22-04 Collier Avenue
Queens, NY 11691BBL 4-15771-0071Map
Owner of record: 22-04 Collier Ave LLC
22-04 Collier Avenue is an elevator apartment building built in 1963 in Queens, 11691. It has 62 residential units across 6 floors. The owner of record is 22-04 Collier Ave LLC. HPD has recorded 1,450 housing violations here, most recently on October 7, 2026. 22 of the 50 most recent violations are still open. City tax records listed 62 rent-stabilized apartments here in 2024.
- HPD violations
- 1,450
- DOB violations
- 31
- ECB violations
- 27
- HPD complaints
- 2,466
What to know
Immediately hazardous issues among recent violations are still open.
Date of the most recent HPD inspection that found a problem.
No balance due on recent ECB violations.
Rent stabilization
Counts come from owners' rent-stabilization filings shown on NYC Department of Finance tax bills, as extracted by JustFix. They tell you a building has stabilized apartments, not which ones.
Think your apartment is stabilized? Request its rent history from HCR (free), then check your renewal with the renewal calculator.
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 1,450
- CImmediately hazardous
Abate the infestation consisting of roaches in the entire apartment located at apt 6k, 6th story, 2nd apartment from north at east
Oct 7, 2026 · Apt 6K
Open — Civ14 mailed - BHazardous
Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling in the 3rd room from north located at apt 3f, 3rd story, 2nd apartment from south at west
Aug 21, 2026 · Apt 3F
Open — Nov sent out - ANon-hazardous
Trace and repair the source and abate the visible mold condition... less than 10 square feet at ceiling in the 3rd room from north located at apt 3f, 3rd story, 2nd apartment from south at west
Aug 21, 2026 · Apt 3F
Open — Notice of issuance sent to tenant - CImmediately hazardous
Fire escape defective. replace with new the broken, defective and/or missing 6th metal tread from bottom at 2nd stack at west at 1st story balcony at fire escape
Aug 21, 2026
Open — Nov certified on time - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective closer arm at 1st fire door leading to boiler room at basement at east
Aug 7, 2026
Closed — Violation closed - BHazardous
Properly repair or replace the broken or defective latch set at fire door leading to fire stairs (labeled 4th floor) at public hall, 3rd story
Jul 14, 2026
Open — Nov certified on time - ANon-hazardous
Paint with light colored paint to the satisfaction of this department at all walls and ceiling at basement
Jul 14, 2026
Open — Nov certified on time - BHazardous
Properly repair with similar material the broken or defective fire retardant materials at ceiling and east wall at lobby area at basement
Jul 14, 2026
Open — Nov certified on time - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective hinges at 1st fire door leading to boiler room at section east at basement
Jul 14, 2026
Open — Not complied with - ANon-hazardous
Trace and repair the source and abate the visible mold condition... less than 50 square feet at ceiling and east wall at lobby area at basement
Jul 14, 2026
Open — Nov sent out
Show 40 more ↓
- ANon-hazardous
Paint with light colored paint to the satisfaction of this department at all walls and ceiling ( labeled 7th floor ) at public hall, 6th story
Jul 14, 2026
Open — Nov sent out - CImmediately hazardous
Remove device preventing door from being self-closing wood wedge at 1st and 2nd fire door leading to laundry room at basement
Jul 14, 2026
Closed — Violation closed - BHazardous
Repair the leaky and/or defective faucets ,at wash basin in the bathroom located at apt 2k, 1st story, 2nd apartment from north at east
Jun 14, 2026 · Apt 2K
Open — Nov sent out - ANon-hazardous
Dept. rules and regs. replace refuse chute warning sign public hall door to service closet or on wall over hopper door at 1st,4th,5th and 6th story public hall at compactor closet
May 21, 2026
Open — Nov sent out - ANon-hazardous
Paint with light colored paint to the satisfaction of this department at ceiling and east wall in the 1st room from north at west located at apt 5j, 4th story, 1st apartment from north at east
May 21, 2026 · Apt 5J
Open — Civ14 mailed - ANon-hazardous
Paint with light colored paint to the satisfaction of this department at ceiling in the 1st room from north at east located at apt 5j, 4th story, 1st apartment from north at east
