Violations at 149 West 77 Street
Manhattan, NY 10024 · BBL 1-01149-0007 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
13 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - dismissed - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2020)
Jun 20, 2021
Dob violation - dismissed - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 in 2019
Jun 29, 2020
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed
ECB violations
The newest 50 of 71 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner. at the time of inspection, stairwell "d" had water stains and efflorescence as a result of roof overflow test. remedy: repair and/or replace.
Mar 19, 2026 · Penalty $1,250
Active - Class - 2
Re-issued 35717111z. at the time of inspection, the following emergency lights were inoperable:-2-53, 2-6, 2-7, 1-17, b-8, b-5, 1 emergency lights over a exit door from auditorium. remedy: repair/replace lighti
Mar 19, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). at the time of inspection, the following room doors had turn knob handles:-312, 309, 310
Mar 19, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. at the time of inspection, the following room doors were not self-closing properly:-1door on 2nd floor, 1 door from 1st floor cafeteria, staircase "a" on 1
Mar 19, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors. per bc 1006.1; 27-381. at the time of inspection observed and noted. at 2nd floor gym 1 place
Apr 11, 2025 · Penalty $1,250
Active - Class - 2
Exit door not self-closing properly at the time of inspection i observed and noted at basement level auditorium. in main entrance one exit door not open when push at push bar. and 1st floor stairway "c" and sta
Apr 11, 2025 · Penalty $625
Resolve - Class - 1
Observed unsafe lifiting of equipment on supported scaffold at exposure 1 from pulley system. man receiving materail had no harness and lifeline for safe operation of receiving material.creating a hazardous con
Jul 22, 2024
Resolve - Class - 1
Observed at 78 street side of active jobs at ps 78. no flag man observed at time of delivery operations as required per 3307.4.3
Jul 22, 2024 · Penalty $5,000
Active - Class - 1
Observed unsafe storage of construction materials at street level on 78 street side exp 1. blocking fire hydrant adjacent to the jobsite with work materials.
Jul 22, 2024 · Penalty $2,500
Active - Class - 1
Active alt jobsite at ps 78 observed supported scaffold installed not to code missing top, mid rails and toe boards . also missing pins for side bracket/bicycle.
Jul 22, 2024
Resolve - Class - 2
Unlawful display of artwork in corridors greater than 20% per fdny 2008 code;fc 803.3.2.noted:observed throughout the 3 story occupied school,corridors have excessive amount of combustable material being stored
Jun 10, 2024 · Penalty $1,250
Resolve - Class - 2
Work without an after hours variance permit on file contrary to 28-105.12.5 - at time of inspection, approx. 20 workers in total commencing in asbestos abatement under subcontractor asar international and gener
Sep 5, 2023 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc1006.1,27-381.i observed on 2nd floor hallway in room 208 light not working when tested.als
Feb 16, 2023 · Penalty $625
Resolve - Class - 2
Work after hours without a variance permit contrary to 28-105.12.5 at time of inspection noted 2 workers on the 3rd floor along 78th street sweeping masonry debris following masonry pointing operation and confi
Nov 18, 2022 · Penalty $3,125
Resolve - Class - 2
Work contrary to approved construction documents.at time of inspectionnoted access ladder along 78th street to pipe scaffold contrary to site safety plan p-ssp-101.02 and eq-404.00 from street level to 2nd floo
Nov 18, 2022
Resolve - Class - 2
Failure to maintain bldg in code compliant manner:no fire stopping perbc 712.3;27-345 note at cellar level in electrical room no fire stopping around pipes penatrating through wall.remedy:provide & maintain fir
Mar 5, 2021 · Penalty $3,125
Resolve - Class - 2
Reissue 35473997m failure to maintain bldg in code compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381 note emergency lights in corridors on all floors & corridor not
Mar 5, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue 35473498y failure to maintain bldg in code compliant manner note at cellar level in gas meter room gas pipes not painted yellow remedy:comply w/violation & paint pipes yellow.
Mar 5, 2021 · Penalty $1,562
Resolve - Class - 2
28-301.1=failure to provide ventilation to gas meter room for p 115.6(1968 code) fgc appendix e (e4) (2014 code) noted at gas meter room no fresh air ventilaion provided comply with notice violation
Apr 29, 2020 · Penalty $1,250
Resolve - Class - 2
Failur eto maintain building in code compliant manner noted at gas meter room gas pipes are not painted yellow comply with notice of violation
Apr 29, 2020 · Penalty $625
Resolve - Class - 2
Reissue #35402024y failure to maintain building in code compliant manner:illumination for exits exit discharges and public corridoers per bc 1006.1;27-381 noted emergency exit lighting observed inoperative when
Apr 29, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue#35311279m failure to maintain building in code-compliant manner:lack of emergency lighting for exits,exit discharges and public corridors per bc 1006.1;27-542. noted approximately 10 emergency lights ob
Mar 27, 2019
Resolve - Class - 2
Re-issue # 35235798m failure to maintain building in a code compliant manner. lack of emergency lighting for exits, exit discharges and public corridors as per bc 1006.1;27-542.noted:approx.10 emergency lights
Feb 14, 2018
Resolve - Class - 2
Reissued viol #35200872l for: failure to maintain building wall(s) orappurtenances.noted: at north and south sidewalks are buckled and causing trip and fall hazard.rmdy:maintain building wall.
