Violations at 65 East 99 Street

Manhattan, NY 10029 · BBL 1-01605-0024 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

The newest 50 of 79 DOB violations. The city keeps the complete history.

  • Construction other optional

    Failure to maintain building in code compliant manner. at the time of inspection observed the following conditions. broken window pane at the 13 floor and damaged joint on exposure 3, south elevation park avenue. remedy: repair and/or replace

    Jun 3, 2026

    Dob violation - active
  • Construction other optional

    Partial vacate order due to; loose/cracked/spalling concrete, stucco and mortar joints on roof bulkhead/water tower enclosure. remedy: vacate entire roof. restrict access to vacated areas

    May 20, 2025

    Dob violation - active
  • Construction other optional

    Failure to maintain building in code compliant manner. observed defected balcony slab at exposure 1 and facing exposure 4. damaged mortar joints at exposure 2 and 3. remedy: repair and/or replace

    May 15, 2025

    Dob violation - active
  • Construction other optional

    Failure to maintain bldg in code compliant manner. exposures 2,3 &4 multiple corroded, sagging metal lintels on several upper floors roof:water town brick enclosure has defective masonry work such as spalling & missing mortar joints. remedy: repair and/or replace defective condition on ring beam

    May 13, 2025

    Dob violation - active
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2023)

    Jun 23, 2024

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2022)

    Apr 22, 2023

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2021)

    Aug 21, 2022

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 9a technical report by 02/21/2022

    Feb 22, 2022

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 9a technical report by 02/21/2022

    Feb 22, 2022

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 9a technical report by 02/21/2022

    Feb 22, 2022

    Dob violation - active
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 9a technical report by 02/21/2022

    Feb 22, 2022

    Dob violation - active
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 9a technical report by 02/21/2022

    Feb 22, 2022

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 9a technical report by 02/21/2022

    Feb 22, 2022

    Dob violation - active
  • Nycha elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Dec 17, 2021

    Dob violation - dismissed
  • Nycha elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Dec 17, 2021

    Dob violation - dismissed
  • Nycha elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Dec 17, 2021

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2020)

    Jun 20, 2021

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2019)

    Jun 29, 2020

    Dob violation - dismissed
  • Facade safety program facade required

    Fisp-facade safety program facade required

    Jan 23, 2020

    Dob violation - active
  • Facade safety program facade required

    Fisp-facade safety program facade required

    Jan 23, 2020

    Dob violation - active
  • Facade safety program facade required

    Fisp-facade safety program facade required

    Jan 14, 2020

    Dob violation - active
  • Facade safety program facade required

    Fisp-facade safety program facade required

    Jan 14, 2020

    Dob violation - active
  • Facade safety program facade required

    Nycha unsafe cycle 8 report filed

    Jan 13, 2020

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to nycha elevator - fail to correct defects on 2017 cat 1 insp/tst

    Sep 6, 2019

    Dob violation - dismissed
  • Nycha elev annual inspection/test elevatorrequired

    Vio issued to nycha elevator-failure to file category 1 2017 inspection/test

    Apr 5, 2019

    Dob violation - dismissed
  • Nycha elev annual inspection/test elevatorrequired

    Vio issued to nycha elevator-failure to file category 1 2017 inspection/test

    Apr 5, 2019

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 8a technical report by 02/21/2017

    May 31, 2018

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 8a technical report by 02/21/2017

    May 31, 2018

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 8a technical report by 02/21/2017

    May 31, 2018

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 8a technical report by 02/21/2017

    May 31, 2018

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 8a technical report by 02/21/2017

    May 31, 2018

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 8a technical report by 02/21/2017

    May 31, 2018

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2017)

    Mar 27, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to nycha elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to nycha elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to nycha elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to nycha elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2016)

    Feb 16, 2017

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2015

    Mar 14, 2016

    Dob violation - dismissed
  • Facade facade optional

    Cycle 7 unsafe report filed

    Jul 9, 2014

    Dob violation - dismissed
  • Facade facade optional

    Cycle 7 unsafe report filed

    Jun 27, 2014

    Dob violation - dismissed
  • Facade facade optional

    Cycle 7 unsafe report filed

    Dec 4, 2013

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 7a technical report by 02/21/2012

    Jan 31, 2013

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 7a technical report by 02/21/2012

