roofy

161 Avenue Of The Americas

Manhattan, NY 10013BBL 1-00505-0036Map

Owner of record: Oss 2016 LLC

161 Avenue Of The Americas is an office building built in 1926 in Manhattan, 10013. The owner of record is Oss 2016 LLC. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
124
ECB violations
52
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 124

  • Construction other optional

    Failure to maintain building in a code compliant manner as per section 28.301.1 of the nyc admin code. noted at the time of inspection minor masonry cracks at exposure 1, broken glass at exposure 2, at roof top elevation hairline cracks on bulkhead as well as some spalling bricks remedy: repair and or replace

    Jan 20, 2026

    Dob violation - active
  • Construction other optional

    Failure to maintain building walls or appurtances in a code compliant manner . noted ; at exposure # 1& 4 at the parapet level the cornice is deteriorated & pulling away in various locations erect a sidewalk shed for public safety. submit engineers report for conditons cited t [email protected] within 48 ours 718-286-3460

    Feb 9, 2025

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 8, 2025

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 8, 2025

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
Show 40 more ↓
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Failure to post energy grade/score none

    Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3

    Apr 29, 2021

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2019)

    Jun 29, 2020

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2018)

    Jun 28, 2020

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2020

    Dob violation - resolved
  • Sprinkler none

    Failed to file final sprinkler report by july 1, 2019

    Nov 12, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 7, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 6, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 6, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 6, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 6, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 6, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 6, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 2, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 2, 2019

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator - failure to file category 1 2017 inspection/test

    Apr 5, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 19, 2018

    Dob violation - resolved
  • High pressure boiler boiler required

    Hblvio-high pressure boiler boiler required

    Apr 19, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 19, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 19, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 19, 2018

    Dob violation - resolved
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2017

    Mar 27, 2018

    Dob violation - dismissed
  • Construction other optional

    The borough commissioner has issued a stop work order for application #122876174 due to applicants withdrawal, stop all work immediately, ma ke site safe, provide all required information forthwith

    Mar 22, 2018

    Dob violation - dismissed

ECB violations · 52

  • Class - 2

    Observed an supported scaffold @ exp 4. the netting for the pipe scaffold was not properly maintained and secured. at time of inspection dob issued a severe weather advisory and scaffold netting was observed lo

    Sep 25, 2026 · Penalty $2,500

    Active
  • Class - 2

    Failure to file acceptable amended cycle 10b report indicating correction of unsafe conditions described in initial facades report required by 28-302.5 for control #1000947. remedy: file acceptable report.

    Apr 20, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to file acceptable amended cycle 10a report indicating correction of unsafe conditions described in initial facades report required by 28-302.5 for control #1000947. remedy: file acceptable report.

    Apr 20, 2026 · Penalty $1,250

    Active
  • Class - 1

    No certificate of correction on file for class 1 work without a permit violation 39129012h issued on 10/3024 for creating a stair and door opening to vacant lot being used as seating for dining., comply with co

    Apr 15, 2025 · Penalty $2,500

    Resolve
  • Class - 1

    Observed created access door, stair to adjacent vacant lot and operating restaurant service with guests seating arrangement. no permit in dob record., obtain permit

    Oct 30, 2024 · Penalty $2,500

    Resolve
  • Class - 1

    Place of assembly contrary to approved construction documents. place of assembly for eating and drinking establishment "torch and crown" does not reflect current conditions with adjacent lot #24 arranged with s

    Oct 28, 2024 · Penalty $2,500

    Resolve
  • Class - 2

    I observed three platform lifts located on 6 ave sidewalk of building. installed without a permit on file., obtain permit; obtain permit

    Jul 31, 2023 · Penalty $800

    Resolve
  • Class - 2

    Work w/o permit. premises under alt-2 job#123693002,at the time of inspection found application filed to construct new men's and women's bathroom on 6th fl w/ approx 90% of the construction work completed w/o p

    Jan 17, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to file acceptable amended cycle 8a report indicating correct ion of unsafe conditions described in initial facades report required by 28-302.5 for control #800947 .remedy: file acceptable report .

    Aug 1, 2018 · Penalty $1,250

    Resolve
  • Class - 1

    05a10,99bb5-54a10)cease use item. door zone restrictor has been tampered with disabled and rendered inoperative. this is a safety device to ensure elevator passengers safety repair restrictor and contact nycdob

    Oct 2, 2017 · Penalty $1,000

    Resolve
Show 40 more ↓
  • Class - 1

    Failure to safeguard all persons & property affected by construction operations. note: at the time of my inspection responding to complaint #1431979 where ssm reported a piece of pipe fell onto the street from

    Aug 31, 2016 · Penalty $10,000

    Resolve
  • Class - 1

    Sec. 3301.8.1 use & tampering prohibited. note: at the time of my inspection responding to complaint #1431979 where ssm reported a piece of pipe fell onto the street from plumber who were working on the 11th fl

