Violations at 149 West 77 Street

Manhattan, NY 10024 · BBL 1-01149-0007 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

13 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2020)

    Jun 20, 2021

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2019

    Jun 29, 2020

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed

ECB violations

The newest 50 of 71 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner. at the time of inspection, stairwell "d" had water stains and efflorescence as a result of roof overflow test. remedy: repair and/or replace.

    Mar 19, 2026 · Penalty $1,250

    Active
  • Class - 2

    Re-issued 35717111z. at the time of inspection, the following emergency lights were inoperable:-2-53, 2-6, 2-7, 1-17, b-8, b-5, 1 emergency lights over a exit door from auditorium. remedy: repair/replace lighti

    Mar 19, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). at the time of inspection, the following room doors had turn knob handles:-312, 309, 310

    Mar 19, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. at the time of inspection, the following room doors were not self-closing properly:-1door on 2nd floor, 1 door from 1st floor cafeteria, staircase "a" on 1

    Mar 19, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors. per bc 1006.1; 27-381. at the time of inspection observed and noted. at 2nd floor gym 1 place

    Apr 11, 2025 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing properly at the time of inspection i observed and noted at basement level auditorium. in main entrance one exit door not open when push at push bar. and 1st floor stairway "c" and sta

    Apr 11, 2025 · Penalty $625

    Resolve
  • Class - 1

    Observed unsafe lifiting of equipment on supported scaffold at exposure 1 from pulley system. man receiving materail had no harness and lifeline for safe operation of receiving material.creating a hazardous con

    Jul 22, 2024

    Resolve
  • Class - 1

    Observed at 78 street side of active jobs at ps 78. no flag man observed at time of delivery operations as required per 3307.4.3

    Jul 22, 2024 · Penalty $5,000

    Active
  • Class - 1

    Observed unsafe storage of construction materials at street level on 78 street side exp 1. blocking fire hydrant adjacent to the jobsite with work materials.

    Jul 22, 2024 · Penalty $2,500

    Active
  • Class - 1

    Active alt jobsite at ps 78 observed supported scaffold installed not to code missing top, mid rails and toe boards . also missing pins for side bracket/bicycle.

    Jul 22, 2024

    Resolve
  • Class - 2

    Unlawful display of artwork in corridors greater than 20% per fdny 2008 code;fc 803.3.2.noted:observed throughout the 3 story occupied school,corridors have excessive amount of combustable material being stored

    Jun 10, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Work without an after hours variance permit on file contrary to 28-105.12.5 - at time of inspection, approx. 20 workers in total commencing in asbestos abatement under subcontractor asar international and gener

    Sep 5, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc1006.1,27-381.i observed on 2nd floor hallway in room 208 light not working when tested.als

    Feb 16, 2023 · Penalty $625

    Resolve
  • Class - 2

    Work after hours without a variance permit contrary to 28-105.12.5 at time of inspection noted 2 workers on the 3rd floor along 78th street sweeping masonry debris following masonry pointing operation and confi

    Nov 18, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Work contrary to approved construction documents.at time of inspectionnoted access ladder along 78th street to pipe scaffold contrary to site safety plan p-ssp-101.02 and eq-404.00 from street level to 2nd floo

    Nov 18, 2022

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner:no fire stopping perbc 712.3;27-345 note at cellar level in electrical room no fire stopping around pipes penatrating through wall.remedy:provide & maintain fir

    Mar 5, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue 35473997m failure to maintain bldg in code compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381 note emergency lights in corridors on all floors & corridor not

    Mar 5, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue 35473498y failure to maintain bldg in code compliant manner note at cellar level in gas meter room gas pipes not painted yellow remedy:comply w/violation & paint pipes yellow.

    Mar 5, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    28-301.1=failure to provide ventilation to gas meter room for p 115.6(1968 code) fgc appendix e (e4) (2014 code) noted at gas meter room no fresh air ventilaion provided comply with notice violation

    Apr 29, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Failur eto maintain building in code compliant manner noted at gas meter room gas pipes are not painted yellow comply with notice of violation

    Apr 29, 2020 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35402024y failure to maintain building in code compliant manner:illumination for exits exit discharges and public corridoers per bc 1006.1;27-381 noted emergency exit lighting observed inoperative when

    Apr 29, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35311279m failure to maintain building in code-compliant manner:lack of emergency lighting for exits,exit discharges and public corridors per bc 1006.1;27-542. noted approximately 10 emergency lights ob

    Mar 27, 2019

    Resolve
  • Class - 2

    Re-issue # 35235798m failure to maintain building in a code compliant manner. lack of emergency lighting for exits, exit discharges and public corridors as per bc 1006.1;27-542.noted:approx.10 emergency lights

    Feb 14, 2018

    Resolve
  • Class - 2

    Reissued viol #35200872l for: failure to maintain building wall(s) orappurtenances.noted: at north and south sidewalks are buckled and causing trip and fall hazard.rmdy:maintain building wall.

