roofy

2911 Barnes Avenue

Bronx, NY 10467BBL 2-04549-0001Map

Owner of record: Parkash 2911 LLC

2911 Barnes Avenue is an elevator apartment building built in 1931 in Bronx, 10467. It has 96 residential units across 6 floors. The owner of record is Parkash 2911 LLC. HPD has recorded 2,196 housing violations here, most recently on October 5, 2026. 13 of the 50 most recent violations are still open. City tax records listed 96 rent-stabilized apartments here in 2024.

HPD violations
2,196
DOB violations
24
ECB violations
49
HPD complaints
1,195

What to know

Concern
5 open Class C

Immediately hazardous issues among recent violations are still open.

Watch
Last violation Oct 5, 2026

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

Rent-stabilized units in 2024
96
About 100% of the building's 96 apartments

Counts come from owners' rent-stabilization filings shown on NYC Department of Finance tax bills, as extracted by JustFix. They tell you a building has stabilized apartments, not which ones.

Stabilized units by tax-bill year

Think your apartment is stabilized? Request its rent history from HCR (free), then check your renewal with the renewal calculator.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 2,196

  • C

    Provide hot water at all hot water fixtures in the entire apartment located at apt 5f, 6th story, 1st apartment from north at east

    Oct 5, 2026 · Apt 5F

    Open — Civ14 mailed
  • C

    Provide hot water at all hot water fixtures in the entire apartment located at apt 4b, 2nd story, 2nd apartment from south at west

    Oct 5, 2026 · Apt 4B

    Open — Civ14 mailed
  • C

    Provide ready access to buildings heating system door locked at boiler room

    Oct 5, 2026

    Open — Violation will be reinspected
  • C

    Provide ready access to buildings heating system door locked at boiler room

    Oct 5, 2026

    Open — Violation will be reinspected
  • C

    Replace or repair the self-closing doors that is missing or defective hinges at fire door leading to south section at public hall, 2nd story, section ''south''

    Sep 28, 2026

    Closed — Violation closed
  • C

    Install the missing or repair/replace the defective window guard(s) in accordance with the specifications of the new york city health code section 24 rcny chapter 12. wg to install = 3, wg to replace = 0, wg to repair = 0 in the entire apartment located at apt 4b, 2nd story, 8th apartment from south at west , section ''north''

    Sep 28, 2026 · Apt 4B

    Closed — Violation closed
  • C

    Provide ready access to buildings heating system door locked at boiler room

    Sep 28, 2026

    Closed — Violation closed
  • C

    Provide hot water at all hot water fixtures in the entire apartment located at apt 4b, 2nd story, 8th apartment from south at west , section ''north''

    Sep 28, 2026 · Apt 4B

    Open — First no access to re- inspect violation
  • B

    Properly repair with similar material the broken or defective caulking between the counter top and the wall at east in the kitchen located at apt 8e, 5th story, 1st apartment from east at south , section ''center''

    Sep 14, 2026 · Apt 8E

    Open — First no access to re- inspect violation
  • B

    Properly repair or replace the broken or defective faucet at bathtub in the bathroom located at apt 8e, 5th story, 1st apartment from east at south , section ''center''

    Sep 14, 2026 · Apt 8E

    Open — First no access to re- inspect violation
Show 40 more ↓
  • C

    Properly repair the source and abate the evidence of a water leak at ceiling in the 3rd room from north located at apt 8e, 5th story, 1st apartment from east at south , section ''center''

    Sep 14, 2026 · Apt 8E

    Closed — Violation closed
  • C

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling in the 3rd room from north located at apt 8e, 5th story, 1st apartment from east at south , section ''center''

    Sep 14, 2026 · Apt 8E

    Closed — Violation closed
  • C

    Properly repair or replace the broken or defective lock sash at fire escape window at west wall in the kitchen located at apt 15b, 2nd story, 2nd apartment from south at west

    Sep 4, 2026 · Apt 15B

    Closed — Violation closed
  • C

    Abate the infestation consisting of roaches in the entire apartment located at apt 15b, 2nd story, 2nd apartment from south at west

    Sep 4, 2026 · Apt 15B

    Closed — Violation closed
  • C

    Abate the nuisance consisting of evidence of rats and all underlying causes creating the pest infestations, by using integrated pest management (ipm), eliminate all burrow entry and passageways, pest nests, holes, gaps or cracks in walls, ceilings, floors, fixing leaks and managing garbage in public areas. evidence found at rat droppings observed in the entire apartment located at apt 15b, 2nd story, 2nd apartment from south at west