    Aug 31, 2016 · Penalty $1,600

    Resolve
  • Class - 1

    Sec. 3310.7 contractor shall inform personnel. note: at the time of myinspection,responding to complaint #1431979 where ssm reported a pieceof pipe fell onto the street from plumbers who where working on the 11

    Aug 31, 2016

    Resolve
  • Class - 1

    Failure to maintain safety equipment measures or temporary construction-no toe boards.at time of inspection noticed not toe boards availableat differant locations at 11,12,13 floors,which is fall hazards for wo

    Oct 20, 2015 · Penalty $1,000

    Resolve
  • Class - 1

    3308.3 vertical safety netting not per code, (damaged) at time of inspection noticed vertical safety netting at 11,12,13 damaged in serverallocations,gaps and holes in many areas.rem:repair or replace the damag

    Oct 20, 2015 · Penalty $1,600

    Resolve
  • Class - 1

    Fail to perform hydrostatic pressure test-standpipe. note: at the timeof my inspection of a 13 sty alteration bldg at 13 floor level,upon request for hydrostatic test/op98 for stabdpipe(cut & extended)none was

    Aug 13, 2015 · Penalty $2,400

    Resolve
  • Class - 1

    Sec. 3310.6 designated site safety manager. note: at the time of my inspection of a 13 sty alteration up to 13 floor. upon review of site safety logs i observed that ssm#2272,#1719,#2131 & #2208 was signing log

    Aug 13, 2015 · Penalty $400

    Resolve
  • Class - 1

    B154,51.#51-chimney not extend though new extensions on 12th fl do notoperate boiler until hazardous conditions are immediately corrected & dob is notified to reinspect & (to) lift the cease-use order call 212

    Feb 26, 2015 · Penalty $1,000

    Resolve
  • Class - 1

    B154,51,50.#51-chimney not extend through new extension on 12th fl #50-gas meter installed in boiler rm #50a draft(indueer)installed on(h/wheater)do not operate boiler until all hazardous conditions are immedia

    Feb 26, 2015 · Penalty $1,000

    Resolve
  • Class - 1

    Work does not conform to approved construction documents and/or approved amendments.at time of inspection of alteration #121326742 with approved site safety plan has demo only. floors erected from roof to 14 fl

    Feb 25, 2015 · Penalty $1,000

    Resolve
  • Class - 1

    Failure to safeguard all persons and property affected by constructionoperations. at time of inspection with alt 1 #12132674z w/structural steel being erected at exp4 and being tied into building has not prote

    Feb 25, 2015 · Penalty $2,400

    Resolve
  • Class - 2

    Failure to provide approved/accepted plans at jobsite at time of inspection.at time of inspection of alteration #121326742 for vertical and horizontal enlargement,approved structural plan are incomplete.2pp app

    Feb 25, 2015 · Penalty $500

    Resolve
  • Class - 2

    Failure to safeguard all pesons and property affected by construction operations.noted at time of inspection of alteration #121326742 has missing handles on self closing doors and plumbing then penetration with

    Feb 25, 2015 · Penalty $1,200

    Resolve
  • Class - 2

    Design required by provision of chapter 33 at time of inspection the following was observed.re-inforcement plating with stainless steel bolts.hilti into concrete column stairwell b; 1-interior column at exp3 a

    Feb 25, 2015 · Penalty $400

    Resolve
  • Class - 2

    Foundation at time of inspection of proposed 15story bldg under alt #121326742 has installed supported pipe scaffold w/no foundation or screw jacks observed at ground level and at 6 tory of steel deck under con

    Feb 25, 2015

    Resolve
  • Class - 1

    Work does not conform to approved construction documents and/or approved amendments.at time of inspection for 10story bldg under alt 1 #121326742 has erected steel with approved incomplete structural plan shows

    Feb 25, 2015

    Resolve
  • Class - 1

    Erected,dismantled repaired maintained,modified or removed supported scaffold w/out a scaffold cert of completion noted:@time of insp supported scaffold erector (miguel angel cruz) was in possession of a fraudu

    Feb 5, 2015 · Penalty $2,400

    Resolve
  • Class - 1

    Sec. 3307.7 fences: gates "out swinging" note: at time of insp i observed active alteration site. steel work in progress at 11-12 floor,concrete work in progress. the gates at expo 1-3 i observed were swinging

    Dec 2, 2014 · Penalty $1,600

    Resolve
  • Class - 1

    Sec. 3303.1.1 machinery: all exposed electrically charged moving or otherwise dangerous parts of ,achines & const/demo equipt shall be located,grounded,shielded or barricaded also prevent contact w/the public.

