Manhattan, NY 10013 · BBL 1-00216-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

The newest 50 of 250 DOB violations. The city keeps the complete history.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 9a technical report by 02/21/2022

    Feb 22, 2022

    Dob violation - dismissed
  • Failure to post energy grade/score none

    Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3

    Dec 1, 2021

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 24, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 24, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 17, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 17, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 17, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 17, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 17, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 17, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 17, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 17, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 11, 2020

    Dob violation - resolved

ECB violations

The newest 50 of 83 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to submit an acceptable required cycle 8a report of critical examination documenting condition of exterior wall & appurtenances required by 28-302.4 for control#800474. agg1 prior nov 37011164k under 28

    Apr 1, 2021

    Resolve
  • Class - 2

    27-929.1 failure to complete the installation of a full system of automatic sprinklers and file a final sprinkler report prepared by a registered design professional in an office building 100ft or more in heigh

    Mar 30, 2021 · Penalty $3,125

    Resolve
  • Class - 1

    Sec. 3301.1 failure to comply w/osha(rules)& regulations as per 3301.1. at time of inspection on an active jobsite of a 39 sty occupied bldg observed welding operations into a tank at cellar level. no proper

    Dec 3, 2020 · Penalty $2,500

    Resolve
  • Class - 1

    Failure to maintain/display on site drawings/documents required by chapter 33. at time of inspectioin on an active jobsite of 39 sty occupied bldg observed,welding operations at cellar w/excess smoke & fumes. a

    Dec 3, 2020 · Penalty $2,500

    Resolve
  • Class - 2

    27-929.1 failure to complete the installation of a full system of automatic sprinklers and file a final sprinkler report prepared by a registered design professional by july 1,2019,in an office building 100 fee

    Mar 30, 2020

    Resolve
  • Class - 2

    Sec. 27-929.1 ac 27-929.1 failure to complete the installation of a full system of automatic sprinklers & file a final sprinkler report prepared by a registered design professional by 7/1/19,in an office bldg

    Mar 30, 2020 · Penalty $3,125

    Active
  • Class - 2

    Bc27-929.2/a.c. 27-929.1,failure to complete the installation of a full system of automatic sprinklers and file a final sprinkler report prepared by a registered design professional by july 1,2019,in an office

    Nov 15, 2019

    Resolve
  • Class - 2

    27-929.1 a.c. 27-929-1,failure to complete the installation of a full system of automatic sprinklers and file a final sprinkler report prepared by a registered design professional by 7/1/19,in an office buildin

    Nov 15, 2019 · Penalty $3,125

    Resolve
  • Class - 2

    Violation of discretionary zoning conditions on privately owned publicspace noted:as per zoning resolution charter(7) section 37-78(b)a periodic compliance report is required as of date no periodic compliance r

    Nov 8, 2019 · Penalty $625

    Resolve
  • Class - 1

    Failure to institute and maintain safety measures.in response to an accident where it was reported by ssm carpenter(april johnson)was caughtin between sheetrock and wall(loading dock opening)during delivery ope

    Sep 10, 2019

    Resolve
  • Class - 1

    Failure to notify the department of an incident that resulted in a fatality or injury not one worker got caught between the sheetrock and the wall when the delivery truck driver moved the sheetrock he was taken

    Sep 10, 2019 · Penalty $5,000

    Resolve
  • Class - 1

    Failure to notify the department of an incident that resulye din a afatality or injury noted a worker tripped on his extension cord and hurt his sholder was taken to hospital by ambualcen as per department rec

    Sep 6, 2019 · Penalty $5,000

    Resolve
  • Class - 2

    Crane user benson industries cn#336/16 using crane @ 107 north moore st failed to the department of the cranes departure as required by law @ the time of inspection no proof of the cranes departure existed.rem

    Dec 17, 2018 · Penalty $5,000

    Resolve
  • Class - 1

    Material storage @leading edge.@time of insp on a active a 39 story bldg,observed improper material stored @leading edge @exp#3 (west side hwy) material storage consisting of debris,const material,w/in less to

    Jul 12, 2018 · Penalty $2,500

    Resolve
  • Class - 1

    Bc 3308.5.3 cable/ system (guardrails) inadequate @time of insp on an active jobsite of 39 story bldg i oberved from grade level to 14th fl inadequate cable system @exp#3 (westside hwy) cable inadequate due to

