Violations at 850 10 Avenue
Manhattan, NY 10019 · BBL 1-01065-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
The newest 50 of 192 DOB violations. The city keeps the complete history.
- Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
May 11, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 11, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 11, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 11, 2021
Dob violation - resolved - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Mar 3, 2021
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Mar 3, 2021
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Mar 3, 2021
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Mar 3, 2021
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 14, 2020
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Sep 2, 2020
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 8, 2020
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator - failure to file category 1 2017 inspection/test
Apr 5, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Residential elevator periodic inspection/test elevatorrequired
Failure to perform category 5 inspection
Jun 1, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 12, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 12, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 12, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 12, 2016
Dob violation - resolved - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Dec 30, 2015
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Dec 30, 2015
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2014 inspection report
Oct 1, 2015
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2014 inspection report
Oct 1, 2015
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 10, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 10, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 10, 2015
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2014 inspection/test
Jun 10, 2015
Dob violation - dismissed - Construction other optional
Failure to comply with commissioner's order.bldg is warehouse type structure with w/bowstring truss-roof.department served a curable commissioner's order on 1/12/15 to provide an engineer report on your building.no engineer's report has been received. comply per the commissioner's order
Apr 17, 2015
Dob violation - dismissed
ECB violations
The newest 50 of 147 ECB violations. The city keeps the complete history.
- Class - 2
28-301.1 failure to provide ventilation to gas meter room per p115.6(1968 code)egc appendix e,(e4)(2014 code)gas meter room has no ventilation.rem:comply with code.
Apr 16, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. no firestoppingper bc 712.3; 27-345. at the time of inspection observed and noted at cellar level electrical room one hole in wall no firestopping at that
Aug 7, 2025 · Penalty $1,250
Resolve - Class - 2
Exit door not self-closing properly. at the time of inspection observed and noted at 6th fl stairway "d" 1 exit door, 3rd floor gym 2 exit doors and 3rd floor stairway "e" 1 exit door not self-closing properly
Aug 7, 2025 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits; exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection observed and noted at 6th floor auditorium on
Aug 7, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:observed in the gymnasium none of the emergency lights were not operat
Sep 23, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridor per bc 1006.1;27-381.noted:at 3rd floor exit sign by 3079a and 3rd floor gymnasium,the exit signs
Apr 21, 2023 · Penalty $625
Resolve - Class - 2
Exit door not self-closing noted:the exterior door at exit 6 is not working properly.rem:repair/replace door.
Apr 21, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:at 6th floor auditorium entrance by 6089,room adjacent to 6032,4th floor corridor by lunchroom entrance,2nd floor corridor by 2024,room 2021,2060,1st
Apr 21, 2023 · Penalty $625
Resolve - Class - 2
Exit door not selfclosing properly@6fl auditorium in main entrance (leftside) 1exit door&@1fl from 10ave main entrance 1(outside) exit door not selfclosing properly atoi.repair/replace door.
Apr 23, 2021 · Penalty $625
Resolve - Class - 2
Reissue35415348n doi4.8.19 failure to maintain bldg wall(s) or appurtenances.noted shaftway rm@center of rm from 6-4fls spalling stucco exposed rebard on underside of roof soffit overhang.maintain exterior bldg
Apr 23, 2021 · Penalty $3,125
Resolve - Class - 2
Reissue35415347l doi4/8/19 failure to maintain bldg in codecompliant manner noted@1fl shop area spalling&missing plaster&masonry fire retardent coating on steel ibeams/girders.repair &/or replace.
Apr 23, 2021 · Penalty $1,562
Resolve - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. remedy; file application, install dlm a
Dec 9, 2020 · Penalty $1,250
Resolve - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. remedy; file application, install dlm a
Dec 9, 2020 · Penalty $1,250
Resolve - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. remedy; file application, install dlm a
Dec 9, 2020 · Penalty $3,125
Resolve - Class - 1
Out of service. upon inspection, the device is found to be out-of-service, remedy: restore to service immediately and, notify nycdob the device has been returned to service. e-mail [email protected] so an i
Dec 9, 2020 · Penalty $1,250
Resolve - Class - 2
Provide up to date elevator maintenance log book., perform and file cat 1 year test., provide up to date (a.b.c) rated motor room fire extinguisher.
