Violations at 178 Rivington Street
Manhattan, NY 10002 · BBL 1-00344-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
29 DOB violations, newest first.
- Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed - Boiler boiler optional
B-boiler boiler optional
Jan 12, 1993
Dob violation - dismissed - Boiler boiler optional
B-boiler boiler optional
Jan 12, 1993
Dob violation - active
ECB violations
The newest 50 of 71 ECB violations. The city keeps the complete history.
- Class - 2
At time of inspection at 123 ridge street, observed that required dob permits were not posted in a visible location throughout the jobsite. this is a violation of 1 rcny 3301-02, and bc 3301.2, as proper permi
Jul 2, 2025
Resolve - Class - 1
At time of inspection, i observed several workers at the cellar level in an approx 2 b=' (d) x 20' (l) trench, laying electric conduit contrary to the description of work on ahv ref # 1103965. pswo issued for a
Oct 29, 2024
Resolve - Class - 2
Exit door not self-closing.noted:at gym,exit door not self-closing.remrepair or replace.
Sep 9, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.noted:at electrical room at cellar approx.2'hole in the corner under the conduits with no firestopping.rem:provide/maint
Sep 9, 2024 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building wall(s)or appurtenances.noted:at rooftop parapet is only 27"in height and gym auditorium and cafeteria do not hand parapet at all.buildings with bulkhead roof access are required to
Sep 9, 2024 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:the following doors do not close properly.room#304,308,319,220 with broken door closer smoke door next to room 202 staircase b at first floor going to
Sep 9, 2024 · Penalty $625
Resolve - Class - 2
Reissue#35495931n exit door not self-closing.at time of my inspection i observed exit door at 154 no self closing also at the basement levellevel exit door not self-closing properly,violation#35296931n issued 0
May 12, 2022 · Penalty $625
Resolve - Class - 2
Reissue#35560976p failure to maintain building wall(s)or appurtenancesat time of my inspection i observed at roof level parapet wall in disrepair at ne and nw corner of the building with cracks,also capstone or
May 12, 2022 · Penalty $3,125
Resolve - Class - 2
Reissue#35560977r failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.at time of my inspection i observed emergency lights not
May 12, 2022 · Penalty $1,562
Resolve - Class - 2
Exit door not selfclosing note following doors dont close properly exit door2a 2fl b1 1fl &bsmt exitb.repair &/or replace door.
Apr 29, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner note@roof level lowerroof over gym roof leaks causing damage to ceiling below.repair &/or replace.
Apr 29, 2021 · Penalty $625
Resolve - Class - 2
Reissue35495931n failure to maintain bldg in codecompliant manner illumination for exits,exit discharges&public corridors per bc1006.1;27-345 note emergency lights not working in gym auditorium@exit1a when test
Apr 29, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue35495933r failure to maintain bldg walls or appurtenances note@roof level parapet wall in disrepair@ne&nw corner of bldg w/cracks.also capstone on parapet wall in disrepair spalling&loose.maintain bldg e
Apr 29, 2021 · Penalty $3,125
Resolve - Class - 2
Sec. 28-301.1 reissue#35495935k failure to provide natual or mechanical ventilation to occupied spaces per mc 401.2. note: at cellar level storage of gas equipment ie 3 snowblower 1 leaf vaccum. remedy: comply
Apr 29, 2021 · Penalty $3,125
Resolve - Class - 2
Sec. 28-301.1 failure to maintain bldg in code compliant manner. note: at cellar level paint not stored n storage cacabinet or closet. remedy: comply w/violation store paint properly.
Jun 1, 2020 · Penalty $1,250
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. note at 3rd fl firesprinkler control valve not working,will not close. remedy: repair &/or replace.
Jun 1, 2020 · Penalty $625
Resolve - Class - 2
Sec. 28-301.1 failure to provide natural or mechanical ventilation to occupied spaces per mc 401.2. note: at cellar level storage at gas equipment 1 snow blower. remedy: cmply w/violation remove gads equipment.