    Dec 2, 2014

    Resolve
  • Class - 1

    Failure to safeguard: debris falling. note: at time of my inspection,iobserved an active steel alteration jobsite, 2 floors of steel erectedon top 10 existing stories. at exp#4, scaffold set up.men working on

    Dec 1, 2014 · Penalty $2,400

    Resolve
  • Class - 1

    Bc3301.1.2 failure to comply w/nyc fire code general no fire site safety manager fire watch.note: at time of inspection observed active alteration jobsite steel erected 2 floors above existing 10 story bldg.men

    Dec 1, 2014 · Penalty $1,600

    Resolve
  • Class - 1

    Sec. 3314.8 pswo (supported scaffold) issued pursuant to 28-207.2 posted the open sides & ends of every scaffold platform shall be provided w/guardrail system & toeboard. noted at time of inspection supported

    Sep 19, 2014 · Penalty $1,600

    Resolve
  • Class - 2

    Work does not conform to approved const documents &/or approved amendments.@ the time of my insp observed-ver-horizontal extension work in progress for a existing 13 story bldg.missing required sws as per appro

    Jun 16, 2014

    Resolve
  • Class - 2

    70x10. 70x10-remove ducktape from pit door switch.

    Mar 5, 2011

    Resolve
  • Class - 2

    97x10 01l10. 97x10-enitre device restore to service. 01l10-alarm bell not working on emergency stop switch.

    Mar 5, 2011

    Resolve
  • Class - 2

    99bb05 01l10. 99bb05-expired,year test tag. 01l10-emergency stop switch alarm no bell.

    Mar 5, 2011 · Penalty $250

    Resolve
  • Class - 2

    67-l-10/39-i-10/23-l-10/34-e-10/67-l-10-repair communications/39-i-10-repair damamged car top light/23-l-10-repair hall stations on 2nd flr & pleoel loos/34-e-10-noise clutch hitting in hoistway (facia)repair

    Feb 26, 2011

    Resolve
  • Class - 2

    67-l-10/99-m-07/67-l-10-communication not working/99-m-07-1 year test tag missing

    Feb 26, 2011

    Resolve
  • Class - 2

    01-l-10/98-m-07/01-l-10-emergency stops no bell (alarm)98-m-07-no 5 year test tags

    Feb 26, 2011

    Resolve
  • Class - 2

    98-m-07/98-m-07-no 5yr test tag provide

    Feb 26, 2011

    Resolve
  • Class - 2

    67-l-10/67-l-10-communication not working

    Feb 26, 2011

    Resolve
  • Class - 2

    01l10 98m07 01-emergency stop sw alarm bell not working 98-current 5year tag

    Feb 6, 2011 · Penalty $250

    Resolve
  • Non-hazardous

    64m7/64a10/74b14/.64m-pit light missing.64a-pit light switch shuts offcar lights-correct.74b-cwt runby insufficient-shorten ropes.

    Apr 30, 2007

    Resolve
  • Hazardous

    Supervision or use of rigging equipment w/o a special rigger license. license rigger designated an unqualified forman. contractor working onscaffold w/ no riggers license, & forman had no id.

    Nov 28, 2006 · Penalty $3,750

    Resolve
  • Non-hazardous

    Licensed rigger failed to ensure scaffold works must minimum requirements. men working on suspended scaffold w/o dob certificate of fitness.

    Nov 28, 2006 · Penalty $2,500

    Resolve
  • Non-hazardous

    73#07 install new door sill and hoist way door panel in lobby as per ebw application 590-94

    Feb 4, 2002

    Resolve
  • Hazardous

    Failure to obtain an equipment use permit. noted: 20 ton a/c unit installed at 1st fl rear d,b,a aveda institute soho. location: 1st fl rearremedy: obtain a equipment use permit for a/c unit immediately.

    Dec 24, 1997 · Penalty $2,500

    Resolve
  • Non-hazardous

    Failure to provide emergency power exit light on 7th & 6th floors at freight elevator bank foyers failure to provide emergency power to exit directional exit signs on 7th and 6thflrs freight elevtr foyer

    May 17, 1993 · Penalty $2,000

    Resolve
  • Non-hazardous

    Failure to provide directional signs on tenant floors throught bldg. failure to provide emergency power to directional signs. failure to provide adequate emergency power light on tenant floors throught bldg. re

    Dec 16, 1992 · Penalty $1,625

    Resolve
  • Unknown

    Failure to provide elevator signs(freight) throughout floors. failure to provide floor numbering signs(3") throughout. failure to provide stair identification (3" letters) throughout/and elevator identification

    Feb 25, 1992

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Office building (O6)
Year built
1926
Floors
13
Residential units
—
Building area
615,107 ft²
Lot area
47,690 ft²
Zoning
M1-6
Community board
102
Council district
3
Block / lot
505 / 36
Assessed value
$172,261,350
Landmark / historic district
No

Questions about 161 Avenue Of The Americas

Who owns 161 Avenue Of The Americas?

The owner of record in NYC Department of City Planning PLUTO data is Oss 2016 LLC.

Does 161 Avenue Of The Americas have violations?

NYC HPD has no housing violations on record for this property.

Is 161 Avenue Of The Americas rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 161 Avenue Of The Americas built?

City records list 1926 as the year it was built.