195 West 134 Street
Manhattan, NY 10030BBL 1-01919-0006Map
Owner of record: NYC Department Of Education
195 West 134 Street is a school building built in 1957 in Manhattan, 10030. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 43
- ECB violations
- 79
- HPD complaints
- 10
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 43
- Construction other optional
Ftm building exterior walls facade and appurtenances. exp1 south elev defected conditions-cracks, damaged window sill, spalling open joints, items on window ledge. remedy: maintain bldg exterior walls facade and appurtenances. repair as per 1rcny 103-04
Jun 2, 2022
Dob violation - active - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2020)
Jun 20, 2021
Dob violation - dismissed - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 in 2019
Jun 29, 2020
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 20, 2019
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 8, 2017
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 11, 2015
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 2, 2015
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - dismissed
Show 33 more ↓
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 24, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 5, 2012
Dob violation - resolved - Construction other optional
C-construction other optional
Jul 1, 2010
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 10, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 27, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 25, 2008
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Nov 19, 2004
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 9, 2004
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 21, 2004
Dob violation - dismissed - Elevator elevatorrequired
1f5009
Apr 2, 2003
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 19, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 20, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 6, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 1996
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 18, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 18, 1993
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 7, 1992
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 25, 1991
Dob violation - dismissed
ECB violations · 79
- Class - 2
Reissued ecb #35721534m. failure to maintain building in code-compliant manner. noted fpsc smoke doors not self-closing at. 3rd floor by room #309, gym(one door). remedy: repair and/or replace.
Aug 3, 2026 · Penalty $3,125
Active - Class - 2
28-301.1. reissued ecb #35721502z. failure to provide ventilation to gas meter room per p115.6, fgc appendix e. noted no ventilation installed at gas meter room. remedy: comply with notice of violation.
Aug 3, 2026 · Penalty $3,125
Active - Class - 2
: failure to maintain building in code compliant manner. upon inspection, the device is found to be out of service. remedy: restore to service.
Jan 30, 2026 · Penalty $625
Active - Class - 2
28-301.1. reissue #35688999k date of issue: 09-19-2024. failure to provide ventilation to gas meter room per p115.6(1968 code), fgc appendixe(e4)(2014 code). at the time of inspection observed and noted at gas
Aug 4, 2025 · Penalty $3,125
Active - Class - 2
Exit door not self-closing properly. at the time of inspection observed and noted at 3rd floor near rm #309 one corridor exit door, 2nd floor stairway "c" 1 exit door, at 1st floor exit-4 1 exit door, at 1st fl
Aug 4, 2025 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection observed and noted at 1st floor gym two place
Aug 4, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: interiorfire proof self-closing doors not working properly.-at 3rd fl stairwell "c", 2nd fl. corridor smoke doors by rm #249 are racked, gym entry d
Sep 19, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted at 2nd flrm #201 and at auditorium exit #6b, spalling/crumbling plaster on walls. remedy: repair and/or replace.
Sep 19, 2024 · Penalty $625
Resolve - Class - 2
28-301.1. reissue #35663404l. failure to provide ventilation to gas meter room per p115.6(1968 code), fgc appendix e(e4)(2014 code). noted at gas meter room, no natural or mechanical ventilation provided. remed
Sep 19, 2024 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1, 27-381. noted emergency lights not working at gymnasium(2-lights), cafeteria(1-
Sep 19, 2024 · Penalty $625
Resolve
Show 40 more ↓
- Class - 2
Failure to maintain building in code-compliant manner. noted at top roof level, peeling/missing sections of insulation, exposing defective water proof membrane. moss growing around several roof's surture drains
Sep 19, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted, peeling and missing cement finish, expsoing bricks at the exp #4(east) exterior wall along w 134 st adjacent property vehicle access ramp. remedy: r
Sep 19, 2024 · Penalty $625
Resolve - Class - 2
Exit door not-self closing. noted exterior doors at exit #7 and 8 not properly self-closing when tested. remedy: repair/replace doors.
Sep 19, 2024 · Penalty $625
Resolve - Class - 2
28-301.1 reissue #35658064h date of issue: 05.23.2022 failure to providde ventilation to gas meter room per p115.6 (1966 code), fgc apendix e(e4) (2014 code). at time of inspection noted no mechanical or natura
Jun 1, 2023 · Penalty $3,125
Active - Class - 2
Temporary construction on site-expired permit.note:permit expired on date of inspection 02/09/21 #122656009-01-eq-sh.remedy:renew permit.