    Sep 4, 2026 · Apt 15B

    Closed — Violation closed
  • B

    Properly repair or replace the broken or defective latch and assemblys at door at compactor closet, 1st story

    Aug 21, 2026

    Open — Not complied with
  • C

    Replace or repair the self-closing doors that is missing or defective latch at door at compactor closet, 1st story

    Aug 21, 2026

    Closed — Violation closed
  • A

    Remove the accumulation of refuse and/or rubbish and maintain in a clean condition the garbage. at compactor closet, 5th story

    Aug 13, 2026

    Open — First no access to re- inspect violation
  • C

    Replace or repair the self-closing doors that is missing or defective hinges at door in the entrance located at apt 15b, 2nd story, 2nd apartment from south at west , section ''south ''

    Aug 5, 2026 · Apt 15B

    Closed — Violation closed
  • C

    Replace or repair the self-closing doors that is missing or defective hinges at fire door south section at public hall, 2nd story

    Aug 5, 2026

    Closed — Violation closed
  • C

    Replace or repair the self-closing doors that is missing or defective latch at compactor room closet door, north section at public hall, 2nd story

    Aug 5, 2026

    Closed — Violation closed
  • B

    And dept. rules and regulations. remove the encumbrance obstructing egress from fire escapes consisting of household items at 2nd fire escape from south at east exterior wall at fire escape, 3rd story

    Aug 5, 2026

    Closed — Violation closed
  • B

    File certification of satisfactory installation of smoke detecting device in accordance with h.p.d. rules and regulations. in the entire apartment located at apt 2a, 1st story

    Aug 5, 2026 · Apt 2A

    Open — First no access to re- inspect violation
  • B

    Repair, replace or provide an approved and operational carbon monoxide detecting device, installed in accordance with applicable law and rules missing in the entire apartment located at apt 2a, 1st story

    Aug 5, 2026 · Apt 2A

    Open — First no access to re- inspect violation
  • B

    Repair, replace or provide an approved and operational smoke detecting device, installed in accordance with department of buildings rules and regulations defective in the entire apartment located at apt 14e, 5th story

    Aug 5, 2026 · Apt 14E

    Open — First no access to re- inspect violation
  • B

    Repair, replace or provide an approved and operational carbon monoxide detecting device, installed in accordance with applicable law and rules defective in the entire apartment located at apt 14e, 5th story

    Aug 5, 2026 · Apt 14E

    Open — First no access to re- inspect violation
  • C

    Abate the infestation consisting of mice in the entire apartment located at apt 14e, 5th story

    Aug 5, 2026 · Apt 14E

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling and walls in the closet in the private hallway located at apt 3e, 5th story, 7th apartment from south at west

    Jul 20, 2026 · Apt 3E

    Closed — Violation closed
  • C

    Properly repair or replace the broken or defective exterior glass pane at upper sash window in the kitchen located at apt 2a, 1st story, 2nd apartment from south at west

    Jul 20, 2026 · Apt 2A

    Closed — Violation closed
  • B

    Properly repair with similar material the broken or defective ceramic tiles at east wall in the bathroom located at apt 2a, 1st story, 2nd apartment from south at west

    Jul 20, 2026 · Apt 2A

    Closed — Violation closed
  • B

    Properly repair with similar material the broken or defective ceramic floor tiles in the bathroom located at apt 2a, 1st story, 2nd apartment from south at west

    Jul 20, 2026 · Apt 2A

    Closed — Violation closed
  • B

    § 27-2033.3(e) correct failure to maintain required records regarding internet capable temperature reporting devices and submit such records to the department upon request. data requested for the period of april 2026

    Jul 9, 2026

    Closed — Violation closed
  • B

    § 27-2033.3(e) correct failure to maintain required records regarding internet capable temperature reporting devices and submit such records to the department upon request. data requested for the period of may 2026

    Jul 9, 2026

    Closed — Violation closed
  • B

    Properly repair with similar material the broken or defective porcelain enamel finish by method of reglazing at bathtub. in the bathroom located at apt 3e, 5th story, 7th apartment from south at west

    Jul 8, 2026 · Apt 3E

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color the west wall in the kitchen located at apt 3e, 5th story, 7th apartment from south at west

