Violations at 179 1 Avenue

Manhattan, NY 10003 · BBL 1-00453-0034 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

8 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed

ECB violations

The newest 50 of 55 ECB violations. The city keeps the complete history.

  • Class - 2

    Reissued ecb#35724607h failure to maintain building in code-compliant manner.noted several fpsc smoke doors including all 4 bulkhead doors not self closing throughout the school.rem:repair and/or replace.

    Aug 7, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35688914m. exit door not self-closing. noted: several exit doors and smoke doors that should self-close, were not closing at t. o.i. remedy: repair/replace.

    Aug 27, 2025 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue #35688917h. failure to maintain building in code-compliant manner. noted: there are several doors throughout the school not closingproperly. all stairways and bulkheads included. remedy: repair/replace

    Aug 27, 2025 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.observed above exit 6 exterior below windows exposure 2 2 fl windows cracks and spalling concrete,main entrance saddle bulging.rem:repair and/or replace.

    Sep 18, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. observed at stair a, b, c, d door are not closing properly at roof bulkheads. remedy:repair and/or replace.

    Sep 18, 2024 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). observed at 1 floor kitchen stair c door hardware not working. remedy; provide legal har

    Sep 18, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridor per bc1006.1; 27-381. observed at 1 floor stair a, box #1, 2, 4, 6, 7, 9, 10 and auditorium eme

    Sep 18, 2024 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing. observed at 2 floor smoke stair b, exit 1,4. exit 2 and 6 not closing properly. remedy: repair/replace door.

    Sep 18, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. at 1 floor kitchen entrances by 136, stair g, f and gym doors are not closing properly. remedy: repair and/or replace.

    Sep 18, 2024 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing properly at the time of inspection. at the time of inspection i observed that at 2nd fl stairway "b" 1 exit door inside,1 exit door outside,at 1st fl cafeteria near stairway "f" 2 exi

    May 23, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc1006.1;27-381.at the time of inspection,i observed tat at 1st fl level cafeteria there are

    May 23, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35496076x exit door not self closing. noted: at time of my inspection,i observed at the front entrance exit door is not self closingproperty,vio#35496076x issued 5/29/2020 for violating condition,need

    Apr 27, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#3542239j exit door not self closing. noted: at time of inspection i observed at the front entrance exit door is not self closing property need to make repair. remedy: comply w/code repair &/or replace.

    May 29, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Pedestrian protection does not meet code standards. at time of inspection the sidewalk shed along 1st ave was missing weather and vandal resistant fixtures,in addition 1 bulb was not illuminated. remedy:comply

    Sep 26, 2019 · Penalty $2,400

    Resolve
  • Class - 2

    Exit door not self closing. 1st floor in main entrance (in side) one exit door is not self closing properly. at first floor outside two doors at stair "e" two exit doors are not self closing properly, at

    Apr 29, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illuminaiton forexits, exit discharges and public corridors per bc 1006.1; 27-381. at first fl stair "d" 2 place each place 2 lights in main ent. basement

    Apr 29, 2019

    Resolve
  • Class - 2

    Reissue 35325084j date of issue: 03.15.18 failure to maintain buildingin code-compliant manner approximately 75' of 220v electrical wire running from outside of cellar computer or om and attached to facade of

    Apr 29, 2019

    Resolve
  • Class - 2

    Work w/out a permit. @ old boys locker room behind gymnasium erected metal frame/drywall partitions w/ metal door creating approx 200 sq.font computer room w/ electrical power for lighting fixtures & computer o

    Mar 15, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc1008.1.8; 27-371(j). at cafeteria exit(6) and backstage (2)exits no panic bar and locking device that require

    Mar 15, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. approximately 75ftof 220v electrical wire running from outside of cellar computer ro om and attached to facade of building street level - the wire is low e

    Mar 15, 2018

    Resolve
  • Class - 2

    Failure to maintain building walls or appurtenances. at rear of building next to exit(8) masonry cellar stairs broken, damaged and cracked. rem: maintain building walls and appurtenances.

    Mar 15, 2018

    Resolve
  • Class - 2

    28-301.1 reissue #35253578j. unlawful placement of furnishing decorations or other objects that obstruct access to egress or visibility thereof per fdny fc1027.4. partial obstruction at 1st & 2nd floors from de

    Mar 15, 2018

    Resolve
  • Class - 2

    Reissue# 35253580z. exit doors not self closing. exit doors not self closing following locations 2 fl near rm# 215 1st floor exit (3). rem: repair/replace doors.

    Mar 15, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner; illumination for exits, exit discharges & public corridors per bc1006.1; 27-381. existing emergency lights are not operational when tested. @ auditorium 2 ligh

    Apr 26, 2017

    Resolve
  • Class - 2

    Exit ddor not self closing,swing-out doors on 2nd fl next to rm 215,exit 5 exterior door right side on 1st fl,exit 5 interior door on right side, 1st fl, exit 3 interior door ,1st fl back stage door apposite of

    Apr 26, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: illegal use of storage (rugs,carpets) in electrical storage rm in bsmt/cellar. remedy: remove carpets/rugs.