Jun 2, 2022
Resolve - Class - 2
28-301.1 reissue35582146n failure to provide ventilation to gas meter rm per 115.6(1965code)/ac apdxe(e4)(2014code).atoi i observed@gas meter@bsmt level no fresh air or mechanical ventilation was provided@gas m
May 23, 2022 · Penalty $3,125
Active - Class - 1
Out of service return to service
Nov 12, 2021 · Penalty $3,125
Active - Class - 2
28.301.1 - re-issue #35495824h failure to provide ventilation at gas meter room at time of inspection noted: no mechanical or natural ventilation at cellar gas meter room. remedy:
Jun 29, 2021 · Penalty $3,125
Active - Class - 2
Re-issued #35495822y exit doors no self closing.exit #1 door at 1st floor not self closing when tested.remedy:comply with code.
Jun 29, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to maintain buidling in code compliant manner illumination for exits ,exit discharges and public corridors per bc 1006,1/27-381 note dat (1st fl) cafeteria gym auditorium and main entry emergnecy lighst
May 29, 2020 · Penalty $625
Resolve - Class - 2
Failure to mainatin building inc ode compliant manner note dat (1st fl) exit 4 and gym doors are in disrepair /racked in various lcoations repair and or replace
May 29, 2020 · Penalty $625
Resolve - Class - 2
Exit door not self closing noted at (1st fl) exit 1 door check in disrepair /non operatinal when tested repair replace door
May 29, 2020 · Penalty $625
Resolve - Class - 2
28-301.1-failure to provide ventilation to gas meter room per p115.6 fgc appendix e (e4) noted observed gas meter r with having no ventilation system insatlled comply with notice of violdation
May 29, 2020 · Penalty $1,250
Active - Class - 2
28-301.1 reissue#35326089n date of issue 3/27/18 failure to provide ventilation to gas meter room per p115.6(1968 code) fgc appendix e(e4)(2014 code) at the time of inspection the room that has gas meter room a
Jun 13, 2019
Active - Class - 2
Reissue#35324938j date of issue 3/27/18 failure to maintain building in code-compliant manner illumination for exits,exit discharges and public corridors per bc 1006.1;27-381 at 1st fl auditorium exit-8 exit li
Jun 13, 2019
Resolve - Class - 2
Exit door not self closing properly,at 1st fl stair way "a" 3 doors 2 doors outside 1 door inside,at 1st fl main entrance outside 1 door notself closing properly at the time of inspection when we tested. remedy
Jun 13, 2019
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. illumination for exits,exit discharges & public corridors per bc 1006.1;27-381 emergency lights defective at the following locations. auditorium & exit 8.
Mar 27, 2018
Resolve - Class - 2
28-301.1 failure to provide ventilation to gas meter room per p115.6 (1968 code) fgc appendix e (34) (2014 code) noted: at the time of in spection the room that syas gas meter room at basement level doesn't h
Mar 27, 2018
Active - Class - 2
Reissue#35213693z faiure to maintain bldg in code compliant manner-basement corridor obstructed w/deck(storage)& other debris. remedy: comply w/code.
Mar 27, 2018 · Penalty $6,250
Resolve - Class - 3
Failure to maintain bldg in code compliant manner. (a) @ play yard, ground sinking @ drain, buldging/unlevel surface. (b) @ exit#4 @ egress to play area, ramp masonry cracked & spalling. rem: comply w/ code, re
Sep 27, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: lack of power for emergencies or storage battery connection to exit sign per bc 1011.5.3, 27-384. (a) @ stair b, @ 1st flr emergency light number(s) #6,#9,
Sep 27, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. provide required corridor width. reissue nov# 35147015r. noted: @ baseement, corridor obstructed w/ desks (storage) & other debris. rem: comply w/ code.
Sep 27, 2016
Resolve - Class - 2
Exit door not self closing. noted: @ stair a @ 1st flr self closing door stuck in open position. rem: comply w/ code.
Sep 27, 2016
Resolve - Class - 2
Reissue #35085948h exit door not self closing. 2nd flr smoke doors near room 208 and 1st flr gym door not closing. rmdy: repair/replace doors.
Sep 11, 2015
Resolve - Class - 2
Failure to maintain building in code-compliant manner: provide required corridor width per bc 1016.2; 27-369. noted: at basement level partial corridor obstruction with apprx 30% obstruction w/computers,chairs
Sep 11, 2015
Resolve - Class - 2
Reissue:35002841l.2nd fl smoke doors near room 208 are recked.1st fl gym door not closing.rem:repair/replace doors.