May 21, 2026 · Apt 5J
Open — Civ14 mailed - ANon-hazardous
Paint with light colored paint to the satisfaction of this department all walls and ceiling in the private hallway located at apt 5j, 4th story, 1st apartment from north at east
May 21, 2026 · Apt 5J
Open — Civ14 mailed - BHazardous
Repair the broken or defective plastered surfaces and paint in a uniform color at all walls and ceiling in the kitchen located at apt 6k, 5th story, 3rd apartment from west at north
Feb 10, 2026 · Apt 6K
Open — Nov sent out - BHazardous
Repair the broken or defective plastered surfaces and paint in a uniform color at all walls and ceiling in the 1st room from east at north located at apt 6k, 5th story, 3rd apartment from west at north
Feb 10, 2026 · Apt 6K
Open — Nov sent out - BHazardous
Properly repair with similar material the broken or defective fire retardant material at ceiling at lobby
Jan 28, 2026
Closed — Violation closed - BHazardous
Properly repair the source and abate the evidence of a water leak at ceiling at lobby
Jan 28, 2026
Closed — Violation closed - CImmediately hazardous
Properly repair with similar material the broken or defective fire retardant material at ceiling at public hall at basement
Jan 17, 2026
Closed — Violation closed - ANon-hazardous
Paint with light colored paint to the satisfaction of this department ceiling at public hall at basement
Jan 17, 2026
Closed — Violation closed - CImmediately hazardous
Remove all obstructions and repair all defects in bathtub drain pipe in the bathroom located at apt 2k, 1st story, 2nd apartment from north at east , section at west
Dec 18, 2025 · Apt 2K
Closed — Violation dismissed - BHazardous
Properly repair or replace the broken or defective ceiling light fixture in the kitchen located at apt 2k, 1st story, 2nd apartment from north at east , section at west
Dec 18, 2025 · Apt 2K
Closed — Violation dismissed - ANon-hazardous
Paint with light colored paint to the satisfaction of this department ceiling east south and west walls in the 3rd room from north at east located at apt 2k, 1st story, 2nd apartment from north at east , section at west
Dec 18, 2025 · Apt 2K
Closed — Violation dismissed - BHazardous
Properly secure the loose wood saddle on floor entrance in the kitchen located at apt 2k, 1st story, 2nd apartment from north at east , section at west
Dec 18, 2025 · Apt 2K
Open — Nov sent out - BHazardous
Properly secure the loose air condition cover east wall in the 1st room from north located at apt 2k, 1st story, 2nd apartment from north at east , section at west
Dec 18, 2025 · Apt 2K
Closed — Violation dismissed - BHazardous
Properly secure the loose metal radiator cover in the 1st room from north located at apt 2k, 1st story, 2nd apartment from north at east , section at west
Dec 18, 2025 · Apt 2K
Open — Nov sent out - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective hinges in the entrance located at apt 2k, 1st story, 2nd apartment from north at east , section at west
Dec 18, 2025 · Apt 2K
Closed — Violation closed - BHazardous
Properly repair or replace the broken or defective electrical outlet west wall in the 1st room from north located at apt 2k, 1st story, 2nd apartment from north at east , section at west
Dec 18, 2025 · Apt 2K
Closed — Violation dismissed - BHazardous
Replace with new the missing electrical outlet cover in the 1st room from north located at apt 2k, 1st story, 2nd apartment from north at east , section at west
Dec 18, 2025 · Apt 2K
Closed — Violation dismissed - BHazardous
Properly secure the loose wood closet doors in the foyer located at apt 2k, 1st story, 2nd apartment from north at east , section at west
Dec 18, 2025 · Apt 2K
Open — Nov sent out - BHazardous
Properly repair the source and abate the evidence of a water leak ceiling in the 3rd room from north at east located at apt 2k, 1st story, 2nd apartment from north at east , section at west
Dec 18, 2025 · Apt 2K
Open — Nov sent out - CImmediately hazardous
Properly repair or replace the broken or defective counterbalance at lower sash, from 1st window from north at east in the 1st room from east at north located at apt 5a, 4th story, 3rd apartment from north at east
Dec 11, 2025 · Apt 5A
Closed — Violation closed - CImmediately hazardous
Abate the infestation consisting of roaches in the entire apartment located at apt 6k, 6th story, 1st apartment from north at east
Nov 12, 2025 · Apt 6K
