roofy

89-34 162 Street

Queens, NY 11432BBL 4-09760-0061Map

Owner of record: 3551 Boston Associates LLC

89-34 162 Street is a hotel built in 2011 in Queens, 11432. The owner of record is 3551 Boston Associates LLC. HPD has recorded 13 housing violations here, most recently on December 10, 2024.

HPD violations
13
DOB violations
26
ECB violations
32
HPD complaints
9

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
Last violation Dec 10, 2024

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 13

  • C

    Provide hot water at all hot water fixtures in the bathroom located at b-room 606, 6th story, 4th b-room from north at east

    Dec 10, 2024 · Apt 606

    Closed — Violation closed
  • C

    Provide hot water at all hot water fixtures in the entire apartment located at apt 611, 6th story, 5th apartment from east at south

    Jul 26, 2024 · Apt 611

    Closed — Violation closed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 27, 2023

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Mar 31, 2023

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 16, 2022

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Mar 10, 2022

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Mar 10, 2022

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Apr 20, 2021

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Apr 20, 2021

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 6, 2019

    Closed — Violation dismissed
Show 3 more ↓
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Oct 29, 2018

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Dec 12, 2017

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 30, 2016

    Closed — Violation dismissed

DOB building violations · 26

  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 8, 2025

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 9b technical report by 2/21/2023

    Feb 22, 2023

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Aug 2, 2022

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Jun 1, 2022

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Feb 2, 2022

    Dob violation - dismissed
  • Residential elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Dec 17, 2021

    Dob violation - dismissed
  • Failure to post energy grade/score none

    Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3

    Dec 1, 2021

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Nov 2, 2021

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Aug 2, 2021

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Jun 2, 2021

    Dob violation - dismissed
Show 16 more ↓
  • Failure to post energy grade/score none

    Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3

    Apr 29, 2021

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Feb 2, 2021

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Nov 2, 2020

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 11, 2020

    Dob violation - resolved
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Aug 2, 2020

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 2, 2020

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Dec 11, 2019

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 17, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 25, 2019

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 7, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 25, 2016

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 28, 2013

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 11, 2013

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 2, 2013

    Dob violation - dismissed

ECB violations · 32

  • Class - 2

    At the time of inspection observed pvc being used on washing machine drainage which is contrary to pc 701.9 plastic pipe. plastic piping and fittings shall not be used., repair and/or replace

    Sep 21, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. observed garage pals obstructing passageway in stairwell. located throughout building, repair and/or replace

    Sep 29, 2025

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. hole penetration, unpermitted plastic access panel. located on the ceiling in gas

    Sep 29, 2025

    Resolve
  • Class - 2

    Found water heater model# d100-199 serial# f8-3225 leaking, maintain boiler; correct violating condition and submit a certificate of correction

    Sep 29, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Observed 2 painted sprinkler heads in the water heater room located at basement. also observed obstructed sprinkler head in the gas meter room located at basement/cellar. as per 102.3 of the plumbing code maint

    Oct 28, 2024 · Penalty $310

    Resolve
  • Class - 2

    Observed painted sprinkler caps throughout building. as per 102.3 of the plumbing code maintenance. installations, both existing and new, and parts thereof shall be maintained in proper operating condition in a

    Oct 28, 2024

    Resolve
  • Class - 2

    I observed in the laundry room and the basement pantry the failure to provide gfci protection for a receptacle installed within 6 feet of a sink. photos taken., install gfc1 protection

    Oct 28, 2024 · Penalty $1,200

    Resolve
  • Class - 1

    I observed the emergency switch and panel for the backup generator installed in the main electrical room as bc 2702.1.7.1 this is not permitted. photos taken.; bc 2702.1.7.1, comply with code

    Oct 28, 2024 · Penalty $2,500

    Resolve
  • Class - 1

    Main brake picking and dropping in the lobby. device oscillating up and down with the door open(cu). must have the capacity plus 125% for the retest. cat one tag expired on 12/27/22. cat five tag missing the in

    May 29, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to submit an acceptable required cycle 9b report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control #918190. remedy: submit acceptable requ

    Apr 11, 2024 · Penalty $3,125

    Resolve
Show 22 more ↓
  • Class - 1

    Only elevator in the building out of service. restored to service immediately. you can contact nycdob at [email protected] for a complete inspection.

    Feb 23, 2024

    Resolve
  • Class - 1

    Door zone restrictor not working tampered with disabled. the car door can be opened outside the landing zone(cu). rusted cables on the machine. brake maintenance tag expired 7/31/22. cat one tag expired. no ent

    Jan 18, 2024 · Penalty $3,125

    Resolve
  • Class - 1

    Door zone restrictor not woking tampered with . car door can be opened outside of the landing zone (cu).

