roofy
Landlords

NYC Elevator Inspection and Testing Rules

NYC elevator rules for owners: the yearly periodic inspection and CAT1 test, the 5-year CAT5 test, 14- and 21-day DOB filing deadlines, repairs and fines.

7 min read · Updated

Every elevator in a New York City building needs a periodic inspection and a Category 1 (CAT1) test every calendar year, plus a Category 5 (CAT5) full-load test every five years, each done by an approved elevator agency and filed with the Department of Buildings (DOB). Inspection reports are due 14 days after the inspection and test reports 21 days after the test, and missing them can cost $3,000 to $5,000 per elevator in a typical apartment building.

DOB says the city has more than 70,000 elevators and escalators. The rules below come from DOB's Elevator Compliance page and the department's rule, 1 RCNY §103-02. They apply to the owner, even when a managing agent or the elevator company handles the paperwork.

Elevator compliance at a glance

Periodic inspection
Every year, Jan 1–Dec 31
File within 14 days of the inspection
Category 1 test (no load)
Every year, Jan 1–Dec 31
File within 21 days of the test
Category 5 test (full load, rated speed)
Every 5 years
Due by the month of the 5-year anniversary
Fix defects
Within 90 days
Hazardous and firefighter-service defects: immediately
Affirmation of correction
Within 14 days of the repair
Filed in DOB NOW: Safety
Door lock monitoring
Required since Jan 1, 2020
All automatic passenger and freight elevators

The three required inspections and tests

The NYC Building Code (Appendix K, Table N1) sets the intervals, and 1 RCNY §103-02 sets the filing rules. For a standard electric or hydraulic elevator in an apartment building, the schedule looks like this:

Required elevator inspections and tests in NYC
TypeHow oftenWhat happensWho does itFiling deadline
Periodic inspectionOnce each calendar year, at least 3 months after any CAT1 test or the previous periodic inspectionAnnual visual inspection of the deviceAn approved elevator agency that is not affiliated with your maintenance company14 days after the inspection; not accepted after Jan 14 of the next year
Category 1 (CAT1) testOnce each calendar year (Jan 1–Dec 31)Annual safety test with no load in the carPerformed by an approved agency and witnessed by a separate, independent approved agency21 days after the test; not accepted after Jan 21 of the next year
Category 5 (CAT5) testWithin 5 years of the month of the last CAT5 test, or of the certificate of compliance for a new elevatorFull-load test at rated load and speedPerformed by an approved agency and witnessed by a separate, independent approved agency21 days after the test; the test itself must happen by the end of the anniversary month
Source: NYC DOB Elevator Compliance; 1 RCNY §103-02; Building Code Appendix K Table N1

Escalators, moving walks, dumbwaiters, wheelchair lifts and other conveying equipment have their own lines in Table N1. Private residence elevators follow a lighter schedule in Table N1, and under the rule their periodic inspection reports do not need to be filed with DOB, though they must be kept for six years and shown to DOB on request. Under note 5 of Table N1, a dismantled device does not need CAT1 or CAT5 tests but still needs periodic inspections.

Who can inspect and test

Only an approved elevator agency, meaning a DOB-licensed agency director and its licensed inspectors, can do this work. Two independence rules matter:

  • The agency doing the periodic inspection cannot be affiliated with the company that maintains the elevator.
  • Category tests are performed by an approved agency and witnessed by an independent, approved third-party agency, so plan on two agencies being involved in each CAT1 and CAT5.

The agency must notify DOB at least five calendar days before a Category 3 or 5 test (and before Category 1 tests on escalators). Filings are submitted in DOB NOW: Safety. The owner, the agency director and the inspector each need an NYC.ID account, and the owner's email should be on the filing so it shows on the owner's dashboard.

Correcting defects and filing the affirmation

  1. 1

    Get the report

  2. 2

    Fix hazardous items immediately

  3. 3

    Fix everything else within 90 days

  4. 4

    File the Affirmation of Correction (AOC)

  5. 5

    Ask for an extension before the deadline if you need one

Door lock monitoring

Appendix K of the Building Code (Section 3.10.12) required all automatic passenger and freight elevators to have a door lock monitoring system by January 1, 2020. The system watches the car door and landing door contacts and stops the car from running if a door is not closed or a contact has been bypassed. Limited-use/limited-application (LULA) elevators have until January 1, 2027 to comply with the same section. If your building has a LULA and has not added door lock monitoring, talk to your elevator contractor now, because the work usually needs a DOB permit filed by a licensed elevator agency director or registered design professional.