Closed — Violation dismissed - ANon-hazardous
Properly repair with similar material the broken or defective porcelain enamel glazing at interior of bathtub in the bathroom located at apt 6k, 5th story, 2nd apartment from north at east
Oct 30, 2025 · Apt 6K
Closed — Violation dismissed - CImmediately hazardous
Remove device preventing door from being self-closing consisting of a kick down door stopper on 1st door from north at east, labeled 2j at public hall, 1st story
Oct 30, 2025
Closed — Violation closed - BHazardous
Properly repair or replace the broken or defective light fixture at ceiling, at fire stairs, 5th story
Oct 30, 2025
Closed — Violation dismissed - ANon-hazardous
Properly repair or replace the broken or defective light fixture at ceiling in the kitchen located at apt 2k, 1st story, 2nd apartment from north at east
Oct 30, 2025 · Apt 2K
Closed — Violation dismissed - BHazardous
Repair, replace or provide an approved and operational smoke detecting device, installed in accordance with department of buildings rules and regulations missing in the entire apartment located at apt 2k, 1st story, 2nd apartment from north at east
Oct 30, 2025 · Apt 2K
Closed — Violation dismissed - BHazardous
Repair, replace or provide an approved and operational carbon monoxide detecting device, installed in accordance with applicable law and rules missing in the entire apartment located at apt 2k, 1st story, 2nd apartment from north at east
Oct 30, 2025 · Apt 2K
Closed — Violation dismissed - ANon-hazardous
Replace with new the missing electrical outlet cover plate at north wall in the 1st room from north located at apt 2k, 1st story, 2nd apartment from north at east
Oct 30, 2025 · Apt 2K
Closed — Violation dismissed - ANon-hazardous
Properly repair or replace the broken or defective light fixture at ceiling in the 1st room from north located at apt 2k, 1st story, 2nd apartment from north at east
Oct 30, 2025 · Apt 2K
Closed — Violation dismissed - ANon-hazardous
Properly repair with similar material the broken or defective caulking at perimeter of bathtub in the bathroom located at apt 6k, 5th story, 2nd apartment from north at east
Oct 30, 2025 · Apt 6K
Closed — Violation dismissed - ANon-hazardous
Refit sliding doors, closet at north in the foyer located at apt 2k, 1st story, 2nd apartment from north at east
Oct 30, 2025 · Apt 2K
Open — Nov sent out - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective frame/door, 1st firedoor from north at east leading to firestairs at public hall, 6th story
Oct 25, 2025
Closed — Violation closed - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective hinges, at 1st firedoor from north at east leading to firestairs at public hall, 2nd story
Oct 25, 2025
Closed — Violation closed - BHazardous
Properly repair the source and abate the evidence of a water leak at ceiling at lobby
Oct 25, 2025
Closed — Violation dismissed - ANon-hazardous
Cleanse to the satisfaction of this department the floor at compactor closet, 2nd story
Oct 4, 2025
Closed — Violation dismissed
DOB building violations · 31
- Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Jun 2, 2021
Dob violation - dismissed - Facade safety program facade required
Cycle 9c unsafe report filed
May 28, 2020
Dob violation - dismissed - Facade safety program facade required
Cycle 8c unsafe report filed
May 28, 2020
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 13, 2019
Dob violation - resolved - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
May 2, 2019
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Feb 16, 2019
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Feb 2, 2018
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Nov 2, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 30, 2017
Dob violation - resolved
Show 21 more ↓
- Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Aug 2, 2017
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
May 2, 2017
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Feb 22, 2017
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Feb 2, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 21, 2016
Dob violation - resolved - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Nov 2, 2016
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Aug 2, 2016
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Jun 2, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 11, 2014
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2012 inspection report
