500 East 134 Street

Bronx, NY 10454BBL 2-02261-0005Map

Owner of record: 500 East 134th Owners LLC

500 East 134 Street is a hotel built in 1931 in Bronx, 10454. The owner of record is 500 East 134th Owners LLC. HPD has recorded 6 housing violations here, most recently on June 5, 2025.

HPD violations
6
DOB violations
27
ECB violations
28
HPD complaints
24

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
Last violation Jun 5, 2025

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 6

  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Jun 5, 2025

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Apr 2, 2021

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Apr 2, 2021

    Closed — Violation dismissed
  • C

    Provide an adequate supply of heat for the apartment in the entire apartment located at apt 407, 4th story, 2nd apartment from west at north

    Dec 2, 2019 · Apt 407

    Closed — Violation closed
  • C

    Provide hot water at all hot water fixtures in the entire apartment located at apt 407, 4th story, 2nd apartment from west at north

    Dec 2, 2019 · Apt 407

    Closed — Violation closed
  • C

    Provide ready access to buildings heating system boiler room door locked at basement

    Dec 2, 2019

    Closed — Violation closed

DOB building violations · 27

  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Nov 22, 2023

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 10, 2020

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator - failure to file category 1 2017 inspection/test

    Apr 5, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Apr 4, 2018

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Nov 15, 2017

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2016 inspection/test

    Sep 15, 2017

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2015 inspection/test

    Dec 1, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 5, 2015

    Dob violation - resolved
Show 17 more ↓
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 18, 2010

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 4, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 23, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 30, 2006

    Dob violation - resolved
  • Construction other optional

    C-construction other optional

    Jun 6, 2005

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 15, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 21, 2003

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 6, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - active
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 1996

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 17, 1995

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Oct 12, 1989

    Dob violation - dismissed

ECB violations · 28

  • Class - 2

    Class 2: hoist cables show signs of rouge/defective condition. fire extinguisher provided is class b:c only. maintenance log not up to date. city id tag on car station unreadable. top of car junction box cover

    Apr 28, 2026 · Penalty $310

    Active
  • Class - 1

    Observed in laundry room on first floor 4in pvc pipe being used on roof drains. which is contrary to code pc 701.9 plastic piping and fittings shall not be used, repair and/replace

    Apr 28, 2026 · Penalty $2,500

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. observed no 2ndmeans of egress. fire escape leads back into the building. potential hazard., repair and/or replace

    May 5, 2025

    Resolve
  • Class - 2

    Class 2 item: hoist ropes show sign of rouge. ropes need to be shortened. provide a city id number in car station.

    May 5, 2025 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. observed stand pipe clearance from staircase. potential hazard, repair and/or replace

    May 1, 2025 · Penalty $1,250

    Active
  • Class - 1

    Unlawful acts: failure to comply with the commissioners order contained in summons/violation# 39093766m issued on 8/30/2023 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01., comply

    May 28, 2024

    Resolve
  • Class - 1

    Unlawful acts: failure to comply with the commissioners order contained in summons/violation# 39093766m issued on 08/30/23 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. (failure

    Dec 22, 2023 · Penalty $625

    Resolve
  • Class - 1

    I observed on multiple occasions the main entrance & the curb cut designed for access by wheelchairs or mobility assistance devices blocked by the personal vehicle of the shelter food vendor. the points of egre

    Aug 30, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    I observed on the rooftop the use of flexible wiring from the outdoor compressor unit to the wall blower unit in the elevator motor room, as per ec 400.8 flexible wiring shall not be used as permanent wiring no

    Aug 22, 2023

    Resolve
  • Class - 2

    I observed on the rooftop the installation of a a.c. split system to supply cooling to the elevator motor room. all of the equipment in use were dated after the final inspection date of the electrical permit. p

    Aug 22, 2023

    Resolve
Show 18 more ↓
  • Class - 1

    Emergency phone not working; alarm bell not working; brake switch on machinery is damaged and broken; repair;unknown jumpers on controller; remove jumper ; cat 5 tags are expired

    Aug 21, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    I observed in the rooftop elevator motor room the installation of conduits, junction boxes and branch circuit wiring for a split a.c unit, the compressor on the exterior wall. no permit in dob records covers th

    Apr 21, 2023

    Resolve
  • Class - 2

    I observed in the elevator motor room the installation of bx cabling through the masonry wall. this not permitted. as per ec 320.12; ec 320.12, comply with ec code; use only as permitted

    Apr 21, 2023

    Resolve
  • Class - 2

    I observed in the stairwells from the roof to the basement fixed electric heaters without the required disconnect as per ec 424.19, an equipment disconnect shall be installed., comply with ec; install equipment

    Apr 21, 2023

    Resolve
  • Class - 2

    No ventilation in the boiler room located in the basement/cellar. the room has 2 gas fired water heaters. as per 304 of the fgc gas fired appliances must have ventilation., repair and/or replace

    Mar 22, 2023

    Resolve
  • Class - 2

    Noted: observed fpsc stair door at 1st. floor stair "a" is loose and detaching from wall on the hinge side which is causing the door not to self closing properly., repair and/or replace

    Apr 5, 2022

    Resolve
  • Class - 2

    Noted: observed at roof's south elevation, elevator machine room's exterior wall have horizontal and vertical cracks approx. 6ft in length as well as spalling cement stucco., maintain exterior building wall

    Apr 5, 2022 · Penalty $625

    Resolve
  • Class - 2

    I observed on the rooftop unsecured wiring, junction boxes, improperly terminated flexible cords and bx cabling in the mechanical rooms on each floor not supported properly., secure/support per ec; support boxe

    Oct 19, 2021

    Resolve
  • Class - 1

    (cease use-42m7)dpm not working code data tag a17.1-2000/2003 provide.