Dec 9, 2020 · Penalty $625
Resolve - Class - 1
Restore to service for proper inspection by dob class 1.
Jul 17, 2020 · Penalty $3,125
Resolve - Class - 2
Pedestrian production does not meet code specific. at the time of my inspection,i observed a sidewalk shed installed at exp#1. during my inspection i observed storage of a shanty,gang box & other materials ins
Jun 5, 2020 · Penalty $1,250
Resolve - Class - 1
Failure to file evidence of compliance with workers comp law and/or disability benefit law.note:at time of my inspection of a 4 storey school building under repair and installation of window sill cover,re-point
May 8, 2020 · Penalty $5,000
Resolve - Class - 2
Failure to maintain building in code compliant manner.note at main entrance exit 1 interior door missing.rem:repair and or replace.
May 1, 2020 · Penalty $625
Resolve - Class - 2
Reissue#35415346j failure to maintain building in code compliant manner no fire stopping per bc 712.3;27-345.note in pamp rooms on 6th and 1st floor no fire stopping where pipe penetrate thur walls.rem:provide
May 1, 2020 · Penalty $3,125
Resolve - Class - 2
Reissue#35415344x failure to maintain building in code compliant manner note at 2nd floor stairway b exit door is racked hitting door jam.rem:repair and or replace.
May 1, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue#35415343y failure to maintain building in code compliant manner note at 6th floor auditorium ceiling having cracks throughout with spalling plaster and peeling paint fallen to floor in multiple areas.ro
May 1, 2020 · Penalty $1,562
Resolve - Class - 1
97/x/17 restore to service for proper inspection by dob.
Dec 26, 2019 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building wall(s) or appurtenances. noted:shaftway room located at center of room from 6th to 4th floors spalling stucco exposed rebar on underside of roof soffit overhang. remedy:maintain ex
Apr 8, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner. noted: at 1st fl shop area spalling and missing plaster and masonary fire retardent coating on steel i beams/girders. remedy: repair and/or replace
Apr 8, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner. no fire stopping per bc712.3; 27-346 noted at 5th floor ac room and 6th floor pomp room (behing auditorium) with having openings/holes in various locations
Apr 8, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner illumination for exits, exit discharges and public coridors and bc 1006.1; 27-381 noted: at 6th floor auditorium, 3rd floor auditorium, gym emergency lights
Apr 8, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner noted: at 2nd floor stair b, main entry (56 st side) double door to hallway doors are in disrepair/racked. remedy: repair and/or replace.
Apr 8, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner noted: 6th floor auditorium/ at roof with having vertical/horizontal cracks throughout in multiple locations. remedy: repair and/or replace.
Apr 8, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner noted: at roof stair e,d, bulkheads with water penetration/damage throughout to walls and ceilings. remedy: repair and/or replace.
Apr 8, 2019
Resolve - Class - 2
Exit door not self closing. note at 6th floor stair d not close properly stair d outside of gym is not close properly, and auditorium door #2 door checks is broken. rmdy: repair/replace door or hardware.
Feb 15, 2018
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner: no firestopping perbc 712.3, 27-345. at room 5039, 5th flr a/c room no fire stopping in several difference area on ceiling and walls. rmdy: provide/maintain
Feb 15, 2018
Resolve - Class - 2
Reissued #35015676j (4/2/2013) noted: shaftway room located at center of room, from 6th floor to 4th floor spalling stucco/exposed rebar on underside of roof soffitt/overhand. rmdy: maintain exterior
Feb 15, 2018
Resolve - Class - 2
Reissued 35119169l (1/22/15) at shop area 1st floor, spalling and missing plaster, masonry fire retardant coat on ceiling steel i beam girders. rmdy: replace/repair masonry coating.
