Violations at 330 West 18 Street

Manhattan, NY 10011 · BBL 1-00741-0010 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

The newest 50 of 73 DOB violations. The city keeps the complete history.

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 11, 2021

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 11, 2021

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 19, 2020

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 19, 2020

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 29, 2019

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 29, 2019

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 16, 2018

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 28, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 12, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 12, 2015

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 20, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 20, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 9, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 9, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 1, 2013

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 14, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 14, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 7, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 7, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 23, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 23, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 7, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 7, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 26, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 15, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 12, 2005

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 4, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 4, 2004

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Elevator elevatorrequired

    1p32024

    Jun 13, 2000

    Dob violation - resolved
  • Elevator elevatorrequired

    1s3797

    Jun 13, 2000

    Dob violation - resolved
  • Elevator elevatorrequired

    1p32024

    Jan 28, 1999

    Dob violation - resolved

ECB violations

The newest 50 of 98 ECB violations. The city keeps the complete history.

  • Class - 2

    At time of inspection, observed jersey barriers not maintained in accordance with manufacturer specifications. barriers were not filled with water or sand as required, contrary to bc 3301.6.1. maintain jersey

    Jun 7, 2026 · Penalty $6,250

    Active
  • Class - 2

    Reissue:35719854z failure to maintain building in code-compliant manner.smoke doors are missing at 3rd floor near rm 326.rem:comply with code.

    Apr 21, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35719855k failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.gym and cafe exits,exit signs do not illuminate.rem:compl

    Apr 21, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at 1st fl gym auditorium and cafeteria emergency lights note not

    Jun 30, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue ecb #35677347l. failure to maintain building in code-compliantmanner. noted: at 3rd fl. near rm 326 smoke door missing/none removed entirely of doors, hardware, checks. remedy: repair and/or replace.

    Jun 30, 2025 · Penalty $1,250

    Active
  • Class - 1

    Class 1 item: no door lock monitoring installed on this controller as mandated by 3.10.12 of appendix k3 of the 2014 nyc building code. this is a feature which ensures passenger safety. file application, instal

    Dec 16, 2024 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code compliant manner. upon inspection, the device is found to be out of service. remedy: restore to service`and call the dob elevator division at (212) 393-2144 or email at eir@

    Dec 16, 2024 · Penalty $625

    Active
  • Class - 2

    Reissue#35674728l failure to maintain building in code-compliant manner:missing door outside of room 326 3rd floor stair a corridor outside of room 323 stair d smoke doors by exit 3,8,auditorium stage on right,

    Sep 10, 2024 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code compliant manner: illumination for exits, exit discharges, and public corridors per bc 1006.1; 27-381. noted: at 4th fl stair well d, 3rd fl stairwell b and d, girls locker

    May 23, 2023 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing. noted: the exterior doors at bulkhead d, exit 5, 8, and 10 are not working properly. remedy: replace/repair door

    May 23, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35655041l noted:the gas meter room at cellar level has holes in various areas throughout. remedy: provide/maintain fire stopping.

    May 23, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35655042n noted: at 3rd fl stair a, corridor by 326, missing doors at corridor by 323, 1st floor stair d, 1st fl smoke by exit 3 a nd 8, auditorium stage on the right and gymnasium entrance at the righ

    May 23, 2023 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35558013j date:04.22.21 failure to maintain building in code-compliant manner at the time of inspection i observed that and noted(near rm-323) at 3rd fl in corridor area. 2 corridor exit door is missing

    Apr 26, 2022 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35558014l date:04.22.21 failure to maintain building in code- compliant manner. no fire stopping per bc 712.3;27-345. at the time ofinspection i observed at basement level gas meter room no fire stoppin

    Apr 26, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#35558015n date:04.22.21 failure to maintain building in code compliant manner. illumination for exits,exit discharges and public corridors per bc 1006.1;27-381. at 1st fl auditorium(right side) 2 emerge

