Violations at 501 Amsterdam Avenue
Manhattan, NY 10024 · BBL 1-01215-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
The newest 50 of 62 DOB violations. The city keeps the complete history.
- Construction other optional
Borough commissioner issued stop work order to application #103651013 due to construction superintendent withdrawal. (no access provided 0% of work completed) stop work immediately and make site safe.
Sep 23, 2020
Dob violation - active - Elevator annual inspection / test elevatorrequired
Violation issued to elevator - failure to file category 1 2017 inspection/test
Apr 5, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 16, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 19, 2016
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2014 inspection report
Oct 1, 2015
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2014 inspection report
Oct 1, 2015
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2014 inspection report
Oct 1, 2015
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2014 inspection report
Oct 1, 2015
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 18, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 31, 2014
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 16, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 23, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 26, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 19, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 22, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 24, 2008
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 13, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 13, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 3, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 3, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 22, 2003
Dob violation - resolved - Elevator elevatorrequired
1p27398
Oct 31, 2002
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Elevator elevatorrequired
1p27398
Jan 4, 2001
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 10, 2000
Dob violation - dismissed - Elevator elevatorrequired
1p27398 cease use
Feb 15, 2000
Dob violation - resolved - Elevator elevatorrequired
1s3793
Feb 15, 2000
Dob violation - resolved - Elevator elevatorrequired
1s3793
Feb 5, 1999
Dob violation - resolved - Elevator elevatorrequired
1p27398
Jan 22, 1999
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 20, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 6, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations
The newest 50 of 128 ECB violations. The city keeps the complete history.
- Class - 2
Reissue: 35717116h-failure to maintain building in code-compliant manner. at the time of inspection observed water seeping through the concrete. remedy: comply with code.
Mar 10, 2026 · Penalty $3,125
Active - Class - 2
Exit door not self closing properly.at the time of inspection observed& noted at 4th floor exit-c one emergency exit door is not self closing properly & at 3rd fl at exit b one exit door not self closing proper
Apr 15, 2025 · Penalty $625
Resolve - Class - 2
Reissue#35663219j date of issue:02.21.2023 failure to maintain building in code compliant manner.at the time of inspection observed & noted that at cellar level full tank rm observed water seeping through concr
Apr 15, 2025 · Penalty $3,125
Active - Class - 1
Ac28-323.8 and rcny 103-13(5). failure to secure public safety and/or make the building structure and appurtenances conform to the provisions of the administrative code after unsafe notification filed by qpsi.
Mar 24, 2025
Resolve - Class - 2
Reissue#35650801m failure to maintain building in code compliant manner.noted at time of inspection,i observed at oil tank room water seeping through concrete ceiling spalling exposing rebar and beams.vio#35650
Feb 21, 2023 · Penalty $1,562
Active - Class - 2
Reissue#35486644x.date of issue:4/15/2020.failure to maintain buildingin code compliant manner.observed sidewalk elevator shaft is flooded with underground water.that water causes severe corrosion to elevator m
Mar 15, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35486643y.date of issue:4/15/2020.failure to maintain buildingin code compliant manner.noted at oil tank room water seeping through concrete pad from underground spalling concrete ceiling exposing rebar
Mar 15, 2022 · Penalty $1,562
Active - Class - 2
Reissue#35486646j.date of issue:4/15/2020.failure to maintain buildingin code compliant manner:illumination for exits discharges and public corridors per bc1006.1;27-381 at the time of inspection at basement le
Mar 15, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue #35402261h failure to maintain buidling in code complaint manner illumination for exits discharges and public corridors per bc 1006.1;27-381 noted emergency exit lighting observed inoperative when teste
Apr 15, 2020 · Penalty $1,562
Resolve - Class - 2
Failure to mainain building in code compliant manner noted at auditorium water puddle observed infront of the stage seeping through the concrete pad from under ground causing floor tiles off the floor approx 10
Apr 15, 2020 · Penalty $625
Resolve - Class - 2
Reissue #35402260x failure to maintain building in code compliant manner noted sidewlak elevator shaft is flooded with underground water causing severe corrosion to elevator motor and parts.make necessary repai
Apr 15, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue #35402262j failure to maintain building in code compliant manner noted at oiltank room water seeping through concrete pad from under ground spalling concrete ceiling exposing rebars in the beams. make
Apr 15, 2020 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code compliant manner. noted at passageway 3rd floor rear of rooms #316 & 325 door are missing. remedy: repair and/or replace.
