3120 Bainbridge Avenue

Bronx, NY 10467BBL 2-03341-0034Map

Owner of record: 3120 Bainbridge LLC

3120 Bainbridge Avenue is an elevator apartment building built in 1929 in Bronx, 10467. It has 56 residential units across 6 floors. The owner of record is 3120 Bainbridge LLC. HPD has recorded 648 housing violations here, most recently on March 4, 2026. 4 of the 50 most recent violations are still open. City tax records listed 55 rent-stabilized apartments here in 2024.

HPD violations
648
DOB violations
38
ECB violations
26
HPD complaints
835

What to know

Concern
4 open Class C

Immediately hazardous issues among recent violations are still open.

Good
Last violation Mar 4, 2026

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

Rent-stabilized units in 2024
55
About 98% of the building's 56 apartments

Counts come from owners' rent-stabilization filings shown on NYC Department of Finance tax bills, as extracted by JustFix. They tell you a building has stabilized apartments, not which ones.

Stabilized units by tax-bill year

Think your apartment is stabilized? Request its rent history from HCR (free), then check your renewal with the renewal calculator.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 648

  • B

    Remove all encumbrances consisting of discarded household ithems at southwall at public hall, 1st story

    Mar 4, 2026

    Closed — Violation dismissed
  • B

    Repair the broken or defective connection at sink in the kitchen located at apt 1j, 1st story, 3rd apartment from north at east

    Feb 9, 2026 · Apt 1J

    Closed — Violation dismissed
  • B

    Provide an adequate supply of gas to the fixtures at stove/range in the kitchen located at apt 1j, 1st story, 3rd apartment from north at east

    Feb 9, 2026 · Apt 1J

    Closed — Violation dismissed
  • C

    Replace or repair the self-closing doors that is missing or defective inoperable hinges in the entrance located at apt 1j, 1st story, 3rd apartment from north at east

    Feb 9, 2026 · Apt 1J

    Closed — Violation dismissed
  • B

    Properly repair or replace the broken or defective water damaged cabinet under sink in the kitchen located at apt 1j, 1st story, 3rd apartment from north at east

    Feb 9, 2026 · Apt 1J

    Closed — Violation dismissed
  • C

    Properly repair or replace the broken or defective air valve at radiator in the 1st room from east at north located at apt 1j, 1st story, 3rd apartment from north at east

    Feb 9, 2026 · Apt 1J

    Closed — Violation dismissed
  • C

    Provide ready access to buildings heating system locked door at boiler room

    Jan 20, 2026

    Closed — Violation dismissed
  • C

    Provide an adequate supply of heat for the apartment in the 3rd room from north located at apt 3d, 3rd story, 2nd apartment from south at west

    Jan 20, 2026 · Apt 3D

    Open — Nov sent out
  • C

    Properly repair with similar material the broken or defective 16th marble tread from bottom at south section at public hall stairs, 6th story

    Jan 3, 2026

    Closed — Violation dismissed
  • B

    Properly repair or replace the broken or defective electrical fixture at ceiling at public hall, 1st story

    Nov 30, 2024

    Closed — Violation dismissed
Show 40 more ↓
  • B

    Repair or replace the smoke detector additional device within 15 ft from sleeping area required in the entire apartment located at apt 3b, 3rd story, 2nd apartment from east at south , section at south

    Nov 30, 2024 · Apt 3B

    Closed — Violation dismissed
  • B

    Repair or replace the carbon monoxide detecting device(s). additional device within 15 ft from sleeping area required in the entire apartment located at apt 3b, 3rd story, 2nd apartment from east at south , section at south

    Nov 30, 2024 · Apt 3B

    Closed — Violation dismissed
  • B

    Repair or replace the smoke detector defective in the entire apartment located at apt 3b, 3rd story, 2nd apartment from east at south , section at south

    Nov 30, 2024 · Apt 3B

    Closed — Violation dismissed
  • B

    Repair or replace the carbon monoxide detecting device(s). defective in the entire apartment located at apt 3b, 3rd story, 2nd apartment from east at south , section at south