    Apr 26, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maitnain building in code-compliant manner illumination forexit,exit discharges and public corridors per bc1006.7;27-381 at firstfloor audutorium near stage right side 1 place 2 emergency light are n

    Apr 22, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35495270p/date of issue:4/28/20.failure to maintain building in code-compliant manner.no fire stopping per bc712.3;27-345.note:at basement level in gasmeter room,no fire stopping in various areas with h

    Apr 22, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#35495272z/date of issue:4/27/20/failure to maintain building in code-compliant manner.note:at 3rd floor west corridor no corridor door installed.remedy:repair and/or replace door.

    Apr 22, 2021 · Penalty $1,562

    Active
  • Class - 2

    Failure to maitnain building in code compliant manner.use of prohibited door and/or hardware per bc1008;27-371(j).note:the following doors have illegal kick stops instaled;4th floor,420,407,3rd floor 314,317,33

    Apr 28, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code complaint manner.note:at 3rd floor west corridor no corridor doors installed.remedy:repair and/or replace.

    Apr 28, 2020 · Penalty $625

    Active
  • Class - 2

    Emergency signs at elevator call stations missing defective or non-complaint with section requirements.note:at all floor no emergency signs at elevators.remedy:install and/or repair signs.

    Apr 28, 2020 · Penalty $625

    Resolve
  • Class - 2

    Reissue 35415523l.failure to maintain building in code compliant manner.no fire stopping per bc712.3;27-345.note at basement level in gas meter room no fire stopping in various areas with holes in walls where p

    Apr 28, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue 35415522j.failure to maintain building in code compliant manner.illumination for exits discharges and public corridors per bc1006.1;27-381.note:at 1st floor auditorium and cafeteria emergency lights not

    Apr 28, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner no fire stoppingper bc 712.3;27-345. noted:at basement gas meter rm fire stopping missing/none throughout in various locations w/ holes/openings in walls an

    Apr 15, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination forexits,exit discharges and public corridors per bc 1006.1;27-381. noted:at(1st fl) auditorium and cafeteria emergency lights non operational

    Apr 15, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted:at(2nd fl) hallway door near rm 207(1st fl) stair c,d,exit 5 doors are in disrepair racked also noted:hallway door at 4th fl near rm 420 in disrepair

    Apr 15, 2019

    Resolve
  • Class - 2

    Exit door not self closing properly. at 1st flr exit "1" with broken/ missing door checks and/or racked to frame. rmdy:replace door closer - refit door.

    Jan 28, 2015

    Resolve
  • Class - 2

    Reissue #35094067m defective corridor ceiling. at 1st flr main corridor to gym several ceiling holes to concealed space above. rmdy: repair ceiling seal all openings.

    Jan 28, 2015

    Resolve
  • Class - 2

    Reissue #35094070n defective emergency lighting. at 1st floor gym-bothsides,apprx 50% of emergency lighting with battery backup is inoperable. rmdy: repair or replace emergency lighint.

    Jan 28, 2015

    Resolve
  • Class - 2

    Reissue #35094071p partial corridor obstruction. at basement adjacent to stair"b",stacks of books,boxes,paper and open files all combustiblermdy: remove all items -maintain coridor width clear.

    Jan 28, 2015

    Resolve
  • Class - 2

    Reissue #35094073z missing emergencfy sign at elevator call station at 3rd floor elevator remedy: provide emergency sign.

    Jan 28, 2015

    Resolve
  • Class - 2

    Reissue #35094152r prohibited hardware. at all bulkhead mesh gates, chains and padlocks installed. rmdy: provide key latch and indicate key location.

    Jan 28, 2015

    Resolve
  • Class - 2

    Prohibited hardware. at all bulkhead mesh gates, chains & padlocks installed. remedy: remove chains & padlocks - provide key latch & indicate key location.

