roofy

77 Clinton Avenue

Brooklyn, NY 11205BBL 3-01888-0034Map

Owner of record: Clinton Assoc Of Kings INC

77 Clinton Avenue is a school building built in 1968 in Brooklyn, 11205. The owner of record is Clinton Assoc Of Kings INC. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
44
ECB violations
98
HPD complaints
1

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 44

  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 11, 2021

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 11, 2021

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 2, 2020

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 2, 2020

    Dob violation - active
Show 34 more ↓
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 3, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 3, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 9, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 9, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 26, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 26, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 14, 2014

    Dob violation - resolved
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Jan 1, 2012

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 3, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 3, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 12, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 12, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 9, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 9, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 7, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 7, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 9, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 9, 2007

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 28, 2003

    Dob violation - resolved
  • Elevator elevatorrequired

    3p8527

    Apr 3, 2002

    Dob violation - resolved
  • Elevator elevatorrequired

    3p8548

    Apr 3, 2002

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 6, 1998

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 1996

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    May 31, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    3

    Apr 7, 1992

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 7, 1990

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 7, 1990

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 7, 1990

    Dob violation - resolved
  • Elevator elevatoroptional

    1

    Oct 12, 1989

    Dob violation - dismissed

ECB violations · 98

  • Class - 2

    Reissue ecb #35693125x. exit door noted: at(1st fl) cafeteria and gym door not check closing when tested. remedy: repair/replace door.

    Feb 2, 2026 · Penalty $625

    Active
  • Class - 2

    Reissue ecb #35675024h. failure to maintain building in code-compliantmanner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at(1st fl) gym and rm 141 auditorium emer

    Feb 2, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue ecb #35675023x. failure to maintain building in code-compliantmanner. noted: at(1st fl) hallway near elevator/gym and cafeteria doors in disrepair/rackets. remedy: repair and/or replace.

    Feb 2, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. lack of emergency lighting for exits, exit discharges and public corridors corridors per bc 1006.1; 27-543. noted: at(3rd fl) r321 library with no emergenc

    Feb 2, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at 1st fl hallway smoke doors near elevat-gym and cafeteria doors are in disrepair/racked. remedy: repair and/or replace.

    Mar 4, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits. exit discharges and public corridors per bc 1006.1; 27-381. noted: at 1st fl gym emergency lights not working throughout variously

    Mar 4, 2025 · Penalty $1,250

    Active
  • Class - 2

    Exit door not closing noted: at 1st fl cafeteria door check/closer notworking when tested. remedy: repair/replace door.

    Mar 4, 2025 · Penalty $625

    Active
  • Class - 2

    Occupancy contrary to that allowed by the certificate of occupancy or buildings department records: at the time of inspection, observed penthouse on the 6th floor designated as an accessory administrative offic

    Jan 14, 2025 · Penalty $6,250

    Active
  • Class - 2

    Reissue#35267611j failure to maintain building in code-compliant manner:gas meter room has openings which should be closed up with concrete on firestopping.rem:comply with code.

    Feb 1, 2024 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#35650888y.failure to maintain building in code compliant manner.noted at electrical meter room,holes/cracks throughout in the wall and ceiling.remedy:repair and/or replace.

    Jan 25, 2023 · Penalty $1,562

    Resolve
Show 40 more ↓
  • Class - 2

    Reissue#35650887m.failure to maintain building in code compliant manner.no fire stopping per bc712.3;27-345.noted at electrical meter room,holes at various locations with no fire stopping.remedy:provide and mai

    Jan 25, 2023 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc1006.1;27-381.noted at gym at 1st floor 5 emergency lighting found inoperative when tested.

