Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 0

No DOB violations on record

ECB violations · 19

  • Class - 1

    Failure to comply with the commissioner's order summons 35644718k 35343150h 35343154p 35343155r 35343156z and 35343157k still exists, comply with commissioner's order; comply with code

    Mar 24, 2022 · Penalty $6,250

    Resolve
  • Class - 1

    Unlawful acts.fail to comply with an order of commissioner.fail to correct and certify ecb#35343154p-no gfci provided outdoor ecb#35343155r-fixable metal conduit more than 6 ft ecb#35343150h-failure to ground,n

    Feb 9, 2022 · Penalty $12,500

    Active
  • Class - 1

    Unlawful acts.failure to comply with an order of the commissioner.failure to correct and certify summons ecb#35343950h;ecb#35343154p and ecb#35343156z.unapproved,unsafe,unsuitable electrical equipment apparatus

    Dec 21, 2021 · Penalty $12,500

    Active
  • Class - 1

    Unlawful acts. failure to comply w/ an order of the commissioner. failure to correct and certify summons#35343150h no water main ground,summons#35343151j gec is not of proper size,summons#35343154p outdoors and

    Nov 6, 2021 · Penalty $2,500

    Active
  • Class - 1

    Failure to comply with the commissioner's order summons 35343150h and 35343155r still remains, comply with commissioner's order; comply with code

    Sep 23, 2021 · Penalty $12,500

    Active
  • Class - 2

    Failure to comply w/ commissioner's order contained in summons/violation#35343248x issued on 8/6/18,and to file a certificate of correction pursuant to 28.201.1 and 1rcny 102-01(d)(2). an acceptable certificate

    May 21, 2019

    Active
  • Class - 1

    210.8.b.gfci is not provided for outlets outdoor and outdoor baks entire grounds outdoor area,rec area,women locker room,sheds.rem:comply with ec code must file an electrical application

    Oct 5, 2018

    Active
  • Class - 1

    350.12.3.amendment.flexible metal conduit feeding outdoor ac unit behind bak is more than 6ft.rem:comply with ec code.must file an electrical application

    Oct 5, 2018

    Active
  • Class - 1

    Unapproved/unsafe/unsuitable electrical equipment apparatus,materials,devices,appliances or wiring in use.emt used outdoor to supply power to women locker room.rem:comply with ec code must file an electrical ap

    Oct 5, 2018

    Active
  • Class - 1

    Unapproved/unsafe/unsuitable electrical equipment apparatus,materials,device appliances or wiring in use,flexible cord used as permanent wiring outdoor flexible cord used as permanent wiring outdoor feeding fas

    Oct 5, 2018

    Active
Show 9 more ↓
  • Class - 1

    Tuble250.66.bonding conductor is not of proper size at ser sw (200a)#8ser ent building cond.used for 2/0 ser ent conductor.bond is not as per table 250.66.rem:comply with ec code must file an electrical permit

    Oct 5, 2018

    Resolve
  • Class - 1

    Failure to ground electrical system.no water main ground is provided at water main for you a senswis.rem:provide grounding.must file an electrical application

    Oct 5, 2018

    Active
  • Class - 1

    Table 250.66.grounding conductor at 400 ser sw is not of proper size #8 bare solid conductor use for ser entrnace conductor 500 inch grounding conductor is not as per table.rem:comply with ec code must file an

    Oct 5, 2018

    Active
  • Class - 1

    Bc250-118.7..flexible metallic raceway fuled over a 20a in ser room isnot provided with an equipment ground.fused at 200a from 200a ser/swo.rem:comply with ec code.must file an electrical application

    Oct 5, 2018

    Resolve
  • Class - 2

    Fail to provide/maintain sufficient access/workspace about electrical equipment.min clearance is not provided in front of electrical panels in kitchen elect area.rem:provide/maintain access/work space

    Oct 5, 2018

    Active
  • Class - 2

    Unapproved/unsafe/unsuitable/electrical equipments,apparatus,materials,devices,apparatus or wiring in use.externsion cords & fixture/zip cords used as permenant wiring throughout.rem:comply w/ec code/obtain per

    Aug 6, 2018 · Penalty $800

    Active
  • Class - 1

    Work without a permit.at the time of my inspection i observed the installation of mobile bathroom at the rear of the establishment i also observed that these bathrooms had pvc piping used for the waste lines i

    Jul 24, 2018

    Active
  • Class - 1

    Gfc503.4.1.misc violations use of approved maintain.on the above mentioned date i observed pvc piping being used to vent 2 hot water heatersat this property which is not permitted as per the code.rem:comply wi

    Jul 24, 2018

    Active
  • Class - 2

    Failure to maintain building in a code compliant manner.failure to comply with law for drainage system per 702.1;27-911;the above mention date i observed the use of pvc piping used throughout premises.the pipin

    Jul 24, 2018

    Active

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Outdoor recreation (Q1)
Year built
—
Floors
—
Residential units
—
Building area
—
Lot area
65,200 ft²
Zoning
PARK
Community board
112
Council district
10
Block / lot
2178 / 530
Assessed value
$428,400
Landmark / historic district
No

Questions about 348 Dyckman Street

Who owns 348 Dyckman Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Parks And Recreation.

Does 348 Dyckman Street have violations?

NYC HPD has no housing violations on record for this property.

Is 348 Dyckman Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.