    Nov 30, 2024 · Apt 3B

    Closed — Violation dismissed
  • C

    M/d law abate the nuisance consisting of key operated lock at door leading to fire escape in the 2nd room from east located at apt 5k, 5th story, 2nd apartment from north at east , section ''south''

    Nov 21, 2024 · Apt 5K

    Open — Nov sent out
  • C

    Replace or repair the self-closing doors that is missing or defective at fire door at public hall, 6th story

    Nov 19, 2024

    Closed — Violation closed
  • A

    Trace and repair the source and abate the visible mold condition... less than 10 square feet at south wall in the 2nd room from east located at apt 6j, 6th story, 3rd apartment from north at east

    Sep 24, 2024 · Apt 6J

    Closed — Violation dismissed
  • B

    Properly repair or replace the broken or defective door knob at door leading to north section at public hall, 6th story

    Sep 24, 2024

    Closed — Violation dismissed
  • B

    Repair the roof so that it will not leak above ceiling at public hall, 6th story

    Sep 24, 2024

    Closed — Violation dismissed
  • A

    Paint with light colored paint to the satisfaction of this department at ceiling at public hall, 4th story

    Sep 24, 2024

    Closed — Violation dismissed
  • B

    Properly repair with similar material the broken or defective fire retardent material at ceiling at public hall, 4th story

    Sep 24, 2024

    Closed — Violation dismissed
  • B

    Properly repair the source and abate the evidence of a water leak above ceiling at public hall, 4th story

    Sep 24, 2024

    Closed — Violation dismissed
  • B

    Properly repair or replace the broken or defective spring balance at lower window sash at east wall at window leading to fire escape in the 1st room from east at north located at apt 6j, 6th story, 3rd apartment from north at east

    Sep 24, 2024 · Apt 6J

    Closed — Violation dismissed
  • C

    Abate the infestation consisting of roaches in the entire apartment located at apt 6j, 6th story, 3rd apartment from north at east

    Sep 24, 2024 · Apt 6J

    Closed — Violation dismissed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling and west wall in the 2nd room from east located at apt 6j, 6th story, 3rd apartment from north at east

    Sep 24, 2024 · Apt 6J

    Closed — Violation dismissed
  • C

    Replace or repair the self-closing doors that is missing or defective frame clashing with floor preventing it from being self closing at public hall, 6th story

    Sep 24, 2024

    Closed — Violation closed
  • A

    Paint with light colored paint to the satisfaction of this department at ceiling and east wall at public hall, 6th story

    Sep 24, 2024

    Closed — Violation dismissed
  • B

    Properly repair with similar material the broken or defective fire retardent material at ceiling and east wall at public hall, 6th story

    Sep 24, 2024

    Closed — Violation dismissed
  • B

    Properly repair or replace the broken or defective ceiling light fixture at public hall, 4th story

    Sep 24, 2024

    Closed — Violation dismissed
  • B

    Properly repair or replace the broken or defective rubber gasket at refrigerator door in the kitchen located at apt 6j, 6th story, 3rd apartment from north at east

    Sep 24, 2024 · Apt 6J

    Closed — Violation dismissed
  • B

    Repair the roof so that it will not leak above ceiling in the 1st room from east at north located at apt 6j, 6th story, 3rd apartment from north at east

    Sep 24, 2024 · Apt 6J

    Closed — Violation dismissed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling and around window frame at east wall in the 1st room from east at north located at apt 6j, 6th story, 3rd apartment from north at east

    Sep 24, 2024 · Apt 6J

    Closed — Violation dismissed
  • B

    Repair the roof so that it will not leak above ceiling in the 2nd room from east located at apt 6j, 6th story, 3rd apartment from north at east

    Sep 24, 2024 · Apt 6J

    Closed — Violation dismissed
  • C

    Remove device preventing door from being self-closing removable device (folded cardboard) at fire door at public hall, 6th story