    Jul 11, 2018 · Penalty $2,500

    Resolve
  • Class - 2

    Failure to submit acceptable 8th round report of critical examination documenting condition of exterior walls and appurtenances required by 28-302.4 for control#800406. remedy: submit required technical report

    May 18, 2018 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to submit acceptable 8th round report of critical examination documenting condition of exterior walls and appurtenances required by 28-302.4 for control#800474. remedy: submit required technical report

    May 18, 2018 · Penalty $3,125

    Resolve
  • Class - 1

    Bc3303.10.operating in occupied buildings.note:at time of my inspection of a building under alteration,construction work in progress.i observed that building was occupied with occupants and on 7th floor level i

    Nov 30, 2017 · Penalty $1,600

    Resolve
  • Class - 1

    Bc3301.1.2.failure to comply with nyc fire code-general-no fire watch,fire guard,certificate of fitness.note:at time of my inspection i observed multide areas of welding operation on 2nd floor level, i also obs

    Nov 30, 2017 · Penalty $1,600

    Resolve
  • Class - 2

    Bc3314.4.3.2.(bc3301.7)installation for suspended scaffold.note:at thetime of inspection of a building under alteration,construction work inprogress.i observed suspended scaffold being used at exposure one and

    Nov 30, 2017 · Penalty $400

    Resolve
  • Class - 1

    Bc3314.11.5.3.protective covers.note:at the time of my inspection of a39 story building under alteration,construction work in progress.i observed that hoist machine was not provided with covers(insualted)as req

    Nov 30, 2017 · Penalty $1,600

    Resolve
  • Class - 1

    Bc3314.11.5.2.insulating material.note:at the time of my inspection ofa 39 story building under alteration,construction work in progress.i observed suspended scaffold being use at exposure one for welding opera

    Nov 30, 2017 · Penalty $1,600

    Resolve
  • Class - 2

    42b10. 42b10 escalator fails to have a variable frequency regenrative drive as per section requirements.rem:comply with code.

    Oct 21, 2017

    Resolve
  • Class - 2

    42b10. 42b10 escalator fails to comply with asme 17.1/csa or local code when not conveying passengers.rem:comply with code.

    Oct 21, 2017

    Resolve
  • Class - 2

    42b10. 42b10 escalator fails to have a variable frequency regenerativedrive as per section requirements.rem:comply with code.

    Oct 21, 2017

    Resolve
  • Class - 2

    42b10. 42b10 escalator fails to comply with asme a17.1/csa or local code when not conveying passengers.rem:comply with code.

    Oct 21, 2017

    Resolve
  • Class - 2

    42b10 escalator fails to comply with asme a.17.1 / csa as locl code when not conveying passengers. rmdy: comply with code.

    Sep 13, 2017

    Resolve
  • Class - 2

    42b10 excalator fails to comply with asme a17.1/ csa on local code when not conveying passengers. rmdy: comply with code.

    Sep 13, 2017

    Resolve
  • Class - 2

    42b10 excalator fails to comply with asme a17.1/ csa on local code when not conveying passengers. rmdy: comply with code.

    Sep 13, 2017

    Resolve
  • Class - 2

    42b10 excalator fails to have a variable frequency regenerative drive as per section requirements.rmdy: comply with code.

    Sep 13, 2017

    Resolve
  • Class - 2

    42b10 excalator fails to have a variable frequency regenerative driveas per seciton requirements. rmdy: comply with code.

    Sep 13, 2017

    Resolve
  • Class - 2

    42b10 excalator fails to have a variable frequency regenerative drive as per section requirements.rmdy: comply with code.

    Sep 13, 2017

    Resolve
  • Class - 1

    Work without permit-work after hours without a variance contrary to 28-105.12.5;work in progress under permit#10454129 after hours without variance.rem:stop all after hours work.