    Jul 8, 2026 · Apt 3E

    Closed — Violation closed
  • B

    Properly repair with similar material the broken or defective caulking around bathtub in the bathroom located at apt 3e, 5th story, 7th apartment from south at west

    Jul 8, 2026 · Apt 3E

    Closed — Violation closed
  • B

    Properly secure the loose upper cabinets at west wall in the kitchen located at apt 3e, 5th story, 7th apartment from south at west

    Jul 8, 2026 · Apt 3E

    Closed — Violation closed
  • C

    M/d law abate the nuisance consisting of discarded refrigerators with door intact at public hall, 1st story

    Jul 8, 2026

    Closed — Violation closed
  • C

    Abate the infestation consisting of mice in the entire apartment located at apt 9c, 3rd story, 5th apartment from north at east

    Jul 8, 2026 · Apt 9C

    Closed — Violation closed
  • C

    Abate the infestation consisting of roaches in the entire apartment located at apt 9c, 3rd story, 5th apartment from north at east

    Jul 8, 2026 · Apt 9C

    Closed — Violation closed
  • B

    Properly repair with similar material the broken or defective caulking around bathtub in the bathroom located at apt 9c, 3rd story, 5th apartment from north at east

    Jul 8, 2026 · Apt 9C

    Closed — Violation closed
  • A

    Reset, so as to secure a proper and tight connection, the water closet bowl ... in the bathroom located at apt 3e, 5th story, 7th apartment from south at west

    Jul 8, 2026 · Apt 3E

    Closed — Violation closed
  • B

    Properly repair the source and abate the evidence of a water leak at ceiling and west wall in the kitchen located at apt 3e, 5th story, 7th apartment from south at west

    Jul 8, 2026 · Apt 3E

    Closed — Violation closed
  • B

    Repair, replace or provide an approved and operational smoke detecting device, installed in accordance with department of buildings rules and regulations missing in the entire apartment located at apt 3d, 4th story, 2nd apartment from south at west

    Jun 27, 2026 · Apt 3D

    Closed — Violation closed
  • B

    Repair, replace or provide an approved and operational carbon monoxide detecting device, installed in accordance with applicable law and rules missing in the entire apartment located at apt 3d, 4th story, 2nd apartment from south at west

    Jun 27, 2026 · Apt 3D

    Closed — Violation closed
  • B

    Properly repair the source and abate the evidence of a water leak at ceiling in the bathroom located at apt 3d, 4th story, 2nd apartment from south at west

    Jun 27, 2026 · Apt 3D

    Closed — Violation closed
  • B

    Repair the leaky and/or defective faucets at bathtub in the bathroom located at apt 8e, 5th story, 1st apartment from north at east

    Jun 27, 2026 · Apt 8E

    Closed — Violation closed
  • C

    Abate the infestation consisting of mice in the entire apartment located at apt 3d, 4th story, 2nd apartment from south at west

    Jun 27, 2026 · Apt 3D

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling in the bathroom located at apt 3d, 4th story, 2nd apartment from south at west

    Jun 27, 2026 · Apt 3D

    Closed — Violation closed
  • B

    Properly repair or replace the broken or defective shower body at bathtub in the bathroom located at apt 1c, 3rd story, 2nd apartment from south at west

    Jun 27, 2026 · Apt 1C

    Closed — Violation closed

DOB building violations · 24

  • Construction other optional

    Structure rendered non-complaint. at time of inspection observed exposure#3 rear shared court yard which is the fire escape pathway obstructed by fallen tree limbsand other debris due to fire at 2910 wallace ave.

    Jan 11, 2025

    Dob violation - dismissed
  • Construction other optional

    Emergency work order. at exposure 1 east elevation step crack on brick (mk) masonry at top floor level at several location. no safety measure in place. remedy: immediately take & provide adequate safety measures (side walk shed) to secure public safety

    Nov 26, 2024

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 1, 2021

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Apr 14, 2021

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 20, 2021

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 28, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 24, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 3, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 2, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 13, 2013

    Dob violation - resolved
Show 14 more ↓
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Jun 3, 2013

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 13, 2012

    Dob violation - resolved
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 3, 2012

    Dob violation - active
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Jan 1, 2012

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 1, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 24, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 20, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 30, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 14, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 31, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 13, 2003