    Jan 31, 2013

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 7a technical report by 02/21/2012

    Jan 31, 2013

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 7a technical report by 02/21/2012

    Jan 31, 2013

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 7a technical report by 02/21/2012

    Jan 31, 2013

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 7a technical report by 02/21/2012

    Jan 31, 2013

    Dob violation - dismissed
  • Facade facade optional

    Cycle 7 unsafe report filed

    Dec 31, 2012

    Dob violation - dismissed
  • Facade facade optional

    Cycle 7 unsafe report filed

    Dec 31, 2012

    Dob violation - dismissed

ECB violations

37 ECB violations, newest first.

  • Class - 2

    Pedestrian protection does not meet code specification:note:observed the following shed conditions.detach cross brace and loose parapet at area of building entrance.also missing parapet post corner of exposure

    Jun 3, 2026 · Penalty $2,400

    Active
  • Class - 1

    Failure to maintain building wall"s" and appurtenances. note: at the time of inspection i observed at ex #1, north elevation, cracked/brokenglass window at 3rd floor. at ex #2, east elevation, inadequate a/c su

    Jan 23, 2026 · Penalty $5,000

    Resolve
  • Class - 2

    Failure to submit an acceptable required cycle 9a report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control#912025.rem:submit acceptable required t

    Dec 2, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to submit an acceptable required cycle 9a report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control#912026.remedy:submit acceptable require

    Dec 2, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to submit an acceptable required cycle 9a report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control#905960.remedy:submit acceptable require

    Dec 2, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to submit an acceptable required cycle 9a report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control#905961.rem:submit acceptable required t

    Dec 2, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to submit an acceptable required cycle 9a report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control#905962.rem:submit acceptable required t

    Dec 2, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to submit an acceptable required cycle 9a report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control#905963.rem:submit acceptable required t

    Dec 2, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    98bb05: (98) expired cat 5 test, perform and file test

    Jan 9, 2021 · Penalty $625

    Resolve
  • Class - 1

    Failure to maintain building exterior walls/facades and appurtenances.exposure 3,west elevation-7 story:broken a/c bracket. remedy:maintain bldg exterior walls/facades and appurtenances. repair and make facade

    Jan 16, 2020 · Penalty $2,500

    Resolve
  • Class - 1

    Failure to provide adequate safety measures,such as shed,netting,etc.-where required to protect and secure public safety-from a documented unsafe facade-file by qewi on 1/13/2020-as per 1rcny 103-04. note:at th

    Jan 16, 2020 · Penalty $10,000

    Resolve
  • Class - 1

    Failure to maintain building exterior walls/facades and appurtenances.exposure 4,south elevation:air conditioners supported by-can-2nd story,book and unknown item-12th story. remedy:maintain bldg exterior walls

    Jan 16, 2020 · Penalty $2,500

    Resolve
  • Class - 1

    Failure to maintain building exterior walls/facades and appurtenance. exposure 1,east elevation:wood supporting a/c at 3rd story-can supporting a/c 2nd story. remedy:maintain bldg exterior walls/facades and app

    Jan 16, 2020 · Penalty $2,500

    Resolve
  • Class - 2

    Failure to maintain exterior facade. 1-all balconies under-finish(paint) defective. 2-random locations-lintels rusting. 3-random location-brick coving. 4-rusting metal balconies railing-framing. remedy:maintain

    Jun 28, 2019

    Resolve
  • Class - 2

    Failure to maintain. balcony ceiling finish defective lintels rusting.remedy: maintain exterior building facade-provide safety measures,makefacade safe as per 1rcny-103-04

    Jun 4, 2019

    Resolve
  • Class - 2

    Failure to maintian exterior building. 1-rusting lintels. 2-a/c units missing brackets. 3-entrance, underside of awning, spalling.rem: maintain exterior building, provide safey measures.

    Apr 25, 2019

    Resolve
  • Class - 2

    Failure to maintain exterior building facade 1-rusting lintels various locations. remedy: maintain exterior building facade provide safety measures make facade safe as pr 1 rcny 103-04

    Apr 23, 2019

    Resolve
  • Class - 2

    Failure to submit acceptable 8th found report of critical examination documenting condition of exterior walls and appurtenances required by 28-302.4 control #812025. rmdy: submit required technical report.