    Jan 25, 2023 · Penalty $1,280

    Resolve
  • Class - 2

    Failure to comply with the commissioners order contained in summons/violation #39006641k issued on 07-29-2019 and to file a certifate of correction pursuant to 28-201.1 and 1rcny 102-01.for:failure to submit a

    Oct 10, 2019 · Penalty $1,250

    Resolve
  • Class - 1

    Cease use 5-a-10 door zone restructor not working this is a safety device to ensure passengers safety repair restrictor and contact nyc dob

    Sep 9, 2019 · Penalty $3,125

    Resolve
  • Class - 1

    Observed at fire department connection no ball drip located., repair and/replace

    Jul 29, 2019 · Penalty $1,250

    Resolve
  • Class - 1

    Failure to perform special inspection duties, as noted: at time of in-spection,steel building erected to 7stories floors 1-7 missing moment connections as shown on amended documents submitted 9/19/11. missing

    Jul 30, 2013 · Penalty $1,600

    Resolve
  • Class - 1

    Work does not conform go approved construction document or approved amendments.as noted:work does not conform to approved construction docu-ment for structural braching at floor #4,exposure #4 stairwells,not in

    Jun 18, 2013 · Penalty $1,000

    Resolve
  • Class - 2

    Sec. 3307.5.1 failure to provide a watch person on duty at construction site. as noted: at time of inspection construction site was closed. i observed all plywood entrance gates were chain & lock from the outsi

    Apr 22, 2013

    Resolve
  • Class - 2

    Sec. 28-105.5 forms filed w/dob's do not have required signatures. re-inspection call ceu at 212-676-9971 as noted: the tr-1 technical reports statement filed w/the dob's don't have required signatures at line

    Apr 19, 2013

    Resolve
  • Class - 1

    Failure to safeguard all persons & property affected by construction operation. as noted: at time of inspection at an active construction site,structural steel building upto 7 stories masonry work inprogress at

    Aug 6, 2012 · Penalty $2,400

    Resolve
  • Class - 1

    Storage of materials during construction. as noted: at time of inspection at an active construction site,structural steel is up to 7 stories,i observed at floor #2 to #5 exposure #1 & #3,material is stored less

    Aug 6, 2012 · Penalty $2,400

    Resolve
  • Class - 2

    Failure to maintain adequate housekeeping per section requirement. as noted: at time of inspection at an active construction site structuralsteel is upto 7 stories,masonry work is in progress observed at floor

    Aug 6, 2012 · Penalty $800

    Resolve
  • Class - 1

    Sec. 3308.1.3 failure to provide horizontal netting during new construction & structural addition. as noted: at time of inspection an a active construction site,structural steel is upto 7 stories,faiure to

    Aug 6, 2012 · Penalty $1,600

    Resolve
  • Class - 1

    Sec. 3308.3 failure to provide vertical safety netting requirements. as noted: at time of inspection at an active construction site,structural steel building upto 7 stories,concrete deck is floor #6 observed at

    Aug 6, 2012 · Penalty $1,600

    Resolve
  • Class - 1

    Failure to institute/maintain safety equipment measure or temporary construction,no guardrails. as noted: at time of inspection at a active construction site,masonry work in progress at floor #6,exposure #4.

    Aug 3, 2012 · Penalty $2,400

    Resolve
  • Class - 2

    Failure to provide approved/accepted plans at job site at time of inspection. noted: at 7 story proposed steel frame bldg under construction, no approved set of structural drawings, steel details or shop notes

    Jun 13, 2012

    Resolve
  • Class - 1

    Sec. 3307.3. overhead protection for walkway and sidewalk. noted: at active construction site, at exp 4, 5th flr unfinished masonry and steel erection to be done has no overhead protection foradjacent property

    Jun 13, 2012 · Penalty $1,600

    Resolve
  • Class - 2

    General contractors registration has expired. noted: n.b. under construction under application #410134224 w/respondent idetified as general contractor on work permit registration has expired on 3-9-12. bldg up

    Apr 17, 2012 · Penalty $250

    Resolve
  • Class - 2

    Failure to safeguard all persons & property affected by construction operations: noted: under job #410134224n.b. proposed 7 story bldg no protection (over head) provided for pedistrian traffic at alleyway

    Apr 13, 2012 · Penalty $1,200

    Resolve
  • Class - 1

    Failure to safeguard all persons & property affected by construction operations. noted: work at premises under permit #420490409 (sheeting &shoring work for support of excavation) observed at exposure #2 walkwa

    Oct 18, 2011 · Penalty $1,200

    Resolve
  • Class - 1

    Noted erecting sheating and shoring appx 13ft deep and appx 350 linear ft long rem: stop all work obtain permit

    Oct 5, 2011 · Penalty $800

    Resolve

Complaints

  • Heat/hot water

    Apartment only

    Jan 24, 2026 · Apt 3B

    Close
  • Heat/hot water

    Entire building

    Sep 23, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 5, 2024 · Apt 606

    Close
  • Heat/hot water

    Entire building

    Jul 25, 2024 · Apt BLDG

    Close
  • Unsanitary condition

    Pests

    Mar 29, 2024 · Apt 404

    Close
  • Unsanitary condition

    Pests

    Mar 29, 2024 · Apt 404

    Close
  • Unsanitary condition

    Mold

    Nov 6, 2023 · Apt 404

    Close
  • Heat/hot water

    Entire building

    Feb 13, 2020 · Apt 710

    Close
  • Unsanitary condition

    Pests

    Jul 18, 2016 · Apt 410

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Hotel (H3)
Year built
2011
Floors
7
Residential units
—
Building area
30,266 ft²
Lot area
6,300 ft²
Zoning
C4-4D
Community board
412
Council district
27
Block / lot
9760 / 61
Assessed value
$4,404,150
Landmark / historic district
No

HPD registration #431885, last renewed Jul 15, 2026.

Questions about 89-34 162 Street

Who owns 89-34 162 Street?

The owner of record in NYC Department of City Planning PLUTO data is 3551 Boston Associates LLC.

Does 89-34 162 Street have violations?

Yes. NYC HPD has recorded 13 housing violations at this property.

Is 89-34 162 Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 89-34 162 Street built?

City records list 2011 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.