Jun 1, 2020 · Penalty $1,250
Resolve - Class - 2
Failure to maintain bldg in code compliant manner use of prohibited door & or hardware per bc 1008.1.8;27-371(j). note: the following door have illegal kick stops installed room 329,316,305,both boys & girls
Jun 1, 2020 · Penalty $625
Resolve - Class - 2
Reissue#35422114x failure to maintain bldg walls & appurtenance. note:at roof level crack at parapet wall & ne & nw corner of bldg on ridge street. also the cap stone on parapet in disrepair. remedy: maintain
Jun 1, 2020 · Penalty $1,250
Resolve - Class - 2
Reissue#35422116j failure to maintain bldg in code compliant manner nofire stopping per bc 712.3;27-345. note: at cellar level in electrical room no fire stopping around pipes penetrating thru ceiling.
Jun 1, 2020 · Penalty $3,125
Resolve - Class - 2
Reissue#35422123h failure to maintain bldg in cofde compliant manner. illumination for exits,exit discharges & public corridors per bc 1006.1;27-345. note: emergency lights not working in gym(all lights)auditor
Jun 1, 2020 · Penalty $1,562
Resolve - Class - 2
Exit door not self closing. at main outside main entrance 2 doors and 2nd fl stair "a" one door is not self closing properly at the time of inspection when tested at the time of inspection. remedy:repair/replac
Apr 25, 2019
Resolve - Class - 2
Failure to maintain building in code-compliant manner illumination forexits,exit discharges and public corridors per bc 1006.1;27-381. at lunch room 3 place each place 2 lights,at 2nd fl exit "2" staircase "a"
Apr 25, 2019
Resolve - Class - 2
Reissue#35322439x date of issue 3/13/18 failure to maintain building in code-compliant manner:no fire stopping per bc 712.3;27-345 at the time of inspection observed at basement level,electric room several hole
Apr 25, 2019
Resolve - Class - 2
Reissue#35322440n date of issue 3/13/18 failure to maintain building in code-compliant manner at time of inspection observed at basement level boiler room water damage to wall due to water penetration,through r
Apr 25, 2019
Resolve - Class - 2
Reissue#35322441p date of issue 3/13/18 failure to maintain building wall(s) or appurtenances. at time of inspection observed cracked exterior brick masonry at n/e corner at ridge st also crack masonry at parap
Apr 25, 2019
Resolve - Class - 2
Reissue 352527751j failure to maintain building wall(s) or appurtenances. noted: at time of inspection observed cracked exterior brick masonry at n/e corner at ridge st also crack masonry at parapet missing mo
Mar 13, 2018
Resolve - Class - 2
Reissue #35252752l. failure to maintain building in code-compliant manner. noted: at time of inspection observed at basement level: boiler room water damage to wall due to water penetration, thought retaining w
Mar 13, 2018
Resolve - Class - 2
Reissue 35252753n failure to maintain bldg in code compliant manner:no fire stopping per bc 7123; 27-345. noted at time of inspection observed at basement level, electric room, several holes around pipe missi
Mar 13, 2018
Resolve - Class - 2
Failure to maintain bldg in code complaint manner: no fire stopping per bc 712.3;27-345. noted: at basement level,electric room,several holes around pipes missing fire stopping. remedy: comply w/code/provide
Apr 7, 2017
Resolve - Class - 2
Failure to maintain bldg in code complaint manner. noted: at basement level,boiler room,water damage to wall due to water penetration through retaining wall. remedy: comply w/code/repair the walls.
Apr 7, 2017
Resolve - Class - 2
Reissue#35201081j failure to maintain bldg walls or appurtenances. noted: cracked exterior masonry at n/e corner at ridge st. also cracked masonry at parapet w/missing mortar joint at same location.
