421 East 106 Street

Manhattan, NY 10029BBL 1-01700-0001Map

Owner of record: NYC Department Of Parks And Recreation

421 East 106 Street is a school building built in 1964 in Manhattan, 10029. The owner of record is NYC Department Of Parks And Recreation. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
36
ECB violations
56
HPD complaints
3

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 36

  • Construction other optional

    Structure rendered non compliant at time of inspection damage observed to have been sustained four metal support beams and cross bracing defective and displaced section damaged approx 10ftx20ft due to car impact

    Feb 28, 2023

    Dob violation - active
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2020

    Jun 20, 2021

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2016 inspection/test

    Sep 15, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 20, 2015

    Dob violation - resolved
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2014 inspection report

    Oct 1, 2015

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2014 inspection report

    Oct 1, 2015

    Dob violation - dismissed
Show 26 more ↓
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 13, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 10, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 1, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 9, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 4, 2007

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 17, 2005

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 22, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    1p32956

    Oct 31, 2001

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 10, 2000

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - active
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed

ECB violations · 56

  • Class - 2

    Reissued ecb#35676342h failure to maintain building in code compliant manner.noted:at roof wall with cracks and missing mortar throughout various areas.rem:repair and/or replace.

    Jul 22, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at 3rd fl stair c,smoke doors rm 308 2nd fl stair c smoke doors rm 236 1st fl cafeteria,stair b all door are in disrepair/racked.rem:repair and/or rep

    Jul 22, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.lack of emergency lighting for exits,exit discharges and public corridors per bc 1006.1;27-542.noted:at 2nd fl library rm 209 not installed/provided without

    Jul 22, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted at 1st fl gym,auditorium and every floor/areas emergency lights/exit s

    Jul 22, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:at 1st fl exits2,9,auditorium installed/used eye/hook door stoppers.rem:provide legal

    Jul 22, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner illumination for exits, exit discharges, and public corridors per bc 1006.1;27-381. noted:at 3rd fl exit sign at stair b, c, 2nd fl em of corridor by 236, e

    Jul 18, 2023 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing. noted: the exterior door at exit 1 is not working properly. remedy: repair / replace door.

    Jul 18, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.noted; at 3rd fl rm 331, 2nd fl stair c, corridor by 236, rm 203, 219, 229, 1st fl teachers lounge at cafeteria#6, rm 33 and cafeteria entrance by 122, the door

    Jul 18, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at roof level adjacent to bulkhead c, the corner wall has cracks and missing mortar. at exposure 1 above handicap ramp, has cracks and a hole. also, abo

    Jul 18, 2023 · Penalty $625

    Active
  • Class - 1

    Phone not working,no door lock monitoring installedin controller as mandated in3.10.12 of appendix k or the 2014 buidling code. remedy: install dlm, file, and perform test with nyc dob, fix phone

    Aug 12, 2020 · Penalty $1,250

    Resolve
Show 40 more ↓
  • Class - 2

    Failure toi maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: the entire 1st fl hallway & 3 lights in the cafeteria,all these lights

    May 28, 2020 · Penalty $625

    Resolve
  • Class - 1

    R/c,c/u 42n11; 67x10,15m07,68m07,64m07,100bb11. 42n11-cease use items replace bypass fuses on controller and install correct fuses inall slot. contact nycdob at [email protected] to restore service

    Feb 13, 2018

    Resolve
  • Class - 1

    Ac211.1:42n11:excel elev&escal corp lic#501001,submitted a notorized affirmation of correction w/intent of dismissing pvt #555714 after and inspection conducted on 2/13/18 shows this statement to be false.defic

    Feb 13, 2018 · Penalty $250

    Resolve
  • Class - 2

    Defective door. at exit 12, double door frame cut & welded with one side jammed -50% obstruction. remedy: repair if feasible or replace door.

    May 21, 2014

    Resolve
  • Class - 2

    Defective emergency lighting. at 1st floor gym, inoperative emergency lighting with battery back up over exit doors. remedy: repair or replace emergency lighting.