Mar 30, 2017
Resolve - Class - 2
Exit door not self closing. noted: at 2nd floor stairway b, 1st flr, sairway c, 1st flr exits, doors are not self closing. rmdy: repair/replace door.
Mar 30, 2017
Resolve - Class - 2
Failure to maintain building in code compliant manner: lack of emergency lighting for exits, exit discharges, and public corridors per bc 1006.1; 27-542. noted: defective emergency lighting observed at 2nd an
Mar 30, 2017
Resolve - Class - 2
Failure to maintain bldg.noted:north & south sidewalks are buckled &causing,trip & fall hazard.prior nov#35128135h cites same condition.rem:comply with notice of violation.
Sep 21, 2016
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner. note:trip and fall hazards outside in front of school. main entrance. uplifted trees(2)raised concrete 2"-3".rmdy:comply with nov.
Apr 7, 2015
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner. note:for right auditorium door defective wedges into the door buck.at the far right side exiting into the main lobby area.rmdy:comply w/nov.
Apr 7, 2015
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j) noteall 1st flr exit doors has slide bolt/padlocks. rmdy:comply w/nov.
Apr 7, 2015
Resolve - Class - 3
Work w/o a permit. @ end of boiler rm erected partition & doors creating 3 rms installed lighting/electric. remedy:obtain permit or restore premises to prior legal condition.
Apr 2, 2014
Resolve - Class - 2
Failure to maintain bldg wall(s) or appurtenances. @ exit 7 (@ stair d) exterior canopy top has water pooling @ drain area. remedy: repair and or replace drain.
Apr 2, 2014
Resolve - Class - 2
Re-issue ecb #35019042x failure to maintain bldg walls & appurtenaces @ exit 7 (stair d) exterior canopy underside concrete flaking off exposing rebar. remedy:repair and/or replace concrete.
Apr 2, 2014
Resolve - Class - 2
Fuel tank room - floor to wall joint, left side, missing concrete sealrmdy: maintain building as per code.
May 28, 2013
Resolve - Class - 2
Exit 7 at 1st flr exterior. door overhang and/or roof-underside concrete flaking off exposing rebar. rmdy: repair and/or replace concrete.
May 28, 2013
Resolve - Class - 2
Reissue: 34941365z - 2nd fl: gym metal suspended ceiling panels are loose broken. rmdy: repair and/or replace metal pan ceiling.
May 28, 2013
Resolve - Class - 2
Reissue: 34941367m - 3rd fl: stwy "a" door racked; 2nd fl: stwy "c" door racked. rmdy: repair and/or replace.
May 28, 2013
Resolve - Class - 2
3rd & 2nd floor hall corridors are partial obstruction with tv carts,computer carts,tables,boxes. remedy: remove obstructions.
Feb 16, 2012
Resolve - Class - 2
3rd floor stwy "c" door not closing, stwy "a" door racked, 2nd floor corridor smoke doors near room 211 not closing, 1st floor stwy "d" door racked. remedy: repair/replace doors.
Feb 16, 2012
Resolve - Class - 2
At: roof level south east side parapet wall brick is spalling. remedy: repair parapet wall.
Feb 16, 2012
Resolve - Class - 2
Reissue # 34921735z. at: 2nd floor gym metal suspended ceiling panels are loose,missing or broken. remedy: repair/replace metal ceiling panels.
Feb 16, 2012
Resolve - Class - 2
Plexi installed in stairway at stairway b & c 1st to 3rd fl installed plexi on guard rails to exterior windows rem: remove all plexi thermo plastic
Jul 27, 2011
Resolve - Class - 2
A/c unit w/ wood blocking at 3fl east window a/c unit installed w/o proper supports wood blocking protruding rem: provide proper a/c unit supports
Jul 27, 2011
Resolve - Class - 2
Reissue #34871723z defective metal suspended ceiling at 2fl gym metal suspended ceiling panels are loose missing or broken rem: replace secure all metal panels
Jul 27, 2011
Resolve - Class - 2
Interior metal ceiling panels in the gymnasium is loose/missing/brokenlocated on the 2nd floor level. remedy: repair and/or replace metal ceiling panels.
Aug 12, 2010
Resolve - Class - 2
Windows in room 104 on the 1st floor level does not open & close properly.noted:chain is defective in window.rem:repair and/or replace windows.
Aug 12, 2010
Resolve - Class - 2
Exterior sidewalk on west 78 street is uneven causing a tripping hazard.noted:sidewalk has lip of 3"inches on west 78 street.rem:repair and/or replace sidewalk.
Aug 12, 2010
Resolve - Class - 2
Gas meter room being used as storage room.ie:storage shelves w/cleaning products,boxes etc.remedy:remove all items.
May 8, 2009
Resolve - Class - 2
Reissue:34771746z. no fresh air vent in gas meter room. remedy:providefresh air vent.
May 8, 2009
Resolve - Class - 2
No fresh air vent in gas room (meter). remedy: provide fresh air vent.
Oct 8, 2008
Resolve