Apr 2, 2019
Resolve - Class - 2
Reissue 35311289x failure to maintain building in code compliant manner. noted at oil tank room in disrepair with water leak from underground also concrete ceiling spalling exposing rebar and beams. remedy: rep
Apr 2, 2019
Active - Class - 2
Reissue 35311290n failure to maintain building in code compliant manner: illumination for exits, exits discharges and public corridors for bc 1006.1; 27-381. observed exit lights for gym, auditory cafeteria, do
Apr 2, 2019
Resolve - Class - 2
Reissue 35311291p. failure to maintain building in code compliant manner. observed: sidewalk elevator shaft is flooded with under ground water, that water causes severe corrosion to elevator motor and parts. re
Apr 2, 2019
Resolve - Class - 2
Reissue #35195316r failure to maintain building in code compliant manner. noted: sidewlk elevator shaft is flooded with under ground water the elevator has unsae tag on it, water has caused severe corrosi
Feb 20, 2018
Resolve - Class - 2
Reissue #35267278p failure to maintain building in code compliant manner. illumination for exits, exit discharges and public corridors as per bc 1006.1; 27-381 noted: gym, auditorium lunch room and other
Feb 20, 2018
Resolve - Class - 2
Reissue #35267277n failure to maintain building in code compliant manner. noted at fuel tank room ceiling has penetrations, concrete cover for beams missing exposing beams, corrosion in multiple locations.
Feb 20, 2018
Active - Class - 1
44r5 work w/o permit. 44r5 and part installed w/o permit being obtained and application bein filed. rmdy: file application and obtain permitfor work and schedule test appointment with nycdob.
Feb 14, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner,lack of emergency lights not working when tested at lunch rm 1 flood light,at gym 2 flood lights at auditorium 8 flood lights. remedy: comply w/code.
May 18, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. reissue nov#35195314n noted: at fuel tank room 1 corroded light fixture & penetration @ ceiling w/exposed steel beam. remedy: comply w/code.
May 18, 2017
Active - Class - 2
Failure to maintain bldg in code compliant manner. reissue nov#35195315p noted: at auditorium crack in wall of stage. remedy: comply w/code.
May 18, 2017
Resolve - Class - 2
Failure to maintain bldg. noted: water damaged ceiling outside 1st flr room#113/auditorium projection room. leak from exterior court yard drain above ceiling. rem: comply w/ nov.
Oct 5, 2016
Resolve - Class - 2
Failure to maintain bldg. noted:reissue 35128975k. gas meter room has no fresh air vent. rem: comply w/ nov.
Oct 5, 2016
Resolve - Class - 2
Failure to maintain bldg. noted: reissue 351284404. cellar elevator pit floods. sump pit doors locked preventing access. rem: comply w/ nov.
Oct 5, 2016
Resolve - Class - 2
Failure to maintain bldg. noted: reissue 35128443j. crack @ center of auditorium stage wall. rem: comply w/ nov.
Oct 5, 2016
Resolve - Class - 2
Failure to maintain bldg. noted: reissue 35128448z. fuel tank room w/ 1 corroded wire light & steel beam & dislodged masonry fire stopping @ ceiling. rem: comply w/ nov.
Oct 5, 2016
Resolve - Class - 2
Fresh air in gas meter room. no fresh air vent in gas meter room. reissued viol #35093294h. rmdy: comply w/nov.
May 19, 2015
Resolve - Class - 2
Failure to maintain building in code-compliant manner. in fuel tank room concrete ceiling spalling exposing rebar & beams. at exterior en try at soutn east corner. reissue: 35093295j. rmdy: comply w/nov
May 19, 2015
Active - Class - 2
Failure to maintain bldg in code-compliant manner. at rear of auditorium apprx 20'-0" vertical crack at center of stage wall. reissued viol #35093296l. rmdy: comply w/nov.
