required. the equipment is separated from the room with wooden bi-folding doors.; 110.33, comply with ec code; provide pro
Nov 25, 2024
Resolve - Class - 1
: failure to maintain building in code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon inspection, the device is found to be out of service, creating a hazardous condition per 1rcny
Aug 21, 2024 · Penalty $1,250
Active - Class - 1
Unlawful act.failure to comply with commissioner's order.respondent did not comply with previous ecb violation#35651585l issued on 6/3/2022 to installed adequate sidewalk shed safety at exp2 south elevation.as
Aug 13, 2022
Resolve - Class - 1
Failure to provide sidewalk shed where required.note:respondent failed to correct previously written ecb#35647537p dated 3/31/22 which required respondent to provide sws where required.as of today 6/3/22 sws is
Jun 3, 2022
Resolve - Class - 1
Failure to maintain building in code compliant manner.note:respondent failed to correct previously written ecb #35647536n dated 3/31/22 of today 6/3/22 defective facade conditions stated in previous ecb violati
Jun 3, 2022 · Penalty $1,250
Resolve - Class - 2
Info panel missing on sws.ato my insp i observed [email protected] noticed sws w/missing info panel.w/corresponding address.creating situation w/1st responders locating property in case of emergency.comply w/code pro
Apr 14, 2022 · Penalty $3,125
Resolve - Class - 2
Jobsite fence not constructed or maintained persuant to subsection.note:at the time of inspection on a non-active jobsite,i observed that the construction fence has been poorly maintained.for instance,fence has
Apr 13, 2022
Resolve - Class - 1
Failure to maintain building in code compliant manner.note:observed the same unsafe condition issued on 01/13/2022 on previous violation#35640470h:at east elevation exposure#1 observed spalled and cracked stone
Mar 31, 2022 · Penalty $3,125
Resolve - Class - 1
Failure to provide sidewalk shed where required.note:observed the sameunsafe conditions on previous violation#35640471j issued on 01/13/2022at the time of inspection observed unsafe conditons at east elevation
Mar 31, 2022 · Penalty $25,000
Resolve - Class - 1
Failure to maintain building in code compliant manner.at east elevation exp #1 observed spalling & cracked stones & damaged mortar joints at multiple locations at south eastern corner w/o protection provided un
Jan 13, 2022 · Penalty $1,250
Resolve - Class - 1
Failure to provide sidewalk shed where required.at time of inspection observed unsafe conditions at east elevation(south eastern corner)as spalled stones & damaged mortar joints w/o protection underneath
Jan 13, 2022 · Penalty $10,000
Resolve - Class - 1
97x17.97-x-17 entire device inoperative;upon arrival found device out of service;rem:repair device back 4 and contact nyc dob to notifiy that the device has been repair back to device so a proper inspection can
Aug 31, 2020
Resolve - Class - 2
Occupancy contrary to that allowed by the c of o or bldg dept records.under job #200023704 to charge c of o from (convent) to not for profitinstitution from 1-11-1990 last permit expired on 1-12-1991, no new c
Jun 8, 2018
Resolve - Class - 2
B254,50a,50b,50c,50d,50e as per class 2 (b254) 28.301.1 failure to maintain 50a-two "u" rated tanks (expansion) safety no safety valves installed; 50b-exposed electrical wiring in boiler room; 50c-blow off
May 29, 2018 · Penalty $312
Resolve - Class - 1
97x10,cu3810. 97x10-device is inoperative repair; 38i10-junction box is damaged with exposed wiring posing a possible threat (unsafe) repair.
May 14, 2018 · Penalty $1,250
Resolve - Class - 2
Expired permit. note: at time of inspection, i observed sidewalk shed in place with permit #220479220 expired 9/17/2016. rem: comply with code-renew permit.
Apr 18, 2018
Resolve - Class - 2
Pedestrian protection does not meet code specification as per 3307.6.4.8.1. note: at time of inspection, i observed sidewalk shed in place without lights in operation condition. rem: comply with code-provide li
Apr 18, 2018 · Penalty $2,400
Resolve - Class - 2
Failure to comply w/the comm's order to file a cert of correctioon w/the dob .the summons #35216877r & was issued on 11/01/2016.rem:file a cert of correction.