    Mar 8, 2024

    Closed — Violation closed
  • C

    Properly repair or replace the broken or defective lower sash inner glass window in the 4th room from east located at apt 6c, 6th story, 1st apartment from east at south

    Mar 1, 2024 · Apt 6C

    Closed — Violation dismissed
  • C

    Provide hot water at all hot water fixtures in the 2nd room from north located at apt 6b, 6th story, 2nd apartment from east at south

    Feb 29, 2024 · Apt 6B

    Open — Nov sent out
  • C

    Replace or repair the self-closing doors that is missing or defective the hinges in the entrance located at apt 6a, 6th story, 1st apartment from east at south , section at south

    Feb 17, 2024 · Apt 6A

    Closed — Violation dismissed
  • C

    Replace or repair the self-closing doors that is missing or defective closure arm at vestibule door ( vestibule to 1st story public hallway)

    Dec 24, 2023

    Closed — Violation dismissed
  • C

    Replace or repair the self-closing doors that is missing or defective hinges at building entrance door [ from vestibule to public hallway ]

    Dec 4, 2023

    Closed — Violation closed
  • C

    Abate the infestation consisting of roaches in the entire apartment located at apt 2k, 2nd story, 2nd apartment from north at east , section at south

    Dec 4, 2023 · Apt 2K

    Closed — Violation dismissed
  • C

    Properly repair or replace the broken or defective mortise lock at building entrance door , 1st story

    Nov 24, 2023

    Closed — Violation dismissed
  • C

    Abate the infestation consisting of roaches in the entire apartment located at apt 6j, 6th story, 3rd apartment from north at east , section ''south''

    Nov 24, 2023 · Apt 6J

    Open — First no access to re- inspect violation
  • B

    Repair or replace the smoke detector missing in the entire apartment located at apt 6j, 6th story, 3rd apartment from north at east , section ''south''

    Nov 24, 2023 · Apt 6J

    Closed — Violation dismissed
  • B

    Repair or replace the carbon monoxide detecting device(s). defective in the entire apartment located at apt 6j, 6th story, 3rd apartment from north at east , section ''south''

    Nov 24, 2023 · Apt 6J

    Closed — Violation dismissed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at west wall in the 1st room from east located at apt 6j, 6th story, 3rd apartment from north at east , section ''south''

    Nov 24, 2023 · Apt 6J

    Closed — Violation dismissed
  • C

    Properly repair or replace the broken or defective mortise lock on building entrance door

    Nov 15, 2023

    Closed — Violation dismissed
  • C

    Replace or repair the self-closing doors that is missing or defective hinge in the entrance located at apt 2k, 2nd story, 4th apartment from west at north

    Nov 15, 2023 · Apt 2K

    Closed — Violation closed
  • C

    Abate the infestation consisting of mice in the entire apartment located at apt 2k, 2nd story, 4th apartment from west at north

    Nov 15, 2023 · Apt 2K

    Closed — Violation dismissed
  • C

    Abate the infestation consisting of roaches in the entire apartment located at apt 2k, 2nd story, 4th apartment from west at north

    Nov 15, 2023 · Apt 2K

    Closed — Violation dismissed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling, north wall and east walls in the 3rd room from north located at apt 5f, 5th story, 3rd apartment from south at west , section ''north''

    Oct 12, 2023 · Apt 5F

    Closed — Violation dismissed

DOB building violations · 38

  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2022

    Apr 22, 2023

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Mar 16, 2022

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Dec 22, 2021

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jun 9, 2021

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    May 12, 2021

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Mar 31, 2021

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 20, 2020

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 14, 2018

    Dob violation - resolved
Show 28 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 16, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 15, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 1, 2015

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2014 inspection/test

    Jun 10, 2015

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 2, 2015

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 22, 2014

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 5, 2013

    Dob violation - resolved
  • Emergency none

    Egncy-emergency none

    Oct 1, 2012

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2011 inspection/test

    Oct 1, 2012

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 1, 2012

    Dob violation - resolved
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Jan 1, 2012