Mar 13, 2014
Resolve - Class - 2
Reissure 34954442x doors at 1st floor stair a, exit 4 1st flr and 2nd flr corridor near rm 208 are racked,corridor doors at 3 flr near room 312,and doros to rooms 301,303,308,312,319,109 and door at left of sta
Jan 18, 2013
Resolve - Class - 2
3rd flr stwy "a" corridor smoke doors near rooms 312 & 309 & 2nd flr stwy "a" doors not closing due to illegal hardware installed. (hold backs). rem:remove illegal hardware.
May 2, 2012
Resolve - Class - 2
At cellar level hole in wall near door where data cables penetrations exist. rem:provide/maintain fire stopping.
May 2, 2012
Resolve - Class - 2
Electrical room at cellar level is being used to store box's,tv,carts etc.. remedy: remove storage from electrical room.
Jun 15, 2011
Resolve - Class - 2
Reissue 34839448n 2nd floor corridor smoke doors near rm 219 racked. 1st floor exit door to play yard from auditorium (right side) is racked. remedy: repair/replace doors.
Jun 15, 2011 · Penalty $2,500
Resolve - Class - 2
3rd fl stwy "b" door racked. 2nd fl stwy "c" door racked, corridor smoke doors near room 219 racked, 1st fl auditorium stage left exit door & front left exit door not closing. remedy: repair / replace doors
Apr 16, 2010
Resolve - Class - 2
Reissue: 34792779m electrical room @ cellar level is being used to store a table & chairs. remedy: remove storage form electrical room
Apr 16, 2010
Resolve - Class - 2
Bc1017.1 27-369 corridor width decreased at 2nd fl near room 201-204 with tables and chairs rem: remove items from corridors provide proper corridor width
Jun 19, 2009
Resolve - Class - 2
Gas meter room and electrical room at cellar lvl is being used to store tables windows plastic buckets wheel barrels etc rem: remove storagefrom gas meter room and electrical room
Jun 19, 2009
Resolve - Class - 2
Stwy labels missing at stair case size of stairway from 1st fl to 3rd fl all stwy rem: provide letter stwy labels for all stwy where missing
Jun 19, 2009
Resolve - Class - 3
50. lp firetube, firebox boiler #1.50-referenced boiler structure has an elevation in excess of 8ft.the boiler must be equipped w/a fixed ladder & associated platform to facilitate safe access by operations,mai
Nov 21, 2008
Resolve - Class - 3
50. lp firetube,firebox,boiler #2.50-referenced boiler structure has an elevation in egress of 8ft.the boiler must be quipped w/a fixed ladder & associated platform to facilitate safe access by operations maint
Nov 21, 2008
Resolve - Hazardous
Interior classroom door is defective (door handle is broken) located in room 209 on the 1nd flr. remedy: repair/replace interior door w/ handle.
Jul 11, 2007
Resolve - Hazardous
Interior hallway leading to exit door is partially blocked w/ books & school furniture located on cellar level adj to electrical room. remedy: remove obstruction.
Jul 11, 2007
Resolve
Complaints
- Plumbing
Basin/sink
Sep 24, 2025 · Apt 3C
Close - Water leak
Heavy flow
Sep 24, 2025 · Apt 3C
Close - General
Bell/buzzer/intercom
Jun 1, 2023 · Apt 3B
Close - Heat/hot water
Entire building
Oct 4, 2022 · Apt 1
Close - Heat/hot water
Entire building
Dec 11, 2014 · Apt 1F
Close - Appliance
Refrigerator
Jul 9, 2010 · Apt 7
Close - Nonconst
Odor
Jun 26, 2004 · Apt BLDG
Close - Nonconst
Vermin
Jun 26, 2004 · Apt BLDG
Close - Nonconst
Odor
Jun 26, 2004 · Apt BLDG
Close - Electric
Lighting
Mar 10, 2004 · Apt 4
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1957
- Floors
- 3
- Residential units
- —
- Building area
- 219,780 ft²
- Lot area
- 77,435 ft²
- Zoning
- R7-2
- Community board
- 110
- Council district
- 9
- Block / lot
- 1919 / 6
- Assessed value
- $10,603,350
- Landmark / historic district
- No
Questions about 195 West 134 Street
Who owns 195 West 134 Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 195 West 134 Street have violations?
NYC HPD has no housing violations on record for this property.
Is 195 West 134 Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 195 West 134 Street built?
City records list 1957 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.