May 26, 2017
Resolve - Class - 2
Failure to comply w/commissioner's order contained in summons/violation #35216877r issued on 11/10/16 and to file a certificate of correction pursuant to 28-201.1 and 14dny 102-01. rmdy: comply w/commissioner's
Mar 25, 2017
Resolve - Class - 3
Failure to maintain bldg walls &/or appurtenances. noted: at parapet,facade w/step cracks & spalling masonry along nelson ave & along 108 street sides. remedy: comply w/code.
Mar 16, 2017 · Penalty $200
Active - Class - 2
Failure to maintain bldg in code compliant manner;lack of emergency lighting for exits,exit discharges & public corridors per bc 1006.1;27-542. noted: the follow emergency lights & sign are not working when tes
Mar 16, 2017 · Penalty $500
Active - Class - 2
Exit door not self closing. noted: fpsc door not self closing at kg-3 hall,at rm 2 hall. remedy: comply w/code.
Mar 16, 2017 · Penalty $250
Active - Class - 1
Work without a permit.at the time of my inspection, 11:25am,on 11/1/16at the above place of occurrence address i observed two installed and operating hot water heaters in the boiler room.the dates of manufactur
Nov 1, 2016 · Penalty $1,600
Resolve - Class - 1
411.1miscellaneous violation:residential gas flex used on commercial equipment.at the time of my inspection 11:25am on 11/01/16 at the aboveplace of occurrence address i observed in the kitchen area a commercia
Nov 1, 2016 · Penalty $1,600
Resolve - Class - 1
Failure to have new or altered plumbing system tested.at the time of my inspection 11:25am,on 11/01/16 at the above place of occurrence address i observed in the boiler roomtwo hot water heaters installed with
Nov 1, 2016 · Penalty $1,000
Resolve - Non-hazardous
Failure to provide emergency power exit lights on staircases throughout building. remedy: provide emergency power exit lights according to b.e.c. standards
Nov 7, 1991
Resolve - Unknown
Failure to have approved p.a. plans available for inspection. remedy; provide approved p.a. plans.
Jan 24, 1989 · Penalty $100
Resolve
Complaints
- Heat/hot water
Entire building
Oct 29, 2024 · Apt 18
Close - Heat/hot water
Entire building
Oct 25, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 22, 2024 · Apt 18
Close - Heat/hot water
Entire building
Jul 28, 2024 · Apt 18
Close - Heat/hot water
Entire building
Dec 8, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Jul 1, 2019 · Apt 5G
Close - Heating
Heat related
Oct 31, 2013 · Apt NA
Close - Heating
Heat related
Oct 27, 2013 · Apt 19
Close - Heating
Heat related
Oct 27, 2013 · Apt 24
Close - Electric
Electric-supply
Aug 9, 2007 · Apt 2
Close
Show 4 more ↓
- General
Stairs
Aug 9, 2007 · Apt 2
Close - General
Doors
Aug 9, 2007 · Apt 2
Close - General
Floor
Aug 9, 2007 · Apt 2
Close - Nonconst
Vermin
Aug 9, 2007 · Apt 2
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W2)
- Year built
- 1950
- Floors
- 4
- Residential units
- —
- Building area
- 90,748 ft²
- Lot area
- 64,250 ft²
- Zoning
- R7-1
- Community board
- 204
- Council district
- 16
- Block / lot
- 2517 / 1
- Assessed value
- $13,705,650
- Landmark / historic district
- No
Questions about 75 West 168 Street
Who owns 75 West 168 Street?
The owner of record in NYC Department of City Planning PLUTO data is Rc Ch Sacred Heart.
Does 75 West 168 Street have violations?
NYC HPD has no housing violations on record for this property.
Is 75 West 168 Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 75 West 168 Street built?
City records list 1950 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.