    May 21, 2014

    Resolve
  • Class - 2

    Defective door. at 2nd floor stwy 'c', door closer is broken and not closing. remedy: replac edoor closer.

    Feb 22, 2013

    Resolve
  • Class - 2

    Emergency exit signs not illuminated at rooms 129,131,133,135,exit signs are not on separate circuit and not illuminated. remedy:provide continues illumination of emergency exit signs.

    Feb 22, 2013

    Resolve
  • Class - 2

    Reissue #34982071y defective cobble stone paving at 1st ave exit area way,uneven and missing cobble stones creating a trip condition.defective stone are not in exit passage line but area is used by waiting pare

    Feb 22, 2013

    Resolve
  • Class - 2

    Defective cement stucco. at parapet along east 106th street sidewalk right off h/c ramp, cracking and minor separation of approx 10"round area of cement stucco coating. rmdy: repair exterior masonry.

    Feb 22, 2013

    Resolve
  • Class - 2

    Missing hardware at room 135, missing door knobs on adjoining door to room 133 leading to exit door. remedy: replace door knobs.

    Feb 22, 2013

    Resolve
  • Class - 2

    Reissue 34927087r. at 1st ave exit area way uneven & missing cobblestones creating a tripping hazards. rem:repair uneven surface.

    Jun 22, 2012

    Resolve
  • Class - 2

    Reissue 34927086p. handrails at handicap entrance to right of main entry are loose. rem:repair hand rails.

    Jun 22, 2012

    Resolve
  • Class - 2

    27-371(b): reissue 34927084l. plexi vision panels installed at variousrooms throughout 1st,2nd & 3rd flrs. rem:provide code compliant visionpanels.

    Jun 22, 2012

    Resolve
  • Class - 2

    34927083j. auditorium lobby exit door to 107st is racked. rem:repair/replace doors.

    Jun 22, 2012

    Resolve
  • Class - 3

    Unauthorized storage. at electric room,storage of maintenance equipment & supplies. remedy: remove all items maintain service room storage free.

    Aug 18, 2011

    Resolve
  • Class - 2

    Defective pavers. at 1st ave exit a areaway,uneven & missing cobblestones creating a trip condition. remedy: repair areaway paving.

    Aug 18, 2011

    Resolve
  • Class - 2

    Defective guardrails. at handicap entrance to right of main entry,both guardrails/handrails are loose w/1 leaning & offering little support.remedy: repair h/c guard/hand rails.

    Aug 18, 2011

    Resolve
  • Class - 2

    Water penetration. the roof has become porous allowing rain water to enter room 330 & gym. noted wet at time of inspection w/light rain. remedy: water proof roof.

    Aug 18, 2011

    Resolve
  • Class - 2

    Sec. 27-371(b) plexi vision panels. plexi (thermo plastic) vision panels installed at various rooms throughout 1st,2nd,3rd floors. remedy: provide code-compliant vision panels.

    Aug 18, 2011

    Resolve
  • Class - 2

    Racked door. the fire proof self closing door is racked to frame & saddle requiring extreme force to open & close at auditorium lobby exit to 107 street. remedy: repair door to properly open & self close.

    Aug 18, 2011

    Resolve
  • Class - 2

    Reissue: 34791344z 3rd floor stwy 'b' door not closing. 2nd floor corridor smoke doors near room 229 not closing. 1st floor auditorium rear left door closing too fast. remedy: repair/replace doors.

    Aug 12, 2010

    Resolve
  • Class - 2

    Corridor smoke doors on 2nd fl near rm 229 not crossing 1st fl auditorium door closing too fast rem: repair/replace doors

    Jun 4, 2009

    Resolve
  • Non-hazardous

    50a 29c 18a 50a pipe down safety valve discharge to prevent scalding.

    Oct 14, 2005

    Resolve
  • Non-hazardous

    50a 50b 50a pipe down safety valve discharge to a safe point to prevent scalding 50b steam leak on header befor stop valve.

    Oct 14, 2005

    Resolve
  • Non-hazardous

    Plaster missing in corridor on 1st floor next to boys room #122. remedy:replace plaster.