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 23, 2011

    Dob violation - resolved
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 17, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 23, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 9, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 20, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 10, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 23, 2005

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 15, 2003

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Elevator elevatorrequired

    2p936

    Feb 28, 2002

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 17, 1993

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Oct 12, 1989

    Dob violation - active
  • Elevator elevatorrequired

    (51) remove unauthorized latches off of basement hoistway door (52) replace missing splice box covers where necessary

    Oct 11, 1988

    Dob violation - resolved

ECB violations · 26

  • Class - 2

    Install control temperature in motor room. insufficent lighting in motor room. install self closeing self locking motor door.

    Jul 25, 2022

    Resolve
  • Class - 1

    Class 1 violation issued dlm improperly installed on this device. no fireman service present in controller. install fireman service so dlm is in compliance with section 3.10.12 of appendix k3, class 2 violation

    Dec 4, 2021

    Resolve
  • Class - 2

    Pedestrian protection doesnt meet code spec.note:atoi observed heavyduty sws installed@exp1 w/active permitx00413167-sh.pedestrian walking under this sws.also observed some area havent maintained min clear ht o

    Nov 18, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Replace traction sheave. replace hoist cables.

    Sep 17, 2021

    Resolve
  • Class - 1

    Cease use item,/ brake sleeve worn, perform repairs then contact nycdob,for re-inspection at time of inspection full test weight with 125% at time of inspection. class 1 violation recurring condition,/ no fire

    Sep 1, 2021 · Penalty $3,125

    Active
  • Class - 2

    Pedestrian protection doesnt meet code spec.note:atoi observed hd sws installed@exp1,in front of bldg.pedestrian walking under sws.also observed sharp edges (ec3307.6.5.6) condition or bolt&screws w/o cap@sever

    Jun 25, 2021

    Resolve
  • Class - 2

    Tri-cock corroded-corrosion on domestic hw coil plate-no thermometer on dom. hw piping-no guards at gage glass-combustible material stored in boiler room-no body drain on safety valve; correct all violating con

    May 24, 2021

    Resolve
  • Class - 1

    Class 1 violation issued, 1/ in car phone not working 2/ in car stop switch bell not working 3/ in car alarm bell not working remedy; repair all items then notify nycdob of repairs immediately,

    Feb 26, 2021 · Penalty $1,250

    Active
  • Class - 1

    Door on sixth floor does not close on its own, adjust. alarm bell inoperative, repair. emergency phone inoperative, repair.

    Feb 16, 2021

    Resolve
  • Class - 1

    Class 1 no dlm installed in controller as mandated by 3.10.12 of appendix k3 of the 2014nycbc. remedy; file application, install dlm and file test with nycdob, class 2 in car phone not working remedy; repair, c

    Dec 28, 2020 · Penalty $1,250

    Active
Show 16 more ↓
  • Class - 2

    Failure to comply w/comm's order contained in summons/violation #35375392r issued on 3/2/19,& to file a certificate of correction pursuant to 28.201.1&1rcny 102-01(d)(2).an acceptable certificate has not yet be

    Dec 9, 2019 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. at the time of inspection it was observed in hallway & apt#6c that ceiling was instate of roof level. observed water damage cracks peeling plaster & disrepair

    Mar 2, 2019 · Penalty $625

    Resolve
  • Class - 2

    59bb5,99bb5,40m7,60m3,67x10,64m7,32h10,52m7. (59bb)remedy repair brake & test. (99bb)remedy file & repair test. (60m)remedy provide & install light guard. (40m)remedy install ventilation system in motor room. (

    Aug 2, 2018 · Penalty $313

    Resolve
  • Class - 1

    5a10,12i10,3d6,5i10,8v1,25m7,37o2,37b10,39d10,39x10,70o2,71x10,68b7,68m7,50y13,67x10,59b7. (5a)repair door zone restrictor.(12i)provide car lighting.(3d)secure wires in cab enclosure.(5i)repair gap in car door