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 22, 1993

    Vp*-violation unserved ecb- dismissed
  • Elevator elevatorrequired

    (75) lock motor room (76) repair safety edge

    Jul 24, 1989

    Dob violation - resolved
  • Elevator elevatorrequired

    51)install 6x16motor room 52)install guard main machine 53)file application for new cab

    Jan 5, 1989

    Dob violation - resolved

ECB violations · 49

  • Class - 1

    Failure to comply with commissioner's orders.noted as per inspection and document review.it was revealed that the property owner did not comply with ecb violation#35716688z dated on 03/16/2025 for failure to pr

    Nov 14, 2025

    Resolve
  • Class - 1

    Failure to maintain exterior building facade and appurtenances.noted:observed cracked masonry at multiple locations at exp 1(e.elev),exp 2(s.elev).also observed deteriorated mortar at all exposures.these condit

    Nov 14, 2025 · Penalty $7,500

    Active
  • Class - 2

    Class 2:failure to maintain building in code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon inspection,emergency phone in elevator inoprative,rapair/connect phone to 24hrs emergency

    Aug 6, 2025 · Penalty $3,125

    Active
  • Class - 2

    At 5:05am i observed lights defective exp#1and4 creates dark conditions leads slip,trip,falls for tenants. no preventive measures for criminal activity as per bc3307.6.4.8 states sws shall illuminate entire len

    Aug 4, 2025 · Penalty $2,400

    Resolve
  • Class - 2

    Failure to comply with the commissioners orders to file a certificate of correction with the dob, for violation#35694035r, file a certificate of correction; file for a certificate of correction

    Jul 28, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to comply with the commissioners orders to file a certificate of correction with the dob for violation#35687039z, file a certificate of correction; file a certificate of correction.

    Jul 28, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to comply with the commissioners orders to file a certificate of correction with the dob, for violation#35717067k, file a certificate of correction; file a certificate of correction

    Jul 28, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to comply with the commissioners orders to file a certificate of correction with the dob for violation#35716687r, file a certificate of correction; file a certificate of correction

    Jul 28, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to compýly with the commissioners orders to file a certificate of correction with the dob for violation#35689624z, file a certificate of correction; file a certificate of correction

    Jul 28, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to compýly with the commissioners orders to file a certificate of correction with the dob for violation#35689256y, file a certificate of correction; file a certificate of correction

    Jul 28, 2025 · Penalty $1,250

    Active
Show 39 more ↓
  • Class - 2

    Failure to maintain building in code compliant manner. class 2 items: in-car communication inoperative, repair. provide a city id device number in the car. provide floor numbering with braille tags on all floor

    Jul 25, 2025 · Penalty $625

    Active
  • Class - 1

    Failure to maintain building exterior wall(s) or appurtenances. note: at the time of inspection observed (1) at expo #1, 2 and 4 east, southand north elevation crack/step crack at several location crack/step cr

    Jul 21, 2025 · Penalty $5,000

    Active
  • Class - 1

    Failure to maintain building exterior facade and/or appurtenances in acode-compliant manner. at time of inspection it was observed throughout the building spalling/missing/damaged mortar joints around parapet w

    Jun 27, 2025 · Penalty $5,000

    Active
  • Class - 1

    Cease use item: door zone restrictor inoperative. this is a safety feature which ensures passenger safety. remedy: to restore service, email the d.o.b. [email protected]. for a reinspection. class 2 items:

    Apr 10, 2025 · Penalty $1,250

    Active
  • Class - 1

    Failure to maintain exterior building facade and appurtenances. noted:obdserved cracked masonry at multiple locations at exp 1(e. elev), expexp 2(s. elev) and exp 3(w. elev). also observed inadequate ac units a

    Mar 26, 2025 · Penalty $7,500

    Active
  • Class - 1

    Failure to provide unobstructed exit passageway.-noted: observed at exposure 1(e. elev) objects like clothing, bath towels, and curtain are on the fire escape at the third floor level. remedy: remove obstructio

    Mar 26, 2025 · Penalty $625

    Resolve
  • Class - 1

    I observed in apartment 10a, 3a, 4a, 14f, 15d, and 9c the improper use of electrical extension cords to permanently provide power for appliances, electronic, receptacles, and lighting due to non working outlets

    Mar 12, 2025

    Resolve
  • Class - 1

    Observed electrical work done without a permit on file.in 14f a new el panel, apt 9c & 1d new light fixtures., obtain permit; obtain electrical permit

