DOB building violations

29 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed

ECB violations

The newest 50 of 114 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner.noted fpsc smokedoors not operating properly at:classrooms#146,#404;#417,#319,#335,door to stairs j and i;corridor door by room#249;door to cafeteria.rem:re

    Jul 28, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissued ecb#35725237y work without a permit noted partitions erected with doors at room#320 and #220 creating additional office spaces.alsoat 3rd floor corridor wall with door erected creating separate room.re

    Jul 28, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissued ecb#35725239h failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors perbc 1006.1;27-381.noted exit emergency lights not working at:2nd floor

    Jul 28, 2026 · Penalty $3,125

    Active
  • Class - 2

    Exit door not self-closing. noted: at(1st fl) stair o, b, d, exit 15, 4, 6, 7, auditorium(2nd fl) stair j, i gym, hallway smoke near rm 232(3rd fl) stair o, hallway smoke near-rm 335(basement) stair g, l all do

    Sep 9, 2025 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. note: at(1st fland 2nd fl) hallways installed non-retardent fire decorations to ceilings throughout various areas. remedy: comply with code.

    Sep 9, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at(1st fl) auditorium emergency lights not working throughout va

    Sep 9, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. note: at(1st fl) auditorium ceiling having water damage/staining with spalling plaster/paint. remedy: comply with code.

    Sep 9, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue ecb #35684867k. failure to maintain building in code-compliantmanner. noted: at(3rd fl) erected full height partitions installed door w/closer and office items creating additional office room. remedy: c

    Sep 9, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35094593m work without a permit.noted:at 3rd floor,new room created by erecting a full height partitions and installing a hollow core door.rem:obtain permit or resore to original condition.

    Aug 26, 2024 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building wall(s)or appurtenances.noted:at gym,rooftop,parapet missing at 3 sides.rem:provide parapet.

    Aug 26, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at 1st floor staircase o both door and classroom#239 and gym,one door do not close properly.rem:repair/replace door.

    Aug 26, 2024 · Penalty $625

    Resolve
  • Class - 2

    Observed three cracks in auditorium ceiling dew to a water leak from the roof the fire safety coordinator said they are getting a new roof this summer., repair and/or replace

    May 1, 2024 · Penalty $625

    Active
  • Class - 2

    Reissue #35655375l failure to maintain building in code-compliant manner. noted: observed during inspection of pool, vertical crack along entire back end of pool. remedy: repair and/or replace

    Jul 25, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35584238j.date 8/2/2021.failure to maintain building in code compliant manner.at the time of inspection i observed that at basement level,swimming rool has 25'crack at rear wall.need to repair.remedy:c

    Jun 7, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    28-301.1=reissue :35433790p unsafe storage of combustabvle material snowblowing with gas stored @ cellar presents a fire hazard comply with code

    Aug 2, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue:35342398r failure to maintain building in code compliant manner noted at basement swimming pool has a 25" crack @ rear wall of pool comply with code

    Aug 2, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self-closing properly.at the time of inspection,i observed on 4th floor at exit 4,one exit door not self-closing properly.on 2nd floor near room 214,two corridor exit doors not self-closing.on 2nd

    Jun 7, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35433788x failure to maintain bldg in code compliant manner. note: during inspection observed at cellar level,swimming pool has a horizontal crack approx 30ft long on the deep end of the pool(wall).

    May 29, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. note: during inspection observed at various locations throughout the entire bld

    May 29, 2020 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35433790p misc violation as per bc 3303.4.6 & 27-1018. unsafe storage of combustible material &/or equipment that may present a fire hazard located at cellar level/boiler room area,e.g. power washer,gra

    May 29, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    27-108 miscellaneous violations, as per bc 3303.4.6 and 27-1018. unsafe storage of gasoline powerd eqipment @cellar's boiler room area, eg show blower, lawn mower, john deer machine, grass trimmers. re-issue

    Jun 28, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges, and public corridors per bc 1006.1, 27-381.noted; observed existing emergency light packages with battery back-up

    Jun 28, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code-complaint manner; noted: observed@cellar pool wall @the deepest end has an approx 30 ft long horizontalcrack along entire span of the wall. re-issue #35342398k.rem; repair

    Jun 28, 2019

    Resolve
  • Class - 2

    28-301.1 failure to maintain building in code-complaint manner. no storage of gas fueled portable equipment in building per fc313 at cellar, noted: (3) snowblowers and (1) riding mower.

    Jun 14, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. at basement swimming pool, 25" horizontal crack at rear wall of pool. rem: repair/replace.

    Jun 14, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371. at basement cross over doors near room #b14 door has dead bolt locking device that requires

    Jun 14, 2018

    Resolve
  • Class - 2

    Reissue #35127674m failure to maintain bilding walks or appurtenances.noted:at cellar adjacent to poos pumps,foundation walls spalling rebar exposed and rusted.remedy:comply with notice of violation.

