1150 Morris Avenue
Bronx, NY 10456BBL 2-02438-0050Map
Owner of record: NYC Department Of Education
1150 Morris Avenue is a school building built in 1950 in Bronx, 10456. The owner of record is NYC Department Of Education. HPD has recorded 1 housing violation here, most recently on August 21, 2018. 1 of the 1 most recent violations are still open.
- HPD violations
- 1
- DOB violations
- 44
- ECB violations
- 77
- HPD complaints
- 15
What to know
No open immediately-hazardous violations among recent records.
Date of the most recent HPD inspection that found a problem.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 1
- BHazardous
Properly repair the broken or defective return buzzer intercom system from building entrance to apartment in the foyer located at apt 5g, 5th story, 1st apartment from north at east
Aug 21, 2018 · Apt 5G
Open — Nov sent out
DOB building violations · 44
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 3, 2019
Dob violation - active
Show 34 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Jun 9, 2018
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 25, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 20, 2015
Vw*-violation - work w/o permit dismissed - Elevator elevatorrequired
Nyc department of education
Apr 1, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 25, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 19, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 23, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 14, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 14, 2010
Dob violation - resolved - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 2, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 2, 2009
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 16, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 16, 2008
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 3, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 3, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 3, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 3, 2006
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 27, 2003
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 27, 2003
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 9, 1994
Dob violation - dismissed
ECB violations · 77
- Class - 2
Re-issue #35720001p. failure to maintain building in code-compliant manner. noted: interior fire-proof doors do not self-close properly at, 3rd flr-staircase "b", "g", "j". 2nd flr-staircase "a", "b". 1st flr-e
Mar 25, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. no fire stopping per bc 712.3; 27-345. noted: in basement inside gas meter room, firestopping is missing around pipes in multiple locations. remedy: provid
Mar 25, 2026 · Penalty $1,250
Active - Class - 2
Found farrar & treft oil fired boiler not operable due to leaking tubes and corroded tube sheet. repair or replace boiler.
Sep 8, 2025 · Penalty $1,250
Active - Class - 2
Reissue#35684632x date of issue:07.17.2024 exit door not self closing properly at the time of inspection.at the time of inspection observed & noted at 3rd floor stair way i one exit door,3rd fl stairway b 2 exi
May 16, 2025 · Penalty $1,562
Active - Class - 1
At a construction site where a worker fell using pipe scaffold on 3/20/2025.upon reviewing department of building records i noticed no notification incident form completed as per local law 78 as of 5/92025.gen
May 9, 2025 · Penalty $5,000
Resolve - Class - 1
Failure to provide adequate means and methods. worker while moving aluminium plank at top platform of scaffold fell approx 12 feet onto lower platform.; 3301.1, comply with code; comply with code stop all scaff
Mar 20, 2025 · Penalty $2,500
Resolve - Class - 2
Restore service to device.
Aug 29, 2024 · Penalty $625
Active - Class - 2
Reissue #35663342p. failure to maintain building in code-compliant manner. at time of my inspection i observed at the 3rd floor doors are not closing properly due to being in state of disrepair. at 1b main entr
Jul 17, 2024 · Penalty $625
Active - Class - 2
Reissued #355916076-failure to maintain building in code-compliant manner.illumination for exits,exit discharges & public corridors per bc 1006.1; 27-381.note:observed existing emergency lights located at 1st f
Mar 15, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue #35591612x - failure to maintain building in code-compliant manner.note:observed at basement level girls gym,ceiling missing aprox ;22; accost drop ceiling tiles & currently exposing electrical/mechanic
Mar 15, 2023 · Penalty $1,562
Resolve
Show 40 more ↓
- Class - 2
Reissue #35591609p failure to maintain building in code-compliant manner.note:observed interior doors located at 3rd fl stair "b" "d" "g" "j" "i" classroom #302,337,338,339. 2nd fl stair "b", classroom #227.1st
Mar 15, 2023 · Penalty $1,562
Active - Class - 2
Stair and/or floor identification signs missing and/or defective.note:observed at roof level,bulkhead(exterior)door not providing id signs for staircase & exit number.stair"i" identification signs missing on 3r
Mar 15, 2023 · Penalty $625
Resolve - Class - 2
Reissued #35591608n failure to maintain building in code-compliant manner:lack of emergency lighting for exits,exit discharges & public corridors per bc 1006.1; 27-542.note:observed required emergency/exit ligh
Mar 15, 2023 · Penalty $3,125
Resolve - Class - 2
Re-issue #35548225m failure to maintain building in code-compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.noted:observed existing emergency light are not operation
Mar 16, 2022 · Penalty $1,562
Resolve - Class - 2
Re-issue #35546398l failure to maintain building in code-compliant manner.noted:observed doors not closing properly due to being in state of disrepair or racked at following locations 3rd fl staircase g&j 2nd f
Mar 16, 2022 · Penalty $1,562
Active - Class - 2
Re-issue #35546397j exit door not self-closing.noted:observed at 3rd fl staircase g&j 2nd fl staircase b/exit #7 1st fl main entrace stair a,auditorium exit #5 & #6 basmt staircase d,exit #8 & #9 door checks ar
Mar 16, 2022 · Penalty $1,562
Resolve - Class - 2
Re-issued #35546399n failure to maintain building in code compliant manner lack of emergency lighting for exits exit discharges & public corridors per bc 1006.1;27-542.noted:observed required emergency lighting
Mar 16, 2022 · Penalty $3,125
Resolve - Class - 2
Re-issued #35546396h failure to maintain building in code compliant manner.noted:observed roof staircase 'a' bulkhead has water penetration creating damage to interior of bldg 3rd fl staircase 'a' water penetra
Mar 16, 2022 · Penalty $1,562
Resolve - Class - 2
Re-issue #35546395x failure to maintain building in code-compliant manner.noted:obseved at bsmt girls gymnasium ceiling missing aprox '20' accoustical ceiling tiles & exposing mechanical/electrical to students
Mar 11, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue: 35490666z exit door not self closing: roof bulkhead,stair'b',3rd floor stair 1,j&g-stair'b',a,auditorium,stair i,j exit 5&6,stair'dexit 9. remedy: comply w/code.