    Jul 20, 2018 · Penalty $3,125

    Resolve
  • Class - 2

    67x10,12m07,35m07,12x10,57m07,46m07-67x10)cab plane not working, repair. 12m07)cab light missing cover, provide. 35m07)electric boxes in shaftway missing covers, provide. 12x10)light under cab not working, repa

    Dec 14, 2017 · Penalty $250

    Resolve
  • Class - 1

    97x17,12o3,2b7,59b7,68m7. the only elevator in bldg out of service upon inspection the device is found to be out of service creating a hazardous condition as per 1rcny 110-02. rmdy: restore to service immediat

    Mar 27, 2017 · Penalty $1,000

    Resolve
  • Class - 1

    Failure to maintain bldg exterior wall. defect noted at exposure #1 atsecond story window brick bulging outward in danger of falling onto public sidewalk. remedy:immediately make safe.repair as required.install

    Sep 26, 2012

    Resolve
  • Class - 3

    B354,15,16,48a,50a,b,c,d,e. 50a- bolts missing on front door of boiler. 50b- valve required on top of oil tank on suction line and anti-syphon. 50c- guard for supply pump missing. 50d- soot on boiler and burner

    Feb 4, 2012

    Resolve
  • Class - 2

    100m10,70o02,08v10,56y13,37t07,37x10,43q03,05l10,52m07.(100)repair missing toeguard (approx).(37)label overhead door & repair work lighting.(05l10)provide slow down for car door on closing.(52)provide anti-spin

    Sep 9, 2010 · Penalty $2,500

    Active
  • Class - 1

    Failure to maintain bldg in code complaint manner improper exit. "magic video games" store awning & roller gate. top is obstructing fire escape ladder from going down. remedy: remove obstruction

    Oct 8, 2009 · Penalty $1,200

    Active
  • Non-hazardous

    50j 57o 74m 50y 74 m 07 toe graud missing provide

    Jun 1, 1999 · Penalty $180

    Resolve
  • Hazardous

    73u,57o,35b,47h,46h,74m,03i,14m,37d,37m,37a, 1. no city tags 2. clean pit 3. insufficient motor room lighting 4. shorten governor cable. 5. hoist cable too deep in sheave. 6. replace missing toe guard 7. repair

    Aug 5, 1997 · Penalty $100

    Resolve
  • Non-hazardous

    50y 73o 28h 14m 11q 05h 15e 62m 62m toe guard

    Dec 7, 1993 · Penalty $200

    Resolve
  • Non-hazardous

    28l, 30o, 35o, 31q, 50y, 33p, 33i, 73u, 74m, 25t.#31 covers motor room#33i repair overhead door #74 provide light top of car

    Sep 23, 1993 · Penalty $200

    Resolve
  • Non-hazardous

    8v 17q 28l 30o 31q 35p 75t 31 covers in shaft & top of car

    Mar 6, 1993 · Penalty $100

    Resolve
  • Non-hazardous

    14i,35p,74o,74r,(35)provide access to motor room (74)clean car top (74)remove illegal latches off of basement hoistway door.

    Dec 11, 1990 · Penalty $1,000

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Feb 8, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Apartment only

