528 Morris Avenue

Bronx, NY 10451BBL 2-02330-0005Map

Owner of record: E&N Refrigeration Corp.

528 Morris Avenue is a care facility built in 1909 in Bronx, 10451. The owner of record is E&N Refrigeration Corp.. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
26
ECB violations
22
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 26

  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 30, 2019

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2016 inspection/test

    Sep 15, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 4, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 11, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 3, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 5, 2013

    Dob violation - resolved
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2010 inspection report

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 28, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 9, 2010

    Dob violation - resolved
Show 16 more ↓
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 1, 2009

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 20, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 6, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 15, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 15, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 20, 2004

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 20, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 22, 2002

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 28, 1993

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 29, 1990

    Dob violation - dismissed
  • Elevator elevatorrequired

    (51)restore elev to service

    Nov 9, 1988

    Dob violation - resolved

ECB violations · 22

  • Class - 2

    Observed on the fourth floor, gas dryer vents are crushed and not sealed properly; on second floor slop sink room, sprinkler head obstructed and pvc piping is used on waste line; in the basement sprinkler line

    Dec 18, 2025 · Penalty $1,250

    Active
  • Class - 2

    Class 2: missing 2025 maintenance log, provide. excessive horizontal movement on car top, adjust steading plates. 5 floor hoistway door not self closing, adjust. g floor door has very little tension, adjust to

    Nov 25, 2025 · Penalty $625

    Active
  • Class - 1

    Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed excessive hole penetrations roof level in it room. potential fire hazard

    Jan 29, 2025 · Penalty $2,500

    Resolve
  • Class - 1

    Failure to maintain building in code-compliant manner. observed no ventilation for gas meter at basement level. potential fire hazard., repair and/replace

    Jan 29, 2025 · Penalty $1,250

    Resolve
  • Class - 1

    Unsafe storage of combustible material and equipment. observed unsafe combustible storage (boxes, shelving, printer, small fan, and drawer) stored in hot water heater room. potential fire hazard., maintain stor

    Jan 29, 2025 · Penalty $2,500

    Resolve
  • Class - 2

    Failure to comply with the commissioner's order contained in summons/violation #39006829m issued on 07/31/19 and to file a certificate of correction pursuant to 28-201.1 and 1 rcny 102-01.remedy:comply with com

    Jan 3, 2020

    Resolve
  • Class - 2

    Failure to comply w/the comm's order contained in summons/vio#39006829m issued on 07-31-19 & to file a c of c pursuant to 28-201.1 & 1rcny 102-01. failure to maintain bldg in code compliant manner. remedy: comp

    Nov 15, 2019

    Resolve
  • Class - 2

    Failure to comply with the commissioner's order contained in summons/violation#39006829m issued on 7/31/19 and to file a certificate of correction pursuant to 28-201.1&1rcny 102-01.for failure to maintain build

    Oct 7, 2019 · Penalty $1,250

    Resolve
  • Class - 1

    Failure to maintain building in a code compliant manner. at the time of inspection, observed building fire escape at rear in state of disrepair throughout with multiple missing and loose metal steps, dislodged

    Jul 31, 2019 · Penalty $1,250

    Resolve
  • Class - 2

    Need to replace cleanout door for chimney. need to fix lighting for boiler room. need to install separate pig tails on all controls.

    Jul 16, 2019 · Penalty $625

    Resolve
Show 12 more ↓
  • Class - 1

    Oac sign on display structure w/o a permit. (telemundo) remedy: removeillegal sign.

    Oct 6, 2011

    Resolve
  • Class - 1

    Oac sign prohibited in c1-4 zone. (telemundo) remedy: remove illegal sign.

    Oct 6, 2011

    Resolve
  • Class - 1

    Oac failed to have licenesed sign hanger attach or erect sign. (telemundo) remedy: remove illegal sign.

    Oct 6, 2011

    Resolve
  • Class - 1

    Oac failed to have licensed siggn hanger attach ul classification markor date of sign's erection to corner of sign fabric. (telemundo) remedy: remove illegal sign.

    Oct 6, 2011

    Resolve
  • Class - 1

    Owner acting as oac failed to obtain oac registration # while engagingin the outdoor ad business. (telemundo) remedy: remove illegal signs/register.

    Oct 6, 2011

    Resolve
  • Class - 2

    39o02,39q03,67x10,70o02. 39-q-03 install guard for light on top of car 67-x-10 repair communication in car telephone.

    Jan 4, 2010

    Resolve
  • Hazardous

    Failure to maintain interior bldg. defect noted: metal staircase leading from cellar to 1st fl level is severely corroded w/open gaps at therun & loose/hanging risers. remedy: repair/replace staircase.

    Jun 23, 2008 · Penalty $800

    Resolve
  • Hazardous

    Failure to maintain bldg. defects noted: cellar west side steel stairsup to first flr severely corrodeo treados & risers w/missing lowest tread & loose/hanging riser at approx. middle run. also noted; cellar

    Jan 18, 2008 · Penalty $2,500

    Resolve
  • Non-hazardous

    Altered building occupied without a valid certificate of occupancy alt#200518886 note-tc of o#200518886 expired 12-1-2000.remedy:obtain a valid certificate of occupancy

    Jun 7, 2001 · Penalty $180

    Resolve
  • Non-hazardous

    74#. 74. file application and obtain permit for removal of device #2f108

    Dec 15, 1993

    Resolve
  • Non-hazardous

    74#,restore to service or file for removal with this dept.

    Nov 10, 1992 · Penalty $1,000

    Resolve
  • Non-hazardous

    Failure to maintain exterior building wall defect is metal cornice pulling away from building wall at roof front of bldg. remedy repair and or secure the metal cornice at roof front forthwith

    Jul 27, 1988 · Penalty $125

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Care facility (N9)
Year built
1909
Floors
5
Residential units
—
Building area
18,226 ft²
Lot area
3,744 ft²
Zoning
C4-4
Community board
201
Council district
17
Block / lot
2330 / 5
Assessed value
$1,740,600
Landmark / historic district
No

Questions about 528 Morris Avenue

Who owns 528 Morris Avenue?

The owner of record in NYC Department of City Planning PLUTO data is E&N Refrigeration Corp..

Does 528 Morris Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 528 Morris Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 528 Morris Avenue built?

City records list 1909 as the year it was built.