    Mar 12, 2025 · Penalty $800

    Resolve
  • Class - 1

    Apt 10a exposed wiring at the el panel, outlets with open ground, apt 3a outlets with open ground and circuits/devices not working,15d outlets not working, outlets open ground & reversed polarity, exposed wirin

    Mar 12, 2025 · Penalty $1,600

    Resolve
  • Class - 2

    Observed 540am exp1,2 defective lights dark areas creates hazard for pedestrians slip,trip hazard,no preventive measures criminial mischief.bc3307.6.4.8 notes sws shall illuminate all times and uniformly distri

    Feb 14, 2025 · Penalty $2,400

    Resolve
  • Class - 1

    The only elevator in building (or section of building) out of service. upon inspection, the device is found to be out-of-service creating a hazardous condition as per 1rcny 11-02. remedy: restore to service imm

    Feb 5, 2025 · Penalty $1,250

    Active
  • Class - 2

    Found a rocmill mp175 boiler combustion fan not working and sail switch not working properly/iron body pump on water side/saftey valve missing body drain/correct all violating condition/submit certificate of co

    Jan 29, 2025

    Resolve
  • Class - 1

    Failure to maintain exterior building facade and appurtenances. note: at time of inspection observed broken window at exp #2 ground. 4th floor at exp #2 observed multiple areas of spalling mortar joints. mortar

    Jan 24, 2025 · Penalty $2,500

    Active
  • Class - 1

    Failure to provide unobstructed exit passageway. note: at time of isnpection observed on 3rd level of fire escape of exp #1 objects on fire escape blocking egress and potential to cause serious harm to tenants

    Jan 24, 2025 · Penalty $1,250

    Active
  • Class - 1

    Failure to maintain building exterior wall(s)or appurtenances.note:at the time of inspection observed at expo#1 east elevation on step crackon brick masonry at parapet and building top floor level at several lo

    Nov 26, 2024 · Penalty $2,500

    Active
  • Class - 2

    Observed on the fifth floor in apartment 10 e in the kitchen behind stove no handle on appliance valve for stove also having defective stove. refer to fgh section 409.5, repair and/or replace

    Aug 4, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to certify: failure to comply with the commissioner's order to file a certificate of correction with the department of buildings for nov 39031008j. remedy: file certificate of correction.

    Aug 1, 2023 · Penalty $1,250

    Active
  • Class - 2

    Failure to certify: failure to comply with the commissioner's order to file a certificate of correction with the department of buildings for nov 39036229x. remedy: file certificate of correction.

    Aug 1, 2023

    Resolve
  • Class - 2

    Failure to certify: failure to comply with the commissioner's order to file a certificate of correction with the department of buildings for nov 39035161y. remedy: file certificate of correction.

    Aug 1, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to certify: failure to comply with the commissioner's order to file a certificate of correction with the department of buildings for nov 39041609y. remedy: file certificate of correction.

    Aug 1, 2023 · Penalty $1,250

    Active
  • Class - 2

    In car communication inoperative, repair. garbage and water in the pit, remove water and clean the pit. floor numbers on inside of hoist way doors missing, provide. top of car dirty, clean. motor room door miss

    Jun 23, 2023 · Penalty $625

    Active
  • Class - 2

    Phone not working, provide keys for motor room

    Dec 5, 2021

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as per 3.10.12 of appendix k3 of the 2014 nycbc. remedy; install dlm and perform and file test with nycdob. emergency phone inoperative, repair.

    May 24, 2021 · Penalty $1,250

    Active
  • Class - 2

    Class 2 violation issued / obtain certificate of compliance on installation of dlm work in controller

    Feb 13, 2021 · Penalty $625

    Resolve
  • Class - 1

    Class 1 : no door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application, install dlm

    Jan 20, 2021 · Penalty $1,250

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as per 3.10.12 of appendix k3 of the 2014 nycbc. remedy; install dlm and perform and file test with nycdob. phone inoperative. no access to pit.

    Oct 26, 2020 · Penalty $1,250

    Active
  • Class - 1

    Cu-2l10,cu1l10,70o2,57m7. 2l10/1l10- defective repair

    Mar 22, 2017 · Penalty $1,000

    Resolve
  • Class - 1

    Failure to maintain bldg walls appurtenance defect noted at north sideyard of bldg along williams bridge road and barnes ave iron fence w/ brick posts is in disrepair and in danger of collapsing into sidewalk b

    Mar 21, 2012 · Penalty $1,000

    Resolve
  • Non-hazardous

    Cease use. 70l10/44b7/85bb5/86bb5. c.u. item - car safety inoperative, defective, repair for re-insp. call 212-566-5544. 44b- provide seal for governor pull through.