    Jan 25, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35267611j.failure to maintain building in code compliant manner.no fire stopping per bc712.3;27-345.noted at cellar gas meter room,holes around the pipes with no fire stopping.remedy:provide/maintain fi

    Jan 25, 2023 · Penalty $3,125

    Resolve
  • Class - 1

    Class 1 item: provide dlm as now required by code. class 2 items: replace gibs where needed. secure gibs where needed. provide designated lobby braille tags. inoperative car phone. main line can be opened when

    Mar 22, 2022 · Penalty $6,250

    Active
  • Class - 1

    Class 1 item: provide dlm as now required by code. class 2 items: replace gibs where needed. secure gibs where needed. provide designated lobby braille tags. unreadable main line fuses.

    Mar 22, 2022 · Penalty $6,250

    Active
  • Class - 2

    Reissued #35553722j failure to maintain building in code compliant manner:no fire stopping per bc 712.3; 27-345.noted:observed throughout cellar's electrical rooom holes/openings in ceiling with no fire stoppin

    Mar 18, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Reissued #35553721h failure to maintain building in code compliant manner:noted:observed holes & cracks throughout electrical meter room at various locations.remedy:repair and/or replace

    Mar 18, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued #35553720x failure to maintain building in code compliant manner:use of prohibited door and/or hardware per bc 1008; 27-371(j) noted:observed throughout first floor exterior exit door have kick stop ha

    Mar 18, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:noted:observed at first floor-fire proof self closing door at stair "b" does not self close due to defective door closing hardware door stays wide open.reme

    Mar 18, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue35496035j failure to maintain bldg in codecompliant manner:use of prohibited door &/or hardware per bc1008.1.8;27-371j.noted:observedon 1fl,all doors have kickstop installed on doors.remove illegal kicks

    Apr 20, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35496030k failure to maintain bldg in codecompliant manner:no fire stopping per bc712.3;27-345.noted:@cellar level electrical rm are holes in ceiling@various locations.provide/maintain firestopping.

    Apr 20, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue35496032y failure to maintain bldg in codecompliant manner.noted:@cellar electrical rm has cracks&holes thruout.repair cracks&holes.

    Apr 20, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35422185n failure to maintain bldg in code compliant manner. nofire stopping for bc 1006.1;27-542. noted: at cellar,gas & electrical room holes in the walls w/no fire stopping. remedy: provide/maintain

    May 29, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#35422184l failure to maintain bldg in code compliant manner. noted: at cellar,at gas & electrical room,illegal storage of misc items. remedy: comply w/notice of violation.

    May 29, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35422180y emergency signs at elevator call stations missing. noted: at all level,elevator call stations,no emergency signs. remedy: install signs.

    May 29, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35422181x exit door not self closing. noted: at 3rd fl stair b2nd fl stair b & 1st fl cafeteria exit doors w/broken door closers. remedy: repair/replace door.

    May 29, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35422183j at cellar,at gas & electrical room,walls w/cracks,holes & water penetration damage. remedy: make necessary repairs.

    May 29, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. use of prohibited door & or hardware per bc 1008.1.8;27-371(j). noted: at main exit/entry doors,all doors are equipped w/kick down door holders. remedy: remove

    May 29, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381 noted: at 1st flr gym and cafeteria emergency lights are no operational

    May 1, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: at cellar gas and electric meter rooms storage of various materials/items box es, equipment, chairs etc. rmdy: comply with code.

    May 1, 2019

    Resolve
  • Class - 2

    Exit door not self closing noted: at 3rd fl, stair b 2nd fl stair b 1st fl cafeteria self closers in disrepair/non operational. rmdy: repair/replace door.

    May 1, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. no fire stopping per bc 1006.1; 27-542 noted: at cellar gas and electric meter rooms fire stopping missing/none in various locations throughout walls and

    May 1, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: at cellar gas, electric meter rooms and storage area ceilings/walls with cracks/holes water penetration/damage. rmdy: repair and/or replace.