Feb 4, 2021 · Penalty $625
Resolve - Class - 2
Reissue: 35490652h failure to maintain bldg in code compliant manner: noted: doors not closing properly doors are in disrepair/parked. roof bulkhead,stair b,g,i&j double doors near rm 227 throughout entire scho
Feb 4, 2021 · Penalty $1,562
Active - Class - 2
Reissue: 35490665r failure to maintain bldg in code compliant manner: lack of emergency lighting for exits,exit discharges & publuc corridors per bc 100.6; 1/27-542. noted: 3rd stair g,basement stair a&b no exi
Feb 4, 2021 · Penalty $3,125
Resolve - Class - 2
Reissue: 35401965l exit doors not self closing: noted: exit 1,stair'a'basement,boys gym/stair'g' exit 10. remedy: comply w/code.
Feb 4, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue: 35401969z failure to maintain bldg in code compliant manner: noted: accostical ceiling missing,exposing mechanicals open to dust & debris. remedy: comply w/code.
Feb 4, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue: 35490651x failure to maintain bldg in code compliant manner. noted: roof level bulkhead has water penetration/damage to ceiling & floor. also water damage @ electrical room. remedy: comply w/code.
Feb 4, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue: 35490664p failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 27-381;bc1006.1. noted: 1st fl emergency lights @ auditorium & basement caf
Feb 4, 2021 · Penalty $1,562
Resolve - Class - 2
Oil leaking from oil piping at burner-exposed wiring at connection box near incinerator-no guards on gage glass assembly for condensate tank.; correct all violating conditions submit a certificate of correction
Sep 1, 2020 · Penalty $625
Active - Class - 2
Failure to maintain bldg in code compliant manner. noted: at 3rd & 2ndfl hallways installed suspended non fire rated decoration from ceilings. remedy: comply w/code.
Mar 26, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: at roof level stair a bulkhead water penetration/damage to ceiling,wall & floor also at basement electric meter rm w/water penetration/damage through
Mar 26, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner lack of emergency lighting for exits,exit discharges & public corridors per bc 100.6.1/27-542. noted: at(3rd fl)stair g(basement)stair a&b no exit sign/lights
Mar 26, 2020 · Penalty $1,250
Resolve - Class - 2
Exit door not self closing. noted: at(roof)bulkhead stair b,(3rd fl) i,j,g,(2nd fl)stair b,exit 7(1st fl)main entry stair a,hallway double door near stair a,auditorium,stair i,j,exit 5&6(basement)stair d,exit 9
Mar 26, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: at(roof)bulkhead stair b(3rd fl)stair b,g,i,j(2nd fl)stair b,hallway double door near rm 227(1st fl)main entry,stair a,exit 5&6(basement)stair g,a,d,j,
Mar 26, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridors per bc 27-381/bc 1006.1, noted: at(1st fl)auditorium & (basement)cafeteria emergency lights are non
Mar 26, 2020 · Penalty $625
Resolve - Class - 2
Reissue#35291045y failure to maintain in code compliant manner use of prohibited door and or hardware per bc10081.18-2-3710.1.notes; door atexit 1,2,3,4 on 1st floor use of kick stands to keep doors in the open
Mar 13, 2019
Resolve - Class - 2
Exit doors not self closing.exit door not self closing at following locations.exit (1)stair(a)fl,basement #9,#8,3fl boys gym stair g exit(10),rem:repair/replace doors.
