Violations at 203 East 109 Street
Manhattan, NY 10029 · BBL 1-01659-0105 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
1 DOB violations, newest first.
- High pressure boiler boiler required
Violation issued for failure to file 2013 annual high pressure boiler inspection
Mar 3, 2015
Dob violation - dismissed
ECB violations
15 ECB violations, newest first.
- Class - 1
Removed or defaced a written posted vacate order. at the time of inspection, i observed that the full vacate order sticker at the front of the building was posted on 7/31/2024 was removed from the glass panel a
Aug 14, 2024 · Penalty $12,500
Active - Class - 1
Occupancy contrary to that allowed by the certificate of occupancy or department building records. at the time of inspection, i observed 1 story building occupied as a medical center contrary to co # m36348 nov
Aug 14, 2024 · Penalty $25,000
Active - Class - 1
Failure to obey a vacate order from the commissioner per 28-207.4. at the time of inspection, i observed urgent care medical center illegally occupied with staff and customer while under an active full vacate o
Aug 14, 2024 · Penalty $25,000
Active - Class - 1
Occupancy contrary to building c/o #36348 which identifies garage occupancy. at time of inspection nfp 1 story building is occupied as an urgent care medical facilty with only one entrance / egress door. note b
Jul 30, 2024 · Penalty $12,500
Active - Class - 1
Work without a permit. all plumbing work including (2) new toilet bowls, waste lines, hot and cold water supply for sinks / toilets in bathrooms and exam rooms all completed without obtaining dob permits for wo
Jul 30, 2024 · Penalty $12,500
Active - Class - 1
Work without a permit. all electrical work including new 1st floor distribution panel located in reception area, all light fixtures, switches and receptacles installed without obtaining dob permits throughout "
Jul 30, 2024 · Penalty $12,500
Active - Class - 1
Work without a permit. full height partitions erected across entirety of 1st floor to create exam rooms, lab rooms, bathrooms and reception for "urgent care health" with no permit on file for work. work 100% co
Jul 30, 2024 · Penalty $12,500
Active - Non-hazardous
18b,50a,40,50b.50a-combustion leak at upper hand hole.50b-clean debris from boiler room.
Oct 31, 2007 · Penalty $180
Resolve - Non-hazardous
48c,32a,50a.50a-boiler feed line missing.(boiler not in use must be maintained or disconnected by means of water,fuel,electric,flue pipe,steamlines capped).
Oct 31, 2007
Resolve - Non-hazardous
50/32a/48c/44a. 50- safety valve rating plate not legable. 50a- oil supply from tank missing valve.
Mar 13, 2006 · Penalty $180
Resolve - Non-hazardous
B4a/32a/44a/48a/50/50a/50b/50c/50d/50e. 50- fuel oil storage tank doesn't meet the clearance requirement to the boiler code. (7 ft clearance) 50a- defected oil gauge to burner. 50b- missing oil shut off valve t
Mar 13, 2006 · Penalty $350
Resolve - Non-hazardous
48b,50a,50b. fulton vt boiler,15hp,nb 69526,oil fired,1994 50a-flue pipe supported by loose wire.install approved hangers to ceiling.50b-improper arranged hangers to ceiling.50b-improper arrangement of blowdown
May 7, 2004 · Penalty $2,500
Resolve - Non-hazardous
50a. fulton vt boiler,15 hp,nb 40491,oil fired, 1981 50a-secondary low water,cut off manual reset switch disconnected
May 7, 2004 · Penalty $2,500
Resolve - Hazardous
21a4951 49)insufficient air for boiler boiler seals do not use chimmney not properly shown in plan which is passing through ceeiling of 1st floor and roof bq9-27-147 operation boiler without equipment use permi
May 19, 2000
Resolve - Non-hazardous
16/49 cut out manual reset switch in panel box missing 2 hand holes welded receipt by a certified welder holding slamp to submit.proof of registration for this boiler fulton nb40491 year 81 to submit.
Apr 17, 2000 · Penalty $350
Resolve