    Mar 15, 2006 · Penalty $500

    Resolve
  • Non-hazardous

    14m07/15m7/13i11/39t15/12x11/66o2/38o2 12 top of car.

    Oct 3, 2005 · Penalty $180

    Resolve
  • Non-hazardous

    74b10/60o02/15m07/60t07 74-provide proper clearance cwt.to buffer,15 post cert as per rule 27-1004a or 27-1004b,60-provide co name.

    Aug 28, 2003 · Penalty $350

    Resolve
  • Non-hazardous

    35p07-74l11-20l11-57o02. 74 repair in car communication 20-repair up call on 2 floor.

    Aug 7, 2002 · Penalty $180

    Resolve
  • Non-hazardous

    75u05-5702-03002-09h10 car top dirty & full of oil rags.

    Nov 15, 2000 · Penalty $350

    Resolve
  • Non-hazardous

    5j11,10l11,15l11,16h12,17a12,22o2,23u16,22l6,25q3,35y2,37g12,51b7,53x11,73o2,57o2,75u5,3m7,14m7.5j-too much gap to post10-sticks 2,4,+5.15-not self closing bsmt fl.16-b,4+6fl.17-must be wire glass,car.22-car to

    Nov 3, 2000 · Penalty $350

    Resolve
  • Non-hazardous

    22q 03o 07q 50o 50y 57o 03 0 02 clean car top 07 q 03 provide safety edge box.

    May 21, 1999 · Penalty $180

    Resolve
  • Non-hazardous

    22d74m05a17a23u08i17i57o18o48b03o38p #74 m no capacity plate #05 a carvision panel not wire glass #08 car saddle #48 insufficient run by #03top of car.

    Nov 21, 1997 · Penalty $350

    Resolve
  • Non-hazardous

    14m,22d,35p,74m,74m,74o,(35)provide access to motor room (74)replace missing hand rail in elevator (74)replace missing splice box covers where necessary(74)clean car top.

    Feb 22, 1993

    Resolve
  • Non-hazardous

    35o,57o,13m,15x,58h, 15repair vision glass were needed. 58eliminate excessive ply in car rails & gide shoes.

    Jun 25, 1991

    Resolve
  • Hazardous

    Failure to maintain exterior of bldg brickwork at front south n/wing above 5sty window is loose, defective and in need of repair. remedy: repair and replace all defective and loose brickwork at front south.