Feb 15, 2018
Resolve - Class - 2
Reissued 35119373z, (1/22/15) noted: no firestopping at 6th floor pumpbehind auditorium. rmdy: provide and maintain fire stopping seals allpenetration.
Feb 15, 2018
Resolve - Class - 2
97x10,59bb7,99bb7. 97x10- restore to service for proper inspection by dob; 59bb7-machine brake tag expired provide; 99bb7-one year tag expired provide.
Jan 26, 2018 · Penalty $500
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. no fire stopping per bc712.3;27-345. noted: missing fire stopping at cellar electric meter room,penetrations terracotta wall of ceiling w/conducts & open
Jun 6, 2016 · Penalty $530
Resolve - Class - 2
Failure to maintain bldg in a code compliant manner. spalling missing plaster at shop area 1st fl & missing plaster & masonry fire retardentcoating on ceiling steel i-beam girders;pipes penetration & exposed
Jun 6, 2016 · Penalty $530
Resolve - Class - 1
Reissue #35119168j failure to maintain bldg code compliant: no 2nd means of egress per 27-366. noted: 6th floor auditorium has two sets of double doors within 5' of each otehr, no 2nd means of egress with
Sep 8, 2015
Resolve - Class - 3
Reissue #35094290p.cracked masonry walls.@ bulkheads"d",horizontal & vertical cracks in masonry walls.rem:repair all masonry cracks.
Jan 22, 2015
Resolve - Class - 2
Bc903.6.3,reissue #35094291r.unpainted sprinkler/standpipe per local law 58/2009;bc 903.6.3 retroactive.the combination sprinkler & standpipe cross connections & risers are not painted red per local law 58/2009
Jan 22, 2015
Resolve - Class - 2
Reissue #35094292z.prohibited door(swing)@ 2nd fl adjacent to room 2019,corridor exit door swings against the flow of exit travel.rem:provide code compliant door swing.
Jan 22, 2015
Resolve - Class - 2
Reissue #35094293k.missing fire stopping.@ bsmt electric meter room,penetrations terracotta wall & ceiling w. conduts & open demoed panel box.rem:provide/maintain fire stopping.
Jan 22, 2015
Resolve - Class - 2
Reissue #35094294m.missing fire stopping.@ 6th fl pump room behind auditorium,penetrations & holes in riser chase walls & ceiling to concealed spaces.rem:provide/maintain fire stopping-seal all penetrations.
Jan 22, 2015
Resolve - Class - 2
Failure to maintain bldg wall(s) or appurtenances. noted: cracked, spalling masonry facade with pieces of concrete missing at exterior rear shaftway. defects from 4th to 6th floor including exposed re-bars of
Jan 22, 2015 · Penalty $500
Resolve - Class - 2
Reissue #35094285k.spalling missing plaster.@ shop area 1st fl,spalling & missing plaster & masonry fire retardant coating on ceiling steel i-beam girders.rem:replace/repair masonry coating.
Jan 22, 2015
Resolve - Class - 1
Reissue #35094286m.no 2nd means of egress per bc 1018.1;27-366.@ 6th fl auditorium,2 connected sets of double doors exit to 6th fl corridor.no 2nd means of egress for 190 seating.rem:discontinue use for pa occu
Jan 22, 2015
Resolve - Class - 2
Failure to maintain bldg wall(s) or appurtencances.noted:cracked,spalling masonry facade w/ pieces of concrete missing @ exterior rear shaftway.defects from 4th to 6th fl including exposed re-bars of shaft roof
Apr 29, 2014 · Penalty $500
Resolve - Class - 2
Missing fire stopping. at 6th floor pump room behind auditorium, penetrations & holes in riser chase walls & ceiling to concealed spaces. remedy: provide/maintain fire stopping - seal all penetrations.
Apr 29, 2014
Resolve