    Apr 10, 2014

    Resolve
  • Class - 2

    Missing fire stopping. at stair "b" to basement, no fire stopping in cmu block wall with conduit penetration in fire wall. remedy: provide/maintain fire stopping - seal opening.

    Apr 10, 2014

    Resolve
  • Class - 2

    Excessive corridor combustibles. at 2nd floor throughout, numerous decorations partially obstruct illuminated exit signs, strings,streamers,hanging paper,balloons,lighting covered with color paper. remedy: remo

    Apr 10, 2014

    Resolve
  • Class - 2

    Broken emergency light, hanging by wires. at the gym main corridor exit. remedy: repair or replace light.

    Apr 10, 2014

    Resolve
  • Class - 2

    Missing emergency sign at elevator call station. at 3rd floor elevator. remedy: provide emergency sign.

    Apr 10, 2014

    Resolve
  • Class - 2

    Missing fire stoppping. at storage room adjacent to 444, no fire stopping with wire penetrations to concealed space in corridor overhead & adjacent cmu block wall. remedy: provide/maintain fire stopping.

    Apr 10, 2014

    Resolve
  • Class - 2

    Partial corridor obstruction. at basement adjacent to stair "b", stacks of books,boxes,paper & open files - all combustible. remedy: remove all items - maintain corridor width clear.

    Apr 10, 2014

    Resolve
  • Class - 2

    Defective emergency lighting. at 1st floor gym - both sides, approx 50% of emergency lighting with battery back up is inoperable. remedy: repair or replace emergency lighting.

    Apr 10, 2014

    Resolve
  • Class - 2

    Defective emergency lighting. at 1st floor auditorium, approx 50% of emergency lighting with battery back up is inoperable. remedy: repair or replace emergency lighting.

    Apr 10, 2014

    Resolve
  • Class - 2

    Exit doors not self closing properly. at 1d,3b,3c & smoke doors adjacent to rooms 420,433 with broken/missing door checks &/or racked to frame. remedy: replace door closers - refit doors.

    Apr 10, 2014

    Resolve
  • Class - 2

    Re-issue # 35013122z. defective corridor ceiling. at 1st floor main corridor to gym, several ceiling holes to concealed space above. remedy: repair ceiling - seal all openings.

    Apr 10, 2014

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner note: 2 holes/openings in ceiling through plaster/lathe. location: opposite main entry to gym in public 1st flr corridor. rmdy: maintain & repair defect.

    Mar 26, 2013

    Resolve
  • Class - 2

    Reissue #34953893k failure to maintain bldg in code compliant manner.note: defective operation/not closing/opening properly of corridor doors. locations: stair d bulkhead stair a 4th flr, stiar b 34d flr, 3rd

    Mar 26, 2013

    Resolve
  • Class - 2

    Defective doors stairs a 4 fl 3fl stair c and corridor door near room 307 2fl stair a-c-d 1st floor stair c and corridor door near room 108 doors fitting frame dragging rem: repair replace doors

    Apr 11, 2012

    Resolve
  • Class - 2

    Re34923263z corridor in bsmt near stair b doe records boxes cabinets obstructing corridor rem: remove obstruction

    Apr 11, 2012

    Resolve
  • Class - 2

    Partial corridor obstruction @ cellar corridor adjacent to stairway b partial obstruction w/school supplies & school material,books,chelves and computers approx 70%obstruction.rem:remove all achool items,mainta

    Jul 19, 2011 · Penalty $2,500

    Resolve
  • Class - 3

    Reissue#34847652k.@ stairway d bulkhead,approx 5'step cracking in cmu block wall near window.rem:reppair cmu block wall

    Jul 19, 2011

    Resolve
  • Class - 2

    Reissue 34793520h failure to maintain observed on 4fl stairwell door d & star door by rm 416 out of alignment properly close at 2fl stair a door cut of alignment missing pull handle in gym stair k door cut of a

    Apr 13, 2010

    Resolve