    Feb 8, 2026 · Apt 5F

    Close
  • Heat/hot water

    Entire building

    Feb 8, 2026 · Apt 3B

    Close
  • Heat/hot water

    Apartment only

    Feb 8, 2026 · Apt 5E

    Close
  • Heat/hot water

    Entire building

    Feb 8, 2026 · Apt 6C

    Close
  • Heat/hot water

    Entire building

    Feb 8, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Apartment only

    Feb 8, 2026 · Apt 1J

    Close
  • General

    Cabinet

    Feb 8, 2026 · Apt 1J

    Close
  • Door/window

    Door

    Feb 8, 2026 · Apt 1J

    Close
  • Appliance

    Electric/gas range

    Feb 8, 2026 · Apt 1J

    Close
Show 40 more ↓
  • Plumbing

    Basin/sink

    Feb 8, 2026 · Apt 1J

    Close
  • Electric

    Outlet/switch

    Feb 8, 2026 · Apt 1J

    Close
  • Plumbing

    Steam pipe/riser

    Feb 8, 2026 · Apt 1J

    Close
  • Heat/hot water

    Entire building

    Feb 7, 2026 · Apt 6B

    Close
  • Heat/hot water

    Entire building

    Feb 3, 2026 · Apt 3D

    Close
  • Heat/hot water

    Apartment only

    Feb 3, 2026 · Apt 3D

    Close
  • Heat/hot water

    Apartment only

    Jan 17, 2026 · Apt 3D

    Close
  • Heat/hot water

    Apartment only

    Jan 13, 2026 · Apt 3D

    Close
  • Heat/hot water

    Apartment only

    Jan 3, 2026 · Apt 3D

    Close
  • Heat/hot water

    Entire building

    Jan 3, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Apartment only

    Jan 2, 2026 · Apt 5F

    Close
  • Heat/hot water

    Apartment only

    Jan 2, 2026 · Apt 3D

    Close
  • Heat/hot water

    Apartment only

    Jan 2, 2026 · Apt 3B

    Close
  • Heat/hot water

    Entire building

    Jan 1, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Jan 1, 2026 · Apt 6B

    Close
  • Heat/hot water

    Apartment only

    Dec 16, 2025 · Apt 6B

    Close
  • Heat/hot water

    Apartment only

    Dec 16, 2025 · Apt 4E

    Close
  • Heat/hot water

    Entire building

    Dec 16, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 16, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 16, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 16, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Apartment only

    Dec 15, 2025 · Apt 4E

    Close
  • Heat/hot water

    Entire building

    Dec 15, 2025 · Apt 6B

    Close
  • Heat/hot water

    Entire building

    Dec 15, 2025 · Apt 3B

    Close
  • Heat/hot water

    Entire building

    Dec 15, 2025 · Apt 3B

    Close
  • Heat/hot water

    Entire building

    Dec 15, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 12, 2025 · Apt 3B

    Close
  • Heat/hot water

    Apartment only

    Dec 5, 2024 · Apt BUILDI

    Close
  • Heat/hot water

    Entire building

    Dec 4, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 4, 2024 · Apt 5K

    Close
  • Heat/hot water

    Entire building

    Dec 3, 2024 · Apt 6B

    Close
  • Heat/hot water

    Entire building

    Dec 2, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 2, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 1, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 30, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Apartment only

    Nov 30, 2024 · Apt 6K

    Close
  • Heat/hot water

    Entire building

    Nov 30, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 30, 2024 · Apt 3B

    Close
  • Heat/hot water

    Apartment only

    Nov 30, 2024 · Apt 5F

    Close
  • Heat/hot water

    Entire building

    Nov 30, 2024 · Apt 5F

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Elevator apartment building (D7)
Year built
1929
Floors
6
Residential units
56
Building area
68,000 ft²
Lot area
17,950 ft²
Zoning
R7A
Community board
207
Council district
11
Block / lot
3341 / 34
Assessed value
$1,041,750
Landmark / historic district
No

HPD registration #207337, last renewed Jul 30, 2026.

Questions about 3120 Bainbridge Avenue

Who owns 3120 Bainbridge Avenue?

The owner of record in NYC Department of City Planning PLUTO data is 3120 Bainbridge LLC.

Does 3120 Bainbridge Avenue have violations?

Yes. NYC HPD has recorded 648 housing violations at this property.

Is 3120 Bainbridge Avenue rent stabilized?

NYC Department of Finance tax bills listed 55 rent-stabilized units here in 2024 (about 98% of its 56 apartments). To confirm a specific apartment, request its rent history from NYS Homes and Community Renewal.

When was 3120 Bainbridge Avenue built?

City records list 1929 as the year it was built.

How many apartments are in 3120 Bainbridge Avenue?

It has 56 residential units and 64 units in total.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.