May 15, 2014
Dob violation - dismissed - Construction other optional
C-construction other optional
Nov 2, 2012
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 17, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 22, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 30, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 23, 2010
Dob violation - resolved - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 21, 2008
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2008
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 17, 1995
Dob violation - dismissed - Elevator elevatorrequired
#(73)capacity plate #(73a)top of car-#(34)junction box cover und- er car-#(73b)fan enclosure on top of car
Apr 20, 1990
Dob violation - resolved - Elevator elevatorrequired
3)car door
Sep 30, 1988
Dob violation - resolved
ECB violations · 27
- Class - 1
Class 1 (cu):failure to maintain building in code compliant manner passenger elevator equipment as per bc3001.2 & 27-987. upon inspection,fuse in elevator controller bypassed/jumped out,repair the device and co
Jul 10, 2026 · Penalty $1,250
Resolve - Class - 1
The only elevator in building (or section of building) out of service. upon inspection, the device is found to be out-of-service creating a hazardous condition as per 1rcny 11-02. remedy: restore to service imm
Jul 11, 2025 · Penalty $1,250
Resolve - Class - 1
Failure to maintain building in code compliant manner. a cease use order is in effect for the following item: 1) the elevator controller has at least 3 fuses that have been bypassed. this is a safety hazard and
Jun 25, 2025 · Penalty $1,250
Resolve - Class - 2
Provide inspection certificate in car. provide light protection in car. remove jumped fuses on controller. provide elevator company contact on mainline.
Apr 25, 2025
Resolve - Class - 1
Failure to maintain building in a code compliant manner. noted at unit 3f. observed in closet in master bedroom, excessive water damage and black mold on ceiling and walls; posing very hazardous condition to oc
Feb 11, 2025 · Penalty $1,250
Resolve - Class - 1
Main brake not adjusted properly not holding the device at the landing. when the brake is set(cu). brake monitoring switch defective arms extremely loose(cu). cat one tag expired. clean dirty pit. clean machine
Jun 6, 2024 · Penalty $1,250
Resolve - Class - 1
The only elevator in building (or section of building) out of service. upon inspection, the device is found to be out-of-service creating a hazardous condition as per 1rcny 11-02. remedy: restore to service imm
Apr 26, 2024 · Penalty $1,250
Resolve - Class - 1
Repair phone and alarm bell. provide outside communication. provide cat 1 tag.
Sep 6, 2023 · Penalty $1,250
Resolve - Class - 1
Cease use item : in car emergency stop switch inoperative , repair / non cease use items : in car emergency outside comm inoperative , repair / in car door close button damaged , replace / once cease use item i
Feb 25, 2022 · Penalty $1,250
Resolve - Class - 2
Pedestrian protection doesnt meet code spec-missing sws or no sws/inadequate sw note:ato my insp observed sws installed on pedestrian walkway not full coverage,missing corner@exp1&2 created unsafe conditions fo
Feb 12, 2022
Resolve
Show 17 more ↓
- Class - 2
Failure to maintain sws.note:ato my insp observed sws installed on walkway w/not maintain as required.sws missing netting,bolt not covered,sws roof parapet damage,loose&falling conditions,created unsafe conditi
Feb 12, 2022
Resolve - Class - 2
Failure to maintain building walls and appurtenances. observed;damaged/cracked mortar joints on parapet at exposure#3,north elevation;brokenglass on bulkhead and improperly covered exhaust shaft w/ a cement boa
Jan 11, 2022
Resolve - Class - 1
Electrical brake monitoring switch defective not working replace. machine room lights not working.
Oct 5, 2020 · Penalty $1,250
Resolve - Class - 1
Failure to take/provide safety measure such as sidewalk sheds,fence,etc where required to protect and secure public safety from documented unsafe facade as per 1rcny-103-04.facade technical report file unsafe f
Jun 13, 2020
Resolve - Class - 2
Failure to submit an acceptable required cycle 8c report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control#814994.rem:submit acceptable required t
Feb 13, 2020 · Penalty $1,250
Resolve - Class - 1
05a10 door zone restrictor altered.repair.