    Sep 13, 2019 · Penalty $1,250

    Resolve
  • Class - 2

    6b10,21m7,67b10. 6b10-door position monitoring did not work code dateplate 2000/03; 21m7-missing interlock cover on top floor; 67b10-in carphone needs to be reprogram.

    Sep 11, 2018 · Penalty $312

    Resolve
  • Class - 1

    97x17,c/u 66h11. 97x17 only car in building out of service upon arrival creating a hazardous condition.for public and tenants musct repair back to service immediately.66h11 c/u rope grippe pads completely worn

    Jan 10, 2018 · Penalty $1,000

    Resolve
  • Class - 3

    Failure to maintain building in code compliant manner.noted: at time of inspection observed the steel support of the ceiling of the electrical room at the basement level is rusted and flaking,as a result decre

    Dec 27, 2017 · Penalty $100

    Resolve
  • Class - 2

    Failure to comply w/the comm's order contained in summons/vio#35287372j issued on 08/16/17 & to file a c of c pursuant to 28-201.1 & 1rcny 102-01. remedy: comply w/comm's order &/or file a c of c.

    Dec 21, 2017

    Resolve
  • Class - 1

    Failure to maintain building in code-compliant manner. at time of my inspection, i observed standpipe in building not protected with fire rated enclosure. standpipe not in staircase, standpipe in public space.

    Aug 24, 2017 · Penalty $1,000

    Resolve
  • Class - 2

    97##5-failure to maintain elefvator device respondent failed to allow mandatory annual/routing inspection by the department or approved agency for 28-304.6.1 and apendix k of the building code.multiple attempts

    Sep 25, 2013

    Resolve
  • Class - 2

    12b7.12q3.39q3.60q3.69m7.12b7 provide sufficent light in car replace llight fixture 39q3 install guard fro light top of car 64a11 replace a;tered nyc device # tag w/correct device #2p3837 and not 2f3837

    Oct 14, 2009

    Resolve
  • Non-hazardous

    Failure to maintain building. defect is: an approx 20' x 60' advertis-ing sign attached to roof of above location has section of metal sheeting that have come loose & have fallen onto brooke ave. there are also

    May 14, 2002 · Penalty $180

    Resolve
  • Non-hazardous

    Replace steam safety valve for 15 p.s.i. type a.s.m.e. approved side outlet. clean firetubes of soot. install chain on lever of steam safety valve. replace baronstris damper defective.

    Jul 10, 1989

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Dec 10, 2025 · Apt 409

    Close
  • Heat/hot water

    Entire building

    Dec 2, 2025 · Apt 409

    Close
  • Heat/hot water

    Entire building

    Nov 21, 2025 · Apt 502

    Close
  • Heat/hot water

    Entire building

    Dec 21, 2024 · Apt 15

    Close
  • Heat/hot water

    Apartment only

    Dec 12, 2024 · Apt 302

    Close
  • Heat/hot water

    Entire building

    Dec 9, 2023 · Apt 510A

    Close
  • Heat/hot water

    Entire building

    May 2, 2023 · Apt 414

    Close
  • Heat/hot water

    Entire building

    Mar 8, 2023 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Jan 3, 2022 · Apt B02

    Close
  • Heat/hot water

    Apartment only

    Jan 2, 2022 · Apt B02

    Close
Show 14 more ↓
  • Heat/hot water

    Entire building

    Mar 16, 2021 · Apt 102

    Close
  • Heat/hot water

    Entire building

    Dec 7, 2020 · Apt 315

    Close
  • Heat/hot water

    Entire building

    Nov 4, 2020 · Apt 315

    Close
  • Heat/hot water

    Entire building

    Nov 1, 2020 · Apt 315

    Close
  • Heat/hot water

    Entire building

    Oct 18, 2020 · Apt 315

    Close
  • Heat/hot water

    Entire building

    Oct 18, 2020 · Apt 315

    Close
  • Heat/hot water

    Entire building

    Feb 17, 2020 · Apt 407

    Close
  • Heat/hot water

    Entire building

    Dec 16, 2019 · Apt 414

    Close
  • Heat/hot water

    Entire building

    Dec 8, 2019 · Apt 412

    Close
  • Heat/hot water

    Entire building

    Dec 2, 2019 · Apt 407

    Close
  • Heat/hot water

    Entire building

    Jan 24, 2019 · Apt 104

    Close
  • Heat/hot water

    Entire building

    Jan 22, 2019 · Apt 513

    Close
  • Heat/hot water

    Entire building

    Feb 27, 2018 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Feb 1, 2018 · Apt 1

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Hotel (H9)
Year built
1931
Floors
6
Residential units
—
Building area
41,080 ft²
Lot area
9,000 ft²
Zoning
M1-2/R6A
Community board
201
Council district
8
Block / lot
2261 / 5
Assessed value
$2,577,150
Landmark / historic district
No

HPD registration #227762, last renewed Oct 11, 2025.

Questions about 500 East 134 Street

Who owns 500 East 134 Street?

The owner of record in NYC Department of City Planning PLUTO data is 500 East 134th Owners LLC.

Does 500 East 134 Street have violations?

Yes. NYC HPD has recorded 6 housing violations at this property.

Is 500 East 134 Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 500 East 134 Street built?

City records list 1931 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.