    Apr 26, 2017

    Resolve
  • Class - 2

    B206,2,28-301.1. unlawful placement of furnishing deco or other objects @ exits that obstruct access to egres from or vosibility there as per fdny 2008 code;fc 1027.4. desk,chairs,art displays in the hallway rm

    Apr 26, 2017

    Resolve
  • Class - 2

    Reissue 35093966l failure to maintain building in code-compliant man ner. lack of emergency lighting fo rexits, exit discharged public corridors per bc 1006.1 27-542. defective emergency lighting at 1st floor

    Oct 7, 2015

    Resolve
  • Class - 2

    Reissue 35093964h failure to maintain building in code-compliant man ner. interior. exit doors not self closing. at 2nd flrs adajacent to room 230,238, the smoke doors have broken closers.rmdy:comply w/code.

    Oct 7, 2015

    Resolve
  • Class - 2

    Unauthorized storage. at gas & electric meter service rooms, storage of various supplies & equipment. remedy: remove all items/maintain meter service rooms storage free.

    Apr 8, 2014

    Resolve
  • Class - 2

    Defective emergency lighting. at 1st floor gym, emergency lighting is not operating at opposite exit doors. remedy: repair or replace lighting with battery back up.

    Apr 8, 2014

    Resolve
  • Class - 2

    Missing fire door. at main entry (exit 1) to stair "a". remedy: replace fire door.

    Apr 8, 2014

    Resolve
  • Class - 2

    Re-issue # 34980685j. exit doors not self closing. at 2nd floor, adjacent to room 230,238, the smoke doors have broken closers. remedy: replace door closers.

    Apr 8, 2014

    Resolve
  • Class - 2

    Missing exterior handrails. at west center exit/entry to school yard, no handrails with 4 risers. remedy: provide handrailings.

    Apr 7, 2014

    Resolve
  • Class - 2

    Defective doors at 2nd flr stair d and corridor doors near room 230 & 238. remedy: repair/replace doors.

    Jan 24, 2013

    Resolve
  • Class - 2

    Reissue 34933716l. defective fire dampers inside boiler room. remedy: repair dampers.

    Jan 24, 2013

    Resolve
  • Class - 2

    27-765. failure to provide ventilation to occupied spaces offices/classroom b47,236 no mechanical ventilation provided. remedy: provide ventilation or discontinue illegal use.

    Mar 14, 2012

    Resolve
  • Class - 2

    Defective fire dampers inside boiler room. remedy: repair/replace dampers.

    Mar 14, 2012

    Resolve
  • Class - 3

    Defective doors 2nd fl corridor doors (all) also auditorium side exit door (right). remedy: repair/replace

    Jun 4, 2010

    Resolve
  • Class - 2

    Reissue 34563189n. obstruction in corridor/passageway noted in cafeteria large warmers obstructing exit passageway,also security desk obstructing exit doors.main entrance 1fl also at basement front of room b3

    Nov 19, 2008

    Resolve
  • Hazardous

    Exit doors are obstructed by security desk located at the main entrance on the 1st floor. remedy: remove security desk.

    Mar 6, 2007

    Resolve
  • Non-hazardous

    Reissue vio #34315403m. noted: major structural crack in south facing wall at main entrance lobby and at basement level (boys bathroom) remedy: make all repairs.

    Mar 9, 2006

    Resolve
  • Non-hazardous

    Reissue 34427906k.classroom door checks through out school not on doors.(fpsc doors are not s.c).remedy:install door checks.

    Jan 26, 2005

    Resolve
  • Non-hazardous

    Use of illegal hardware noted stairway doors on first 2nd floors have slide bolts and padlocks at exit 2,3,4,5,6,7,8,9 note slide bolts were padlocked in an open position remedy remove all illegal hardware

    Jan 12, 2004

    Resolve
  • Non-hazardous

    Failure to maintian noted no doors checks at rooms 238,220 ,217,129,b31 looss pivot hings at fire door dept of room 211 is not opening class remedy maintain building

    Jan 12, 2004

    Resolve
  • Non-hazardous

    Failrue to provide required panic hardware. noted: in cellar gymnasium missing required panic bars on all exit doors. cpacity signs indicate 350 and 258. remedy: provide panic hardware.

    Jan 7, 2003

    Resolve
  • Non-hazardous

    Failure to maintain building. noted: at cellar gymnasium southwest side door check broken. at corner location. remedy: maintain building. repair and /or replace door check.

    Jan 7, 2003

    Resolve
  • Non-hazardous

    Failure to maintain, defect noted ; concrete stair at rear ( north ) of building ( entrace to playground ) is cracked, spalling and uneven remedy : maintian buidling, make all necessary repairs

    Jan 11, 2002

    Resolve
  • Non-hazardous

    Failrue to maintain building, defect noted : major structual crack in south faceing wall of main entrance lobby ( first floor0 also noted : structual crack at south faceing wall at basement level ( boys bathroo

    Jan 11, 2002

    Resolve
  • Non-hazardous

    Failure to maintain, defect's noted : tin - metal ceiling tiles are corroded, hanging, sagging, pulling away at basement and first floor corridors. also noted ; acustic fiber tiles at gymnasium are loose, hangi

    Jan 11, 2002

    Resolve