Aug 2, 2017 · Penalty $1,000
Resolve - Class - 1
97x17. the only elevator in bldg out of service. upon insp the device is found to be out of service creating a hazardous condition as per 1rcny 11-02. rem: restore to service immediately & notify nyc dob the de
Jul 27, 2017 · Penalty $1,000
Resolve - Class - 2
67x10,20i11,100b10,32h11. 67x10-repair communication; 20i11-replace cracked vision panel on car door; 100b10-remove vibrations in ar ride on down travel; 32h11-replace work guide shoes.
May 6, 2017 · Penalty $500
Resolve - Class - 2
05e01,28h11,16e01,45l10,67x10,77m07,70o02. 26h11-need replace hangers16e01-the hoistway door is not closed on the floors; 45i10-governor during operation emits a sound (noise) similar to a worn bearnings.
Dec 21, 2016
Resolve - Class - 1
07m07/07-m-07;zone restrictor missing locking brackett.
Sep 22, 2016
Resolve - Class - 2
59u15,59x10,59d06,67x10,07m07,16e10,10k11. (59x10)brake monitor switch inoperative. (59d06)brake pad on machine brake, loose bolt. (07m07)zone restrictor missing locking bracket. (16e10)4th flr hatch door top p
Sep 22, 2016 · Penalty $500
Resolve - Class - 2
10m07 40p07. 10m07-second car door gib missing.
Sep 12, 2011 · Penalty $250
Resolve - Class - 3
01l10.02l10.40p07. 01 & 02-l-10 alarm bell is defective
Oct 22, 2008 · Penalty $100
Resolve - Non-hazardous
H11-41h8-12i12-57o2. 52-h play in worm & gear 12-i left side guard broken.
Apr 11, 2003 · Penalty $350
Resolve - Non-hazardous
75b05/ 75b 5yr test.
Jan 24, 2001
Resolve - Non-hazardous
38x,75u,50r,15d,09d,57o, 38-rpr inoperative repair 75-perform 5 year test and tsg 15-provide grill guard for 6th floor door 09-provide second car door
Jan 5, 1998
Resolve - Non-hazardous
14m;15t;17l;63e;36m;46l;50f;03l;36r; 14.plastic set screw 7 post copy of cert.frame.15.mark door as per floors where missing.17.car door gtlglass.63.remove noise pit gov.tension sheave.36.door handle.46.replace
Jun 4, 1991 · Penalty $75
Resolve
Complaints
- Unsanitary condition
Pests
Oct 5, 2026 · Apt 3F
Open - Unsanitary condition
Pests
Oct 5, 2026 · Apt 3F
Open - Unsanitary condition
Mold
Oct 5, 2026 · Apt 3F
Open - Unsanitary condition
Pests
Sep 29, 2026 · Apt 6K
Close - Unsanitary condition
Mold
Aug 6, 2026 · Apt 3F
Close - Electric
Power outage
Jul 12, 2026 · Apt BLDG
Close - Plumbing
Water supply
Jul 12, 2026 · Apt BLDG
Close - Safety
Fire escape
Jul 12, 2026 · Apt BLDG
Close - Electric
Power outage
Jul 12, 2026 · Apt BLDG
Close - General
Cooking gas
Jul 12, 2026 · Apt BLDG
Close
Show 40 more ↓
- Unsanitary condition
Garbage/recycling storage
Jul 12, 2026 · Apt BLDG
Close - Elevator
Maintenance
Jul 12, 2026 · Apt BLDG
Close - Electric
No lighting
Jul 12, 2026 · Apt BLDG
Close - Unsanitary condition
Pests
Jul 10, 2026 · Apt 3F
Close - Door/window
Window frame
Jul 8, 2026 · Apt 3F
Close - Unsanitary condition
Mold
Jul 8, 2026 · Apt 3F
Close - Plumbing
Water supply
Jun 13, 2026 · Apt BLDG
Close - Heat/hot water
Apartment only
Jun 13, 2026 · Apt 2K
Close - Plumbing
Water supply