    Mar 31, 1990 · Penalty $140

    Resolve

Complaints

  • Heat/hot water

    Apartment only

    Oct 8, 2026 · Apt 4B

    Close
  • Heat/hot water

    Apartment only

    Oct 6, 2026 · Apt 4B

    Close
  • Heat/hot water

    Apartment only

    Oct 4, 2026 · Apt 7C

    Close
  • Heat/hot water

    Apartment only

    Oct 3, 2026 · Apt 4B

    Close
  • Heat/hot water

    Apartment only

    Oct 1, 2026 · Apt 4B

    Close
  • General

    Cabinet

    Sep 28, 2026 · Apt 5C

    Close
  • Door/window

    Window frame

    Sep 28, 2026 · Apt 5C

    Close
  • Unsanitary condition

    Mold

    Sep 28, 2026 · Apt 5C

    Close
  • Heat/hot water

    Apartment only

    Sep 27, 2026 · Apt 4B

    Close
  • Plumbing

    Bathtub/shower

    Sep 9, 2026 · Apt 8E

    Close
Show 40 more ↓
  • Water leak

    Heavy flow

    Sep 9, 2026 · Apt 8E

    Close
  • Paint/plaster

    Ceiling

    Sep 9, 2026 · Apt 8E

    Close
  • Appliance

    Refrigerator

    Aug 31, 2026 · Apt 10B

    Close
  • Water leak

    Heavy flow

    Aug 27, 2026 · Apt 10A

    Close
  • Appliance

    Refrigerator

    Aug 20, 2026 · Apt 2F

    Close
  • Appliance

    Refrigerator

    Aug 10, 2026 · Apt 10B

    Close
  • Unsanitary condition

    Garbage/recycling storage

    Jul 18, 2026 · Apt BLDG

    Close
  • Unsanitary condition

    Pests

    Jul 15, 2026 · Apt 14E

    Close
  • Paint/plaster

    Ceiling

    Jul 15, 2026 · Apt 14E

    Close
  • Appliance

    Electric/gas range

    Jul 15, 2026 · Apt 14E

    Close
  • Plumbing

    Basin/sink

    Jul 15, 2026 · Apt 14E

    Close
  • Plumbing

    Radiator

    Jul 15, 2026 · Apt 14E

    Close
  • General

    Bell/buzzer/intercom

    Jul 15, 2026 · Apt 14E

    Close
  • Paint/plaster

    Wall

    Jul 15, 2026 · Apt 14E

    Close
  • Unsanitary condition

    Pests

    Jul 15, 2026 · Apt 14E

    Close
  • Electric

    Power outage

    Jul 8, 2026 · Apt 2A

    Close
  • Appliance

    Refrigerator

    Jul 8, 2026 · Apt 3A

    Close
  • Electric

    Power outage

    Jul 7, 2026 · Apt 3E

    Close
  • Electric

    No lighting

    Jul 4, 2026 · Apt 11E

    Close
  • Electric

    Outlet/switch

    Jul 4, 2026 · Apt 3E

    Close
  • Electric

    Wiring

    Jul 4, 2026 · Apt 3E

    Close
  • Electric

    Power outage

    Jul 2, 2026 · Apt 12C

    Close
  • Door/window

    Door

    Jul 2, 2026 · Apt 12C

    Close
  • Plumbing

    Toilet

    Jun 29, 2026 · Apt 3E

    Close
  • Paint/plaster

    Ceiling

    Jun 29, 2026 · Apt 3E

    Close
  • Paint/plaster

    Wall

    Jun 29, 2026 · Apt 3E

    Close
  • Water leak

    Slow leak

    Jun 29, 2026 · Apt 3E

    Close
  • Plumbing

    Bathtub/shower

    Jun 29, 2026 · Apt 3E

    Close
  • General

    Cabinet

    Jun 29, 2026 · Apt 3E

    Close
  • Flooring/stairs

    Floor

    Jun 29, 2026 · Apt 3E

    Close
  • Plumbing

    Bathtub/shower

    Jun 29, 2026 · Apt 9C

    Close
  • Flooring/stairs

    Floor

    Jun 29, 2026 · Apt 9C

    Close
  • Unsanitary condition

    Garbage/recycling storage

    Jun 12, 2026 · Apt BLDG

    Close
  • Unsanitary condition

    Pests

    Jun 12, 2026 · Apt 4C

    Close
  • Water leak

    Heavy flow

    Jun 12, 2026 · Apt 4C

    Close
  • Paint/plaster

    Ceiling

    May 18, 2026 · Apt 1A

    Close
  • Water leak

    Heavy flow

    May 18, 2026 · Apt 1A

    Close
  • Unsanitary condition

    Mold

    May 18, 2026 · Apt 1A

    Close
  • Paint/plaster

    Ceiling

    May 18, 2026 · Apt 1A

    Close
  • Heat/hot water

    Apartment only

    Apr 26, 2026 · Apt 4B

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Elevator apartment building (D1)
Year built
1931
Floors
6
Residential units
96
Building area
113,018 ft²
Lot area
26,850 ft²
Zoning
R6
Community board
211
Council district
12
Block / lot
4549 / 1
Assessed value
$2,115,900
Landmark / historic district
No

HPD registration #205744, last renewed Jul 6, 2026.

Questions about 2911 Barnes Avenue

Who owns 2911 Barnes Avenue?

The owner of record in NYC Department of City Planning PLUTO data is Parkash 2911 LLC.

Does 2911 Barnes Avenue have violations?

Yes. NYC HPD has recorded 2,196 housing violations at this property.

Is 2911 Barnes Avenue rent stabilized?

NYC Department of Finance tax bills listed 96 rent-stabilized units here in 2024 (about 100% of its 96 apartments). To confirm a specific apartment, request its rent history from NYS Homes and Community Renewal.

When was 2911 Barnes Avenue built?

City records list 1931 as the year it was built.

How many apartments are in 2911 Barnes Avenue?

It has 96 residential units.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.