535 East 119 Street

Manhattan, NY 10035BBL 1-01816-0001Map

Owner of record: NYC Department Of Education

535 East 119 Street is a school building built in 1968 in Manhattan, 10035. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
39
ECB violations
103
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 39

  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Residential elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Jun 1, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 14, 2015

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2014 inspection/test

    Jun 10, 2015

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 14, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 18, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 8, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 1, 2010

    Dob violation - resolved
Show 29 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 18, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 16, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 16, 2007

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 21, 2005

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 21, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 12, 2003

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Jan 12, 1999

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 6, 1998

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - active
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 1996

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 17, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 28, 1993

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 29, 1990

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Oct 12, 1989

    Dob violation - dismissed

ECB violations · 103

  • Class - 2

    Temporary construction equipment on site -expired permit. the sidewalk shed permit in place expired 03/20/2026 and not in the dob system for renewal. permits must be maintained for the duration of the use of t

    Aug 21, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissued ecb#35725246x failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors perbc 1006.1;27-381.noted emergency lights not working at gym and through

    Jul 28, 2026 · Penalty $3,125

    Resolve
  • Class - 2

    Reissued ecb#35725242z unlawful placement of furnishings,decorations or other objects at exits that obstruct access to egress from or visibility thereof per fdny 2008 code;fc 1027.4.noted non-fire retandent art

    Jul 28, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissued ecb#35725247h failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371.noted slide bolt locking devices installed at exit#16 doors.rem:provide

    Jul 28, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissued ecb#35725245y exit door not self-closing.noted exit doors#10,#11,#14,#15 in disrepair/rusty and not self-closing.rem:repair/replacedoor.

    Jul 28, 2026 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted roof generator not working.rem:repair and/or replace.

    Jul 28, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted fpsc smokedoors not operating properly at:1st floor main entrance and stair e and d;2nd floor by stair f,e,hallway smoke door by room#244;3rd floor st

    Jul 28, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at(1st fl) gym emergency lights not working throughout various a

    Sep 9, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Exit door not self-closing. noted: at(1st fl) stair a, exit 3, 1 doorsare in disrepair/not closing when tested. remedy: repair/replace door.

    Sep 9, 2025 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at 1st fl installed non-fire retardent to ceilings throughout various areas. remedy: comply with code.

    Sep 9, 2025 · Penalty $1,250

    Active
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at 1st fl installed non-fire retardent decorations to cielings throughout various areas. remedy: comply with code.

    Sep 9, 2025 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing. noted: at(1st fl) main entrance, stair e, d, exit 10, 11, 14, 15(2nd fl) stair f, e hallway smoke door near rm 244(3rd fl) stair e all doors in disrepair/not closing when tested. als

    Sep 9, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8. 27-371(j). noted: at(1st fl) exit 16 installed slide bolt locking devices. remedy: provide legal ha

    Sep 9, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35663589r exit door not self-closing.noted:all the exit door either rusted/needs excessive force to open or not self-closing.rem:repair/replace door.

    Sep 3, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at 3rd floor stairway b do not close properly.rem:repair & or replace.

    Sep 3, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at first floor room#103 and stairway a do not close properly.rem:repair/replace door.

    Sep 3, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1;27-371(j).noted:exit#2,stairway bstairway e and exit 12 doors are attached with kickdown door holders.r

    Sep 3, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.provide requiredcorridor width per bc 1016.2;27-369.noted:at cellar corridor 50% widthblocked by t.v.'s,card board boxes,plastic bins,etc.rem:provide proper

    Sep 3, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1-8;27-371(j).noted:kickdown door holders are attached to classroom door#204,210,319.rem:remove illegal h

    Sep 3, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: observed in basement level hallways have excessive storage of flammable material-ie book, boxes, furniture, tv on both sides of walkway from floor t

    Jul 12, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: observed during inspection of roof level, roofing paper bubbling up detaching from subfloor in various locations. remedy: repair and/or replace

    Jul 12, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: observed during inspection of roof level, roofing paper detached from subfloor. paper bubbling in various locations and standing water at drains. re

    Jul 12, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: observed during inspection of bulkheads leading to roof walls have become porous in each stairwell bulkhead allowing water to penetrate into stairwe

    Jul 12, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: observed during inspection of 1st floor room 131, wall by window spalling/peeling plaster, ceiling tile browned/damaged. remedy: repair and/or repla

    Jul 12, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: observed during inspection of basement, excessive storage of flammable material, from floor to ceiling on both sides of the hallway. no sprinkler sy

    Jul 12, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35655381h 6/7/22 exit door not self closing. noted: observed during inspection of all exterior doors, when tested doors were not operating correctly. when tested doors not self closing or needed great

    Jul 12, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: observed during inspection of roof access bulkheads, walls have become porous allowing water to penetrate into stair wells. 1st floor room 131 wall