Jun 13, 2026 · Apt 2K
Close - Unsanitary condition
Garbage/recycling storage
Feb 24, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Feb 24, 2026 · Apt BLDG
Close - Heat/hot water
Apartment only
Feb 23, 2026 · Apt 6K
Close - Water leak
Heavy flow
Feb 10, 2026 · Apt 3F
Close - Paint/plaster
Wall
Feb 10, 2026 · Apt 3F
Close - Heat/hot water
Entire building
Feb 10, 2026 · Apt 3F
Close - Heat/hot water
Entire building
Feb 8, 2026 · Apt 6K
Close - Heat/hot water
Apartment only
Feb 8, 2026 · Apt 6K
Close - General
Bell/buzzer/intercom
Feb 8, 2026 · Apt 3F
Close - General
Bell/buzzer/intercom
Feb 8, 2026 · Apt 3F
Close - Heat/hot water
Entire building
Feb 8, 2026 · Apt 3F
Close - Heat/hot water
Entire building
Feb 7, 2026 · Apt 6K
Close - Heat/hot water
Apartment only
Feb 6, 2026 · Apt 6K
Close - Heat/hot water
Entire building
Jan 28, 2026 · Apt 3F
Close - Heat/hot water
Entire building
Jan 26, 2026 · Apt 3F
Close - Heat/hot water
Apartment only
Jan 24, 2026 · Apt 6K
Close - Heat/hot water
Entire building
Jan 19, 2026 · Apt BLDG
Close - Water leak
Slow leak
Jan 16, 2026 · Apt 3F
Close - Heat/hot water
Entire building
Jan 16, 2026 · Apt 3F
Close - Heat/hot water
Apartment only
Jan 15, 2026 · Apt 6E
Close - Heat/hot water
Entire building
Dec 29, 2025 · Apt BLDG
Close - Electric
Wiring
Dec 16, 2025 · Apt 2K
Close - Electric
Outlet/switch
Dec 16, 2025 · Apt 2K
Close - Plumbing
Bathtub/shower
Dec 16, 2025 · Apt 2K
Close - Plumbing
Radiator
Dec 16, 2025 · Apt 2K
Close - Flooring/stairs
Floor
Dec 16, 2025 · Apt 2K
Close - Unsanitary condition
Mold
Dec 16, 2025 · Apt 2K
Close - Unsanitary condition
Mold
Dec 13, 2025 · Apt 5A
Close - Heat/hot water
Apartment only
Dec 11, 2025 · Apt 6E
Close - Heat/hot water
Entire building
Dec 9, 2025 · Apt BLDG
Close - Heat/hot water
Apartment only
Dec 5, 2025 · Apt 6K
Open
Sales history
No recorded sales in our data
Building details
- Building type
- Elevator apartment building (D1)
- Year built
- 1963
- Floors
- 6
- Residential units
- 62
- Building area
- 61,068 ft²
- Lot area
- 24,576 ft²
- Zoning
- R4
- Community board
- 414
- Council district
- 31
- Block / lot
- 15771 / 71
- Assessed value
- $1,775,250
- Landmark / historic district
- No
HPD registration #420450, last renewed Jul 8, 2025.
Questions about 22-04 Collier Avenue
Who owns 22-04 Collier Avenue?
The owner of record in NYC Department of City Planning PLUTO data is 22-04 Collier Ave LLC.
Does 22-04 Collier Avenue have violations?
Yes. NYC HPD has recorded 1,450 housing violations at this property.
Is 22-04 Collier Avenue rent stabilized?
NYC Department of Finance tax bills listed 62 rent-stabilized units here in 2024 (about 100% of its 62 apartments). To confirm a specific apartment, request its rent history from NYS Homes and Community Renewal.
When was 22-04 Collier Avenue built?
City records list 1963 as the year it was built.
How many apartments are in 22-04 Collier Avenue?
It has 62 residential units.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.