    Mar 30, 2017

    Resolve
  • Class - 2

    Exit door not self closing. noted: at 2nd floor stairway b, 1st flr, sairway c, 1st flr exits, doors are not self closing. rmdy: repair/replace door.

    Mar 30, 2017

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner: lack of emergency lighting for exits, exit discharges, and public corridors per bc 1006.1; 27-542. noted: defective emergency lighting observed at 2nd an

    Mar 30, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg.noted:north & south sidewalks are buckled &causing,trip & fall hazard.prior nov#35128135h cites same condition.rem:comply with notice of violation.

    Sep 21, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. note:trip and fall hazards outside in front of school. main entrance. uplifted trees(2)raised concrete 2"-3".rmdy:comply with nov.

    Apr 7, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. note:for right auditorium door defective wedges into the door buck.at the far right side exiting into the main lobby area.rmdy:comply w/nov.

    Apr 7, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j) noteall 1st flr exit doors has slide bolt/padlocks. rmdy:comply w/nov.

    Apr 7, 2015

    Resolve
  • Class - 3

    Work w/o a permit. @ end of boiler rm erected partition & doors creating 3 rms installed lighting/electric. remedy:obtain permit or restore premises to prior legal condition.

    Apr 2, 2014

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s) or appurtenances. @ exit 7 (@ stair d) exterior canopy top has water pooling @ drain area. remedy: repair and or replace drain.

    Apr 2, 2014

    Resolve
  • Class - 2

    Re-issue ecb #35019042x failure to maintain bldg walls & appurtenaces @ exit 7 (stair d) exterior canopy underside concrete flaking off exposing rebar. remedy:repair and/or replace concrete.

    Apr 2, 2014

    Resolve
  • Class - 2

    Fuel tank room - floor to wall joint, left side, missing concrete sealrmdy: maintain building as per code.

    May 28, 2013

    Resolve
  • Class - 2

    Exit 7 at 1st flr exterior. door overhang and/or roof-underside concrete flaking off exposing rebar. rmdy: repair and/or replace concrete.

    May 28, 2013

    Resolve
  • Class - 2

    Reissue: 34941365z - 2nd fl: gym metal suspended ceiling panels are loose broken. rmdy: repair and/or replace metal pan ceiling.

    May 28, 2013

    Resolve
  • Class - 2

    Reissue: 34941367m - 3rd fl: stwy "a" door racked; 2nd fl: stwy "c" door racked. rmdy: repair and/or replace.

    May 28, 2013

    Resolve
  • Class - 2

    3rd & 2nd floor hall corridors are partial obstruction with tv carts,computer carts,tables,boxes. remedy: remove obstructions.

    Feb 16, 2012

    Resolve
  • Class - 2

    3rd floor stwy "c" door not closing, stwy "a" door racked, 2nd floor corridor smoke doors near room 211 not closing, 1st floor stwy "d" door racked. remedy: repair/replace doors.

    Feb 16, 2012

    Resolve
  • Class - 2

    At: roof level south east side parapet wall brick is spalling. remedy: repair parapet wall.

    Feb 16, 2012

    Resolve
  • Class - 2

    Reissue # 34921735z. at: 2nd floor gym metal suspended ceiling panels are loose,missing or broken. remedy: repair/replace metal ceiling panels.

    Feb 16, 2012

    Resolve
  • Class - 2

    Plexi installed in stairway at stairway b & c 1st to 3rd fl installed plexi on guard rails to exterior windows rem: remove all plexi thermo plastic

    Jul 27, 2011

    Resolve
  • Class - 2

    A/c unit w/ wood blocking at 3fl east window a/c unit installed w/o proper supports wood blocking protruding rem: provide proper a/c unit supports

    Jul 27, 2011

    Resolve
  • Class - 2

    Reissue #34871723z defective metal suspended ceiling at 2fl gym metal suspended ceiling panels are loose missing or broken rem: replace secure all metal panels

    Jul 27, 2011

    Resolve
  • Class - 2

    Interior metal ceiling panels in the gymnasium is loose/missing/brokenlocated on the 2nd floor level. remedy: repair and/or replace metal ceiling panels.

    Aug 12, 2010

    Resolve
  • Class - 2

    Windows in room 104 on the 1st floor level does not open & close properly.noted:chain is defective in window.rem:repair and/or replace windows.

    Aug 12, 2010

    Resolve
  • Class - 2

    Exterior sidewalk on west 78 street is uneven causing a tripping hazard.noted:sidewalk has lip of 3"inches on west 78 street.rem:repair and/or replace sidewalk.

    Aug 12, 2010

    Resolve
  • Class - 2

    Gas meter room being used as storage room.ie:storage shelves w/cleaning products,boxes etc.remedy:remove all items.

    May 8, 2009

    Resolve
  • Class - 2

    Reissue:34771746z. no fresh air vent in gas meter room. remedy:providefresh air vent.

    May 8, 2009

    Resolve
  • Class - 2

    No fresh air vent in gas room (meter). remedy: provide fresh air vent.

    Oct 8, 2008

    Resolve