    May 1, 2019

    Resolve
  • Class - 2

    Emergency signs at elevator call stations missing defective or non compiant with section requirements. noted: at all levels elevator areas/stations no emergency signage present for emergency staircase lo

    May 1, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner noted: at roof level seciton of roof covering apprx 12'x 20' missing. allowing water penetration into room 603 rendering it unuseable. active leak present

    Oct 3, 2018

    Resolve
  • Class - 2

    Reissue of nov 35267617k. failure to maintain building in code compliant manner. noteda; at 3rd floor, corridor area, adjacent to stair c, missing glass window for doors of boys bathroom and locker room. rmdy:

    Oct 3, 2018

    Resolve
  • Class - 2

    Reissue of nov 35267611j. failure to maintain bldg in code compliant manner. noted: at cellar level gas meter room and storage area ceilingcracks,holes and water damage. rmdy: repair and/or replace.

    Oct 3, 2018

    Resolve
  • Class - 2

    20181001

    Aug 15, 2018

    Resolve
  • Class - 2

    20181001

    Aug 15, 2018

    Resolve
  • Class - 2

    Provide "designated lobby" braille tags, provide missing braille tags, adjust braille tags to ada code height where needed, provide missing handrail, provide guard for sump pump, replace hoistway door gibs wher

    Aug 15, 2018

    Resolve
  • Class - 2

    Unguarded sump pump, provide "designated lobby braille tags, peplace hoistway door gibs where neeeded, secure hoistway door gibs where needed, provide machine room ventilation per k3, unreadable main line fuses

    Aug 15, 2018

    Resolve
  • Class - 2

    Re-issue# 35195384z, failure to maintain bldg in code compliant manner. noted: @ cellar level gas meter room & storage area ceiling cracks holes & water damage in visible some type of drilling was done above th

    Jun 9, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: @ cellar level, gas room & electrical room, combustible material storage inside the rooms like paper rools, wood frame, paint supplies & ladders. rem: c

    Jun 9, 2017

    Resolve
  • Class - 2

    Exit door not self closing. noted: doors have defective in the top hinge & not close completely @ the following locations, @ 1st flr gym area & exit stairway #a & @ 2nd flr, exit staircase b & @ 3rd flr, exit s

    Jun 9, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: missing stall doors @ 3rd flr, boys bathroom & @ 1st flr, girls bathroom. rem: comply w/ code/ install doors.

    Jun 9, 2017

    Resolve
  • Class - 2

    Emergency signs @ elevator call stations missing, defective or non-compliant w/ section requirement. noted: @ 1st,2nd,3rd,4th,5th,6th flrs, the emergency signs @ the elevator call stations are missing. rem: com

    Jun 9, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: @ 4th flr, boys bathroom, broken tap of handicap washbasin. also, @ 1st flr, boys bathrooms missing handicap washbasin. rem: comply w/ code/ install or

    Jun 9, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: @ 1st flr, gym area & locker room, more than 8 emergency lights are broken & not working. rem: comply w/ code/ install new emergency lights.

    Jun 9, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: @ 3rd flr, corridor area adjacent to stair c, missing glass window for doors of boy's bathroom & locker room. rem: comply w/ code/ install a new glasser

    Jun 9, 2017

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.at cellar gas meter room and storage are ceiling cracks holes and water damage is visible some type of drilling was done above these rooms and not fixed

    Oct 27, 2016

    Resolve

Complaints

  • Plumbing

    Water supply

    Jul 21, 2026 · Apt BLDG

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1968
Floors
5
Residential units
—
Building area
112,452 ft²
Lot area
42,000 ft²
Zoning
R6B
Community board
302
Council district
35
Block / lot
1888 / 34
Assessed value
$3,734,100
Landmark / historic district
No

Questions about 77 Clinton Avenue

Who owns 77 Clinton Avenue?

The owner of record in NYC Department of City Planning PLUTO data is Clinton Assoc Of Kings INC.

Does 77 Clinton Avenue have violations?

NYC HPD has no housing violations on record for this property.