Apr 7, 2017
Resolve - Class - 2
Reissued# 35148404p. failure to maintain bldg walls(s) or appurtenances. noted: cracked exterior masonry @ n/e corner @ ridge st, cracking & seperation. missing mortar joints 1st flr to parapet wall. 2nd flr cr
Jul 26, 2016
Resolve - Class - 2
Fail maintain bldg in compliant manner:lack emergency light for exits.note:inoperative emergency lighting above the exit doors at gym. rem:repair and/or replace lighting.
Oct 5, 2015
Resolve - Class - 2
27-371(b) fail to maintain bldg in code-compliant manner.note:missing required wired vision panels in the doors throughout the bldg. rem:repair and replace.
Oct 5, 2015
Resolve - Class - 2
Reissue #35093661k failure to maintain building wall(s) or appurtenancnote:cracked exterior brick masonary @n/e corner @ridge st, cracking & separation,missing mortar joints 1st fl to parapet wall.2nd fl crack
Oct 5, 2015
Resolve - Class - 2
Reissue #35093662m exit door not self-closing.note:at 3b,door racked to frame and not closing.at 3rd floor smoke doors adjacent to room 306:both closers broken. rem:repair/replace doors
Oct 5, 2015
Resolve - Class - 3
Reissue #35093666j failure to maintain building wall(s) or appurtenanc.note:loose roof flashing.several pieces of metal roof flashing are dislodged and loose along east parapet wall facing ridge st.rem:secure l
Oct 5, 2015
Resolve - Class - 3
Loose roof flashing. several pieces of metal roof flashing are dislodged & loose along east parapet wall facingj ridge street. remedy: properly secure loose roof flashing.
Mar 27, 2014
Resolve - Class - 2
Work without permit. at right side along ridge street, installed/erected approx 17'long x 8'deep x 8'high (wood) shed. complete with flat roof & attached to north wall. remedy: obtain permit if feasible or remo
Mar 27, 2014
Resolve - Class - 2
Defective emergency lighting. at 1st floor auditorium, 50% of emergency lighting is inoperative. at gym emergency lighting is not operating. remedy: repair or replace lighting.
Mar 27, 2014
Resolve - Class - 2
Excessive combustibles in fire stairs. at fire stairwell "b", 3 paper sculpture figures installed 2nd to 3rd floor & 3rd floor stairwell landings. remedy: remove items.
Mar 27, 2014
Resolve - Class - 2
Exit doors not self closing. at 3b, door racked to frame & not closing. at 3rd floor smoke doors adjacent to room 306 both closers broken. remedy: repair if feasible or replace.
Mar 27, 2014
Resolve - Class - 2
Re-issue # 34987576m. cracked exterior brick masonry. at northeast corner, cracking & separation missing mortar joints 1st floor to parapet wall. remedy: repair exterior masonry wall.
Mar 27, 2014
Resolve - Class - 2
Reissue 34933923y. exterior wall at northeast corner and west side, (has) cracks w/missing mortar joints. remedy: make repairs.
Jan 9, 2013
Resolve - Class - 2
Failure to maintain exterior wall at: northeast corner slight shifting/missing mortar along window frame & cracked brick parapet n/e corner. remedy: make repairs to facade.
Feb 10, 2012
Resolve - Class - 2
Illegal door hardware per bc 1008.1.8, 27-371(j). at all flrs, the smoke doors in the corridors have hardware installed that stops 1 of 2 smoke doors from self-closing. remedy: remove illegal hardware and/or
Mar 3, 2011
Resolve - Class - 3
Plaster damage at gym above windows near exit 16 in gym. remedy:repairwall.
Nov 17, 2008
Resolve - Class - 2
Exit doors leading to exterior missing panic hardware @ room 139,129. remedy:install panic hardware
Nov 17, 2008
Resolve - Class - 2
Missing exit lighting @ rear door to exterior room 139,129 and kitchen127,131,137.remedy:install exit lighting
Nov 17, 2008
Resolve