    Jun 14, 2017

    Resolve
  • Class - 2

    Reissue #35221377r.failure to maintian building in code compiant mann er.noted:at cellar level adjacent to pool pumps foundation ground and walls are porus allowing water penetration.remedy:repair and/or replac

    Jun 14, 2017

    Resolve
  • Class - 2

    28-301.1 failure to maintain building in code compliant manner.improper storage of fuel powered equipment as per fc313.3 noted:at boiler room in cellar 3 gas powered snow blowers being stored near exit #14.reme

    Jun 14, 2017

    Resolve
  • Class - 2

    Reissue# 35127672z. failure to maintain bldg in code compliant manner. noted: in cafeteria, entrance door to kitchen not working properly. door does not close properly because its dragging on the flr. rem: repa

    Jun 14, 2017

    Resolve
  • Class - 2

    Reissue#352213787 failure to maintain bldg in code compliant manner. noted: wall of swimming pool has a crack approx 15'feet running vertically. remedy: repair &/or replace.

    Jun 14, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. reissue# 35127725n. wall of swimming pool cracked & leaks water. rem: comply w/ nov.

    Nov 14, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: @ bsmt water penetrating from guard & walls. rem: comply w/ nov.

    Nov 14, 2016

    Resolve
  • Class - 1

    Failure to comply w/commissioner's order contained in nov#35094582r issued on 5/14/15 for work w/o a permit. at 2nd flr room 246 room demo'ed, new electrical wiring and panel and plumbing work begun. dob reco

    Jun 27, 2015

    Resolve
  • Class - 2

    Reissue: 35016339n failure to maintain building walls and or appurtenances. at cellar adjacent to pool pumps foundation has become porous allowing water to enter. rmdy: comply w/nov.

    Jun 3, 2015

    Resolve
  • Class - 2

    Reissue: 35016338l failure to maintain building wall(s) and/or appurtenances. at cellar spalling foundation wall adjacent to pool pumps corroding rebar throughout. rmdy: comply w/nov.

    Jun 3, 2015

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. at ceiling in cafeteria a water damage visible ceiling cut open from end to end. rmdy: comply with nov.

    Jun 3, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. all entry doors to cafeteria not operating properly "closing or opening to kitchen area. rmdy: comply w/nov.

    Jun 3, 2015

    Resolve
  • Class - 2

    Reissue: 35099597j failure to maintain building wall(s) or appurtenances. at pool shaft, exterior cover for shaft termination at exterior ground level insufficient support.rmdy: comply w/nov.

    Jun 3, 2015

    Resolve
  • Class - 2

    Inadequate shaft cover. at pool shaft, exterior cover for shaft terminating at exterior ground level is inadequate with insufficient support. remedy: properly seal shaft if feasible or restore to prior legal co

    May 14, 2014

    Resolve
  • Class - 2

    Water penetration. at old fuel tank room, the exterior foundation has become porous allowing water to enter with 1" standing water. also left of area -in boiler room water entering. remedy: water proof foundat

    May 14, 2014

    Resolve
  • Class - 2

    Work without permit. at room 156, full height partitions installed with electric light fixtures passing through. remedy: obtain permit, comply with bldg code or restore to prior legal condition.

    May 14, 2014

    Resolve
  • Class - 2

    Defective emergency lighting. at gym & auditorium & exit 1, inoperative emergency lights over exit doors. also noted same in natatorium. remedy: repair or replace emergency lighting.

    May 14, 2014

    Resolve
  • Class - 2

    Work without permit. at room marked 320b, non full height partition install in corridor creating an office with a hollow core wood door. remedy: obtain permit & comply with bldg code or restore to prior legal c

    May 14, 2014

    Active
  • Class - 2

    Missing illuminated exit sign. at 3rd floor, no illuminated exit sign for stair "d". illuminated exit sign removed & electric box covered. remedy: replace illuminated exit sign.

    May 14, 2014

    Resolve
  • Class - 2

    Partial obstruction. at 4th floor corridor, numerous book bags throughout corridor creating a trip condition. remedy: remove all items from corridor, maintain corridor width clear.

    May 14, 2014

    Resolve
  • Class - 2

    Combustible artwork in stairs. at stair marked "o" 3rd to 4th floor. remedy: remove all items.

    May 14, 2014

    Resolve
  • Class - 2

    Hanging combustible banners. at 1st & 2nd floor corridors, banners hanging from conduits partially obstruct exit signs. remedy: remove banners.

    May 14, 2014

    Resolve
  • Class - 2

    Racked exit door. at 1st floor stair h, door is racked to frame & jams shut requiring extreme force to open. remedy: repair if feasible or replace door.

    May 14, 2014

    Resolve
  • Class - 2

    Exit doors not self closing. at 1st floor stair l, cafeteria door, smoke doors adjacent to 214,314. broken & missing door closers. remedy: replace door closers.

    May 14, 2014

    Resolve