    Jul 12, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35655381h 6/7/22 exit door not self closing noted: observed during inspection of all exterior doors. doors not operating/closing correctly when tested, doors need great force to open and to close. reme

    Jul 12, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: observed during inspection of facade at e 119th st wall over exit 1 and over 3rd fl windows had concrete spalling, bulging and cracking remedy: repa

    Jul 12, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.illumination for exits exit discharges & public corridors per bc 1006.1;27-381 at time of inspection observed basement level front of electrical room one em

    Jun 7, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.at 1st floor gym exit to ps-112(rm no-271)emergency exit door push bar is not working(exit door locked)repair or replace push bar.remedy:repair or replace p

    Jun 7, 2022 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing properly at time of inspection.at time of inspection observed at 1st floor near stairway "e" exit doors & 1st floor auditorium exit-to(ps-112)rm no-116 1 exit door.at 2nd floor near s

    Jun 7, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits exit discharges & public corridors per bc 1006.1;27-381 at time of inspection oberved at 1st floor near main entrance near stairway"

    Jun 7, 2022 · Penalty $625

    Resolve
  • Class - 2

    Exit door not selfclosing properly atoi.@1fl exit to outside 1exit door,inside 1exit door (near gym) @1fl near stairwaya 2exit doors,@3fl near stairwaya&b each place 1exit door not selfclosing properly atoi.rep

    Jun 7, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27.371(j). use of dead bolt locking devices which require a key to operate on both sides. exit door

    Jun 14, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. existing emergency lights not operational when tested at - auditorium,

    Jun 14, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner at stair (d) 5th fl 6' vertical crack in cmu block wall. rem: repair/replace.

    Jun 14, 2018

    Resolve
  • Class - 2

    Exit door not self-closing, next to room #426 exit door not self-closing. rem: repair/replace door.

    Jun 14, 2018

    Resolve
  • Class - 2

    28-301.1 failure to maintain building in code-compliant manner. storage of portable fueled equipment. as per fc313-(2) riding mowers in storage room next to cafeteria. rem: remove gas fueled equipment from bldg

    Jun 14, 2018

    Resolve
  • Class - 2

    28-301.1 unlawful placement of furnishings, decorations or other objects at exits that obstruct access to egress or visibility thereof per fdny 2008; fc 1027.4. outside of classroom #223 furniture, chairs, obje

    Jun 14, 2018

    Resolve
  • Class - 2

    Reissue#35207147k exit door not self closing. noted: at stairway'e'4thfl & stairway'd'1st fl ,exit doors not self closing. remedy: repair &/or replace door.

    Jun 14, 2017

    Resolve
  • Class - 2

    Reissue#35207148m failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: at stairway d 4th fl,stairway f,3rd fl room 340,& stai

    Jun 14, 2017

    Resolve
  • Class - 2

    Failure to maintain excessive supply storage @ 1st flr service entrance storage of supply block egress. rem: remove obstruction.

    Nov 1, 2016

    Resolve
  • Class - 2

    Exit door not closing @ stairway e- 4th flr & stairway d- 1st flr. rem: repair or replace.

    Nov 1, 2016

    Resolve
  • Class - 2

    Failure to maintain. emergency lights not working @ stairway d- 4th flr, stairway f- 3rd flr room 340, stairway d- 3rd flr. rem: repair or replace.

    Nov 1, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s) or appurtenances. at cellar storage room designated c2 water penetrating foundation wall.rmdy:comply with nov; repair defect noted.maintain water proof integrity of foundation

    May 21, 2015

    Resolve
  • Class - 2

    Re-issue # 35016360h. door racked to frame. at 3d, door separating at hinge & not closing properly. remedy: replace door.

    May 13, 2014

    Resolve
  • Class - 2

    Water penetration. at boiler pit, foundation has become porous allowing water to enter with 1/2" standing water. remedy: water proof foundation.

    May 13, 2014

    Resolve
  • Class - 2

    Partial obstruction. at 3rd & 4th floor corridors, with combustible standing artwork tables, chairs, book bags & clothes. remedy: remove all items, maintain corridor width clear.

    May 13, 2014

    Resolve
  • Class - 2

    Occupancy contrary @ small schoolyard on 119 street frontage, 5-cars parked in schoolyard via jumping the curb- no curb cut contrary to c/o #75564 which does not indicate off street parking. rem: discontinue il

    Apr 25, 2013

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1968
Floors
4
Residential units
—
Building area
114,695 ft²
Lot area
113,875 ft²
Zoning
R7-2
Community board
111
Council district
8
Block / lot
1816 / 1
Assessed value
$13,703,850
Landmark / historic district
No

Questions about 535 East 119 Street

Who owns 535 East 119 Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 535 East 119 Street have violations?

NYC HPD has no housing violations on record for this property.

Is 535 East 119 Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 535 East 119 Street built?

City records list 1968 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.