    May 18, 2018

    Resolve
  • Class - 2

    Failure to submit acceptable 8th found report of critical examination documenting condition of exterior walls and appurtenances required by 28-302.4 control #805961. rmdy: submit required technical report.

    May 18, 2018

    Resolve
  • Class - 2

    Failure to submit acceptable 8th found report of critical examination documenting condition of exterior walls and appurtenances required by 28-302.4 control #805963. rmdy: submit required technical report.

    May 18, 2018

    Resolve
  • Class - 2

    Failure to submit acceptable 8th round report of critical examination documenting condition of exterior walls and appurtenances required by 28-302.4 for control #805962. rem: submit required technical report

    May 18, 2018

    Resolve
  • Class - 2

    Failure to submit acceptable 8th round report of critical examination documenting condition of exterior walls and appurtenances required by 28-302.4 for control #805960.rem:submit required technical report.

    May 18, 2018

    Resolve
  • Class - 2

    Failure to submit acceptable 8th round report of critical examination documenting condition of exterior walls and appurtenances required by 28-302.4 for control #812026.rem:submit required technical report.

    May 18, 2018

    Resolve
  • Class - 2

    98-bb-05:5 year tag (5/27/15) expired.(dob records)

    Sep 17, 2015

    Resolve
  • Class - 2

    21-m-07:base assembly (lineage) cover missing for 6,2, & 1st fls-prov ide.

    Sep 17, 2015

    Resolve
  • Class - 2

    Sec. 3314.16.4 partial swo issued for suspended scaffold pursuant 28-207.2 & posted on premises. inspection of angle scaffold. noted: at time of inspeciton 3 angle scaffolds installed at exp#3 suspended scaffol

    Jun 11, 2015

    Resolve
  • Class - 1

    Failure to have new or altered plumbing system tested.note:new standpipe system piping & valve installed on 1st fl staircase.no permits or test on file.*photo taken* rem:obtain permit & perform test.

    Jul 9, 2013

    Resolve
  • Class - 1

    Work w/o permit.note:obs new standpipe system piping and valve instal led on 1st fl staircase.no permits on file.*photo taken* rem:obtain permit.

    Jul 9, 2013

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.note:obs water seeping thru several floors adjacaent to piping located in stairs.rem:repair and/or replace.

    Jul 8, 2013

    Resolve
  • Class - 1

    Work w/o permit.noted:obs approx 10' of 4" stanpipe piping replaced from the cellar to the 1st fl w/o a permit.also noted 1 new 4"x2" saddle & 1 hose valve installed on the new piping on the cellar "b" stairs.

    Jul 8, 2013

    Resolve
  • Non-hazardous

    Failure to submit a 5th round technical report in compliance w/ code provisions: periodic insp of exterior walls & appurtenances as requiredby ll 11/98 & the dob rules & regulations. the 5th round technical

    Aug 31, 2006

    Resolve
  • Non-hazardous

    Failure to submit a fifth round technical report in compliance with code provisions:periodic inspection of exterior walls & appurtenances asrequired by local law 11 of 1998 & the dob rules & regulations.

    Jun 2, 2006

    Resolve
  • Non-hazardous

    Failure to submit a fifth round technical report in compliance with code provisions: periodic inspection of exterior walls & appurtenancesas required by local law 11 of 1998 & the dept of bldgs rules & regul-

    Nov 25, 2005

    Resolve
  • Non-hazardous

    Failure to submit a fifth round technical report in compliance with code provisions:periodic inspection of exterior walls and appurtenances as required by local law 11 of 1998 and the department of buildings ru

    Jun 30, 2005

    Resolve
  • Non-hazardous

    Failure to submit a 5th round technical report in compliance with code provisions:periodic inspection of exterior walls & appurtenances as required by local law 11 of 1998 & the department of buildings rules &

    Mar 18, 2005

    Resolve
  • Non-hazardous

    Failure to submit a 5th round technical report: periodic insp of exterior walls & apprutenances as required by local law 11/98 & the d.o.b, rules & regulations remedy: file the required report to the d.o.b. st

    Aug 20, 2004

    Resolve
  • Hazardous

    Failure to maintain exterior of building facade west issues- i- improperly install a.c. units. ii- loose bricks under a.c. unit on floors 11th and 12th floor, north elevation. remedy: make area safe, re-install

    Jun 19, 2003

    Resolve