    May 10, 2017 · Penalty $800

    Resolve
  • Class - 2

    Operation of a crane without a certificate of on site inspection/no cn-see swo #042717rh01 at time of inspection audit,respondent above usedknuckle bodm sn #100278124 to service jobsite.such operation required

    Apr 27, 2017

    Resolve
  • Class - 2

    Operation of a crane w/o a certificate of on site inspection,no cn-seeswo#042717rh01 at time of inspection audit,respodent above used knuckle boom sn#100278124 to service jobsite. such operation required an ons

    Apr 27, 2017 · Penalty $2,400

    Resolve
  • Class - 2

    Operation of a crane w/o a certificate of on site inspection no cn(crane notice).see swo#042717rh01 at time of inspection audit,respondent above used knuckle boom sn#10027124 to service jobsite. such operation

    Apr 27, 2017 · Penalty $2,400

    Resolve
  • Class - 2

    Operation of crane w/o a c pf p approval no cd-see swo#042717rh01 at time of inspection audit,respondent above used knuckle boom sn#100278124 to service jobsite. such operation required permits(crane). crane sh

    Apr 27, 2017

    Resolve
  • Class - 2

    Operation of crane w/o a c of o approval/no cd-see swo#042717rh01 at time of inspection audit,respondent aboce used knuckle boom sw#100178124 to service jobsite. such operation required permits(crane)crane shal

    Apr 27, 2017 · Penalty $2,400

    Resolve
  • Class - 2

    Operation of crane w/o certificate of approval/operation/no cd-see swo#002717rh01 at time of inspection audit,respondent above used knuckle boom sn#100278124 to service job site. such operation required permits

    Apr 27, 2017 · Penalty $2,400

    Resolve
  • Class - 1

    Operating an articulating boom crane w/o a certificate of approval-see swo#042717rh01 at time of audit inspeciton,m cohen & sons(subcontractor)used knuckle boom sn#100278124 to service jobsite/setting steel a

    Apr 27, 2017 · Penalty $1,000

    Resolve
  • Class - 1

    Operating an artilulating boom crane w/o a certificate of approval-see swo#042717rh01 att ime of audit inspection,g/c tishman construction corp used knuckle boom sn#100278184 to service jobsite/setting steel at

    Apr 27, 2017

    Resolve
  • Class - 1

    Operating an articulating boom crane w/o certificate of approval. see swo#042717rh01. at time of audit inspection lifting solutions used knuckle boom,sn#100278124 to service jobsite/setting steel at aboce locat

    Apr 27, 2017

    Resolve
  • Class - 1

    Supervision or use of power operated machine w/o a hoisting machine operators license-see swo#242717rh01. at time of inspection/ausit respodent above used knuckle boom sw@100278124 to service jobsite,setting

    Apr 27, 2017

    Resolve
  • Class - 1

    Supervision or use of power operated machine w/o a hoisting machine operators license/see swo#042717rh01 at time of inspection/audit respodent aboce used knuckle boom sn#100278124 to service jobsite setting at

    Apr 27, 2017 · Penalty $1,600

    Resolve
  • Class - 1

    Supervision or use of power operated machine w/o a hoisting machine operators license. see seo#042717rh01 at time of inspection/audit respodent above used knuckle boom sn#10027824 to service jobsite,setting ste

    Apr 27, 2017 · Penalty $1,600

    Resolve
  • Class - 1

    3303.10 tenant protection plan-occupied building.note:at the time of my inspectionof a 39 story building under alteration(occupy)upon request for tenant protection plan as require for construction operation in

    Dec 2, 2016 · Penalty $1,600

    Resolve
  • Class - 1

    3310.3 failure to have site safety plan and program as required.note:at the time of my inspection of a 39 story building under alteration.upon request for site safety plan as require for construction operation

    Dec 2, 2016 · Penalty $1,600

    Resolve
  • Class - 1

    Presense at site. note: at the time of my insp. of a 39 story alteration job construction work in progress. responding to compliant # 1438118 where it was reported that a pipe filter was pushing a heating unit

    Nov 25, 2016 · Penalty $1,200

    Resolve
  • Class - 1

    Bc3308.10 tenant protection plan-occupied bldgs. note: at the time of my inspection of a 39 story bldg under alteration (occupy). upon request for tenant protection plan,what was provided was inadequate as it o

    Nov 25, 2016 · Penalty $1,600

    Resolve
  • Class - 1

    Electrical wrk w/out a permit.temporary wiring.the entire bldg temporary wiring,ground flr-construction office cellar storage rooms.sub feeders,sub panels,branch circuit wiring,recepticles outlets,lighting fixt

    Oct 11, 2016 · Penalty $800

    Resolve