Penalties

Penalties depend on the building. The rule sets a lower tier for buildings with one or two residential units and a higher tier for commercial buildings, mixed-use buildings and buildings with more than two apartments. Most NYC rental buildings are in the higher tier.

Civil penalties per elevator under 1 RCNY §103-02
Violation1–2 unit residential3+ units, mixed-use or commercial
Failure to file CAT1 report$1,000$3,000
Failure to file CAT5 (or CAT3) report$1,000$5,000
Failure to file periodic inspection reportNone listed (private elevator reports are kept, not filed)$3,000
Late CAT1 or periodic report$50/month, max $600$150/month, max $1,800
Late CAT5 report$50/month, max $600$250/month, max $3,000
Failure to correct defects / file AOC$1,000$3,000
Late AOC$50/month, max $600$150/month, max $1,800
Source: 1 RCNY §103-02(h) and (i)

A late report is accepted only if you can prove the inspection or test happened during the cycle it was due. Reports filed after the late window are treated as expired: you pay the failure-to-file penalty, redo the inspection or test in the current cycle and file a new report. DOB also says most failure-to-file violations cannot be dismissed without paying the full penalty, and a current report must be on file before older violations can be cleared. New owners, and owners whose elevator was removed, may qualify for a waiver.

A sample year for a building with one elevator

  1. January–March

    Schedule the CAT1 test

    Book the performing and witnessing agencies early so the cycle does not close on you.
  2. Test day + 21 days

    CAT1 report filed in DOB NOW: Safety

    Confirm the filing shows on your owner dashboard.
  3. At least 3 months after the CAT1

    Periodic inspection

    Report due 14 days later.
  4. Within 90 days of each inspection

    Repairs done

    AOC filed within 14 days of the repair.
  5. Anniversary month (every 5 years)

    CAT5 full-load test

    Check the month of your last CAT5 so you do not miss the window.
  6. December 31

    Cycle closes

    CAT1 reports are not accepted after January 21; periodic reports after January 14.

How to check a building's elevator record

Elevator violations show up as DOB and ECB violations. Search an address on Roofy's building lookup to see open DOB violations, and read DOB violations explained and how to clear DOB violations if you find one. For a full list of what your building owes the city each year, use the landlord compliance calendar, and see the boiler inspection rules for the other big annual DOB filing.

This guide is general information, not legal advice. Your elevator agency and DOB's Elevator Division can confirm the exact schedule for your devices.

Fact-checked October 12, 2026

Re-verified 2026-10-12 against the DOB Elevator Compliance page and full text of 1 RCNY §103-02: Jan 1–Dec 31 cycles, 3-month spacing of periodic inspections, 14-day periodic and 21-day test filing deadlines (Jan 14/Jan 21 cutoffs), 90-day correction, 14-day AOC, 104-day FTC trigger, 5-day test notice, private-elevator six-year retention, waiver grounds and both penalty tiers ($1,000/$50/$600 for 1–2 unit residential; $3,000/$5,000, $150/$1,800 and $250/$3,000 for 3+ unit, mixed-use and commercial). Table N1 note 5 (dismantled devices) and door lock monitoring dates (Jan 1, 2020; LULA Jan 1, 2027) checked in Building Code Appendix K. Confirmed DOB FAQ pages still show older 60/120-day figures. NYC.ID and owner-dashboard details from the DOB NOW: Safety elevator FAQs; 70,000 devices from the Elevator Safety page.

Sources

  1. Elevator Compliance · NYC Department of Buildings (accessed October 12, 2026)
  2. 1 RCNY §103-02: Elevator inspections and tests, filing requirements, penalties and waivers · NYC Department of Buildings (accessed October 12, 2026)
  3. 2022 NYC Building Code, Appendix K: Elevator standards (Table N1 and Section 3.10.12) · NYC Department of Buildings (accessed October 12, 2026)
  4. Elevator Frequently Asked Questions · NYC Department of Buildings (accessed October 12, 2026)
  5. DOB NOW: Safety elevator FAQs · NYC Department of Buildings (accessed October 12, 2026)
  6. Elevator Safety · NYC Department of Buildings (accessed October 12, 2026)

General information, not legal, tax or financial advice. Rules change; confirm with the agency or a professional before you act.

Keep reading