May 19, 2015
Resolve - Class - 2
Misc viols. vision panels (thermoplastic or plex) 4th flr room 403,404407,407a,409,411,412,413,414 others 3rd flr room 308. reissued violation #35093297n. rmdy: comply w/nov.
May 19, 2015
Resolve - Class - 2
Approved place of assembly plans or signs not available for inspectionfor cafeteria cellar gymnasiums (3) separated cafeteria area does not reflect modified egress.egress doors blocked by tablet.reissued viol #
May 19, 2015 · Penalty $5,000
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. cellar freight elevator pit and stairs flooded w/water on daily basis.doors to sump pit sealed. reissued viol#35093293x. rmdy: comply w/nov.
May 19, 2015
Resolve - Class - 2
In 1st floor cafeteria, small cafeteria adjacent to mainroom & seating egress doors blocked by tables. remedy: remove tables from doorways.
Mar 28, 2014
Resolve - Class - 2
Approved place of assembly plans or signs not available for inspection. for -"cafeteria" -"cellar gymnasiums (3)" -separated cafeteria area does not reflect modified egress. egress doors blocked by tables. rem
Mar 28, 2014
Resolve - Class - 2
Exit doors not self closing. -defective doors at stair a,b & c 4th fl fire stairs. -defective door at stair d 3rd fl fire stair. -defective hallway smoke door 4th fl @ rm 420. -defective hallway smoke door 2n
Mar 28, 2014
Resolve - Class - 2
Vision panels (thermoplastic or plexi). 4th floor room 403,404,407,407a,409,411,412,413 & 414 & others, 3rd floor room 308. remedy: provide required glass panel.
Mar 28, 2014
Resolve - Class - 2
Re-issue # 35016532p. failure to maintain bldg in code-compliant manner. -at rear of auditorium approx 20'-o" vertical crack at center of stage wall. -in cafeteria, step crack at partition wall at prep area n.e
Mar 28, 2014
Resolve - Class - 2
Re-issue # 35016533r. failure to maintain bldg in code-compliant manner. -in fuel tank room concrete ceiling spalling exposing rebar & beams. -at exterior entry at south east corner. remedy: repair/replace conc
Mar 28, 2014
Active - Class - 2
Re-issue # 35016534z. fresh air in gas meter room. no fresh air vent in gas meter room. remedy: provide fresh air vent.
Mar 28, 2014
Resolve - Class - 2
Re-issue # 35016537y. failure to maintain bldg in code-compliant manner. cellar freight elevator pit & stairs flooded with water on daily basis. doors to sump pit sealed. remedy: remove water. maintain bldg as
Mar 28, 2014
Resolve - Class - 2
Cellar- freight elevator pit and stairs flooded w/water. remedy: remove all water - maintain bldg as per code.
May 13, 2013
Resolve - Class - 2
Exit signs out and/or faded. 1- auditorium exit signs not legible/faded. remedy: maintain signs as per code.
May 13, 2013
Resolve - Class - 2
Reissue- 34779466p. no fresh air vent in gas meter room. remedy: provide fresh air vent.
May 13, 2013
Resolve - Class - 2
Reissue- 34941377x. concrete ceiling spalling exposing rebar and beams. remedy: repair/replace concrete.
May 13, 2013
Active - Class - 2
Reissue: 34941378h. center of auditorium rear masonry wall 20' vertical crack & 10'-0 crack vertical crack. remedy: repair wall as per code.
May 13, 2013
Resolve - Class - 2
Reissue # 34921757j. at: center of auditorium rear masonry wall 20' vertical crack. remedy: repair wall.
Feb 23, 2012
Resolve - Class - 2
Reissue # 34921758l. concrete ceiling spalling at cellar level in fuel tank room, exposing rebar. remedy: repair spalling concrete.
Feb 23, 2012
Active - Class - 1
No record of daily inspec of suspended scaffold performed by authorized person @ site.stop work order issued.3men working on site when asked for inspec log they said "they do not have one"no inspec log @ time o
Aug 9, 2011 · Penalty $2,400
Resolve