Mar 13, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner at time of inspection.noted:at basement stair #7 exit sign hanging hardware is defective exit sign is hanging hardware is defective exit sign is hanging fro
Mar 13, 2019
Resolve - Class - 2
Bc28-301.1/unlawful placement of furninghsing decorations or other objects at exits that obstruct access to egress from or visibility there of as per fdny 2008 code fc803.3.2 at rear of auditorium aisles are pa
Mar 13, 2019
Resolve - Class - 2
Occupancy contrary to certificate of occupancy of dob records.at time of inspection noted at auditorium rear left and right side,movable screws have been rear,left and right side movable screws have been placed
Mar 13, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner.t time of inspection noted at girls gymnasium approximately (20)accostical ceiling this missing exposed mechanicals open to dust and debris.rem:repair repla
Mar 13, 2019
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware per bc 1008.18; 27-371(j). note: doors @ exit# 2,3 & 4, on flr 1,2, & 3, stair b, i & j; cafeteria basement doors toward e
Feb 1, 2018
Resolve - Class - 2
/97x10/ repair device & return to service.
Apr 1, 2015
Active - Class - 2
Roof bulkhead doors -fan room two doors racked. stwy a -hinges, door stwy a -handle stwy a 2nd floor -stwy d, exit 8 door racked, stwy h door racked, cross corridor door near exit h, doors racked, east gymexit
Apr 16, 2014
Resolve - Class - 2
Reissue 34981304l on all levels including bulkheads,too numerous to individually list defective f.p.s.c. doors, some bind on jamb and/or have missing or defective door closers.rem:maintain bldg per code.
Mar 28, 2013
Resolve - Class - 2
Slate stair tread loose/dislodged/trip hazard. at 1st stry stair i 1sttread down toward exit discharge. rem:repair defect noted.
Jun 29, 2012
Resolve - Class - 2
Water damaged plaster ceiling w/section dislodged. at 1st story girls bathroom approx 64 square feet. rem:repair defect noted.
Jun 29, 2012
Resolve - Class - 3
Privacy door/panel displaced/missing. at 1st story boys bathroom. at basement girls bathroom. rem:repair/replace defects noted:
Jun 29, 2012
Resolve - Class - 2
Doors not closing. at basement stair i & stair j. at 1st story stair g& stair i exit vestibule. at 2nd story stair a. at 3rd story stair a,cross corridor door adjoining stair a,stair e,stair h, & stair j. rem:r
Jun 29, 2012
Resolve - Class - 2
The electrical room (b11) is lacking fire-stopping around the pipe penetration going through the wall at the basement level. remedy: provide fire stopping.
Aug 29, 2011
Resolve - Class - 2
The exit door at basement level is missing a door closer by room b6. remedy: replace missing door closer.
Aug 24, 2011
Resolve - Class - 2
Reissue: 34856017k the plaster on the wall & ceiling is spalling located at exit stair "e" 1st floor level. remedy: repair and/or replace plaster.
Aug 24, 2011
Resolve
Complaints
- Heat/hot water
Entire building
Feb 23, 2026 · Apt BLDG
Close - Heat/hot water
Apartment only
Feb 23, 2026 · Apt 3E
Close - Heat/hot water
Entire building
Dec 1, 2024 · Apt BLDG
Close - General
Bell/buzzer/intercom
Sep 9, 2022 · Apt 3A
Close - General
Cabinet
Jun 30, 2019 · Apt 5G
Close - General
Bell/buzzer/intercom
Jun 30, 2019 · Apt 5G
Close - Flooring/stairs
Stairs
May 23, 2019 · Apt 5G
Close - Appliance
Electric/gas range
Aug 14, 2018 · Apt 5G
Close - General
Bell/buzzer/intercom
Aug 14, 2018 · Apt 5G
Close - Unsanitary condition
Pests
May 9, 2018 · Apt 5G
Close
Show 5 more ↓
- General
Cabinet
Jul 7, 2015 · Apt 5G
Close - Plumbing
Bathtub/shower
Jul 7, 2015 · Apt 5G
Close - Appliance
Refrigerator
Jul 7, 2015 · Apt 5G
Close - Heating
Heat related
Dec 5, 2013 · Apt 3J
Close - Heating
Heat related
Nov 16, 2013 · Apt 1A
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1950
- Floors
- 3
- Residential units
- —
- Building area
- 163,572 ft²
- Lot area
- 77,373 ft²
- Zoning
- R7-1
- Community board
- 204
- Council district
- 16
- Block / lot
- 2438 / 50
- Assessed value
- $12,714,750
- Landmark / historic district
- No
Questions about 1150 Morris Avenue
Who owns 1150 Morris Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 1150 Morris Avenue have violations?
Yes. NYC HPD has recorded 1 housing violations at this property.
Is 1150 Morris Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 1150 Morris Avenue built?
City records list 1950 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.