180 Wadsworth Avenue

Manhattan, NY 10033BBL 1-02164-0032Map

Owner of record: NYC Department Of Education

180 Wadsworth Avenue is a school building built in 1900 in Manhattan, 10033. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
26
ECB violations
53
HPD complaints
3

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 26

  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator - failure to file category 1 2017 inspection/test

    Apr 5, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 19, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 21, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 9, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 20, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 27, 2008

    Dob violation - resolved
Show 16 more ↓
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatorrequired

    1p37051

    Nov 24, 1999

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 6, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - active
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 1996

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    May 31, 1994

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Mar 24, 1993

    Vp-violation unserved ecb-active
  • Construction other optional

    C-construction other optional

    Mar 24, 1993

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Aug 17, 1992

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Aug 17, 1992

    Vp-violation unserved ecb-active

ECB violations · 53

  • Class - 2

    Failure to maintain building in code-compliant manner. noted: water damage on ceiling in classroom #407. remedy: repair and/or replace.

    Feb 17, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35676146k failure to maintain building in code compliant manner.noted:at roof level 4th floor rm-403 ceiling is in disrepair.rem:comply with code.

    Feb 20, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at classroom#403,ceiling in state of disrepair due to water penetrations from roof above causing the ceiling be staired and damage the ceiling in the

    Feb 6, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at roof level,observed at various locations,roofing material in state of disrepair with several air or water pockets/blisters and failing membrane cau

    Feb 6, 2024 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35663320y-exit door not self-closing.noted:at 3rd flr-stwy a &b and at 1st flr-exit#2.emergency exit are not working adequately whentested due to dilapidated door/frame and/or defective hardware.rem:rep

    Feb 6, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35657843m date of issue #06.10.2022 exit door not self closing properly at the time of inspection. at the time of inspection at 3rd floor one exit door near stair "b" & one exit door near stair "a" at

    Jun 21, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self-closing properly at time of inspection.at time of inspection observed at 3rd floor 2 exit doors at stairway "a" & one door at stairway "b" not closing properly.at 1st floor near stairway "a"

    Jun 10, 2022 · Penalty $625

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as per 3.10.12 of appendix k3 of the 2014 nycbc. remedy; install dlm and, perform and file test with nycdob.

    Mar 6, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Exit door not self closing at 1st fl.exit-2 outside exit door,one dooris not self closing properly.at 3rd fl.exit stairway "a" 1 door is notself closing properly at the time of inspection when tested.rem:repair

    May 16, 2019

    Resolve
  • Class - 3

    Failure to maintain building in code compliant manner (interior).notedat time of inspection at basement-lumber and plywood material is beingstored within machine room and boiler room area.rmdy:repair and/or rep

    Sep 14, 2016

    Resolve
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code compliant manner: use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted: at time of inspection, when exiting from cafeteria to loading dock and to the pub

    Sep 14, 2016

    Resolve
  • Class - 2

    Excessive combustibles. at 1st floor corridor, combustible paper artwork & decorations continue to ceiling throughout. remedy: remove all excessive combustible art.

    Jun 9, 2014

    Resolve
  • Class - 2

    Partial obstruction. at 1st floor corridor, cardboard boxes & school supplies obstruct approx 1/3' of corridor. remedy: remove all items, maintain corridor width clear.

    Jun 9, 2014

    Resolve
  • Class - 2

    Exit door not self closing. at 4b, broken door closer. remedy: replace door closer.

    Jun 9, 2014

    Resolve
  • Class - 2

    Missing fire stopping. at 4th floor mop sink room, no fire stopping above door with pipe penetration to concealed space above corridor ceiling. remedy: provide/maintain fire stopping.

    Jun 9, 2014

    Resolve
  • Class - 2

    Reissue 34958229p the gas meter room is being used as a storage room consisting of card board boxes, chairs & tables @ the cellar level. rem: remove obstruction.

    Apr 29, 2013

    Resolve
  • Class - 2

    Reissue 34958226j the corridor hallway is partially obstructed by tables, chairs & book cases on the 1st flr level main entrance. rem: remove obstruction.

    Apr 29, 2013

    Resolve
  • Class - 2

    Reissue 34958227l the plaster on the wall is spalling located in room 302 (3rd floor level). rem: repair and/or replace plaster.

    Apr 29, 2013

    Resolve
  • Class - 2

    Reissue: 34908343n coping stone at parapet west side on roof is spalling & crumbling. remedy: replace defective coping.

    May 15, 2012

    Resolve
  • Class - 2

    Reissue: 34908341j at 1st fl corridors partial obstruction w/tables,chairs,book cases boxes etc. remedy: remove obstructions.

    May 15, 2012

    Resolve
  • Class - 2

    2nd fl stwy 'a' door racked. 1st fl stwy 'b' door racked. cafeteria door racked. remedy: repair/replace doors.

    May 15, 2012

    Resolve
  • Class - 2

    At cellar level gas meter room & electrical room are being used for storage (chairs,tables,floor buffing machines etc.) remedy: remove storage items.

    May 15, 2012

    Resolve
  • Class - 2

    3rd floor room 302 plaster spalling from wall near window. cellar north wall across from oil tank room plaster spalling. remedy: repair spalling plaster wall.

    May 15, 2012

    Resolve
  • Class - 2

    Reissue#x0402132m.partial corridor obstruction @ cellar level,the fire corridors have partial obstruction with various school material and classroom supplies.1st flr with tables,cushion chairs,book cases & boxe

    May 4, 2011

    Resolve
  • Class - 2

    Defective coping stones @ roof west parapet wall,several cast coping stone are spalling and crumbling on the top roof side of parapet wall.rem:replace precast coping stones

    May 4, 2011

    Resolve
  • Class - 2

    Reissue#34862131k.prohibited hardware.@ classrooms all flrs,hardware installed prohibited corridor doors from self closing.rem:remove prohibited hardware

    May 4, 2011

    Resolve
  • Class - 2

    Fail to maintain bldg in code compliant manner. noted: rm 202 hole in floor causing tripping hazard approx 4" deep. remedy: maintain bldg replace/repair

    Jul 28, 2010

    Resolve
  • Class - 2

    Fail to maintain bldg in code compliant manner. noted: stair c door missing lockset missing. remedy: maintain bldg replace/repair

    Jul 28, 2010

    Resolve
  • Class - 2

    Fail to maintain bldg in code compliant manner. use of prohibited doorand/or hardware per bc 1008.1.8 noted: installed on classroom, corridor, auditorium doors. remedy: remove illegal hardware.

    Jul 28, 2010

    Resolve
  • Class - 2

    Sec 27-361 misc viol: fail to maintain egress clear & unobstructed. noted: cellar level corridors. obstructed by storage of school supplies in some places reducing egress width