    Feb 16, 2005

    Resolve
  • Non-hazardous

    Plaster ceiling bulging (2'x 2' section) inside of boys bathroom on 2nd floor.remedy:repair plaster ceiling.

    Feb 16, 2005

    Resolve
  • Non-hazardous

    Exit door not self closing.noted:interior exit door at e 107 st does not close due to door jamb is coming off wall.remedy:repair door jamb as required

    Feb 4, 2004

    Resolve
  • Non-hazardous

    Use of illegal hardware.noted:slide bolts/chain and padlocks on interior doors at exits:1, 2/3, 4/5,6, e 107 street and handicap ramps exitsnote:slide bolts,chains and padlocks are removed when school is in

    Feb 4, 2004

    Resolve
  • Non-hazardous

    Failure to maintain building defects doros no not close : at 3rd floor326, 322, smoke doro near 308 1st fl exit door by aduit & e 107 st e 106 st ramp remedy : maintain building repair / replace doors

    Jan 30, 2003

    Resolve
  • Non-hazardous

    Failure to maintain building defect. hole approx 12" x 12" plaster & wire mesh ceilng in room 122 remedy : maintain building repair as needed

    Jan 30, 2003

    Resolve
  • Non-hazardous

    Failure to provide panic hardware no panic hardware : at gym ( occupancy 390 ) 5 doors at carfeteria occupancy 460 ) 6 door also faulty panic bars ( lock stay closed ) at main stair exit 1 door at play ground e

    Jan 30, 2003

    Resolve
  • Non-hazardous

    Failure to maintain building defect broken door checks at 3rd fl smoke door near rxit 2 stwy 4 at 2nd fl exit 1, rooms 222, 226, 236 remedy : maintain building replace door checks

    Jan 30, 2003

    Resolve
  • Hazardous

    Failure to maintain building. defects noted: the exit door leading from the gymnasium and kitchen to east 107 street stuck in closed position and when you do get it open, it fall to pavement off the door jamb.

    Feb 14, 2002

    Resolve
  • Non-hazardous

    Failure to maintain,defects are spalling concrete ceilings(detaching concrete)locations:325,332,334 remedy:do repairs

    Apr 9, 2001

    Resolve
  • Non-hazardous

    Failure to maintain defects are rotted exit doors not self closing.and erroded jambs.locations:exit 6 double door 1st are exits.1st floor stair 1 thru corridor adjacent to auditorium.remedy:do repair

    Apr 9, 2001

    Resolve
  • Hazardous

    Failure to maintain:defects are:exit door total obstruction.location:kindergardens rms, 135 +133 remedy:make safe,do repairs

    Apr 9, 2001

    Resolve
  • Non-hazardous

    Failure to maintain,defects are,buldging bricks and loose mortar jointlocation:roof north bulkhead at door.west bulkhead (exterior)remedy:dorepairs

    Apr 9, 2001

    Resolve
  • Hazardous

    Failure to maintain,defects are,spalling concrete cantileicers at windows over walkway.(shed installed 1/2 of path)location:east walkway adjacent to playyard and all perimeters with concrete overhangs.remedy:ma

    Apr 9, 2001

    Resolve
  • Non-hazardous

    Failure to maintain.defects are.cracked plaster corridor walls,locations,corridors adjacent to 135 + 133, 103 remedy:do repairs

    Apr 9, 2001

    Resolve
  • Non-hazardous

    Failure to maintain.defect are,cracked concrete ceilings .location.304,307.remedy:do repairs

    Apr 9, 2001

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Jan 23, 2022 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Jan 23, 2022 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Sep 24, 2021 · Apt BLDG

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1964
Floors
3
Residential units
—
Building area
93,300 ft²
Lot area
121,100 ft²
Zoning
R7-2
Community board
111
Council district
8
Block / lot
1700 / 1
Assessed value
$8,221,500
Landmark / historic district
No

Questions about 421 East 106 Street

Who owns 421 East 106 Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Parks And Recreation.

Does 421 East 106 Street have violations?

NYC HPD has no housing violations on record for this property.

Is 421 East 106 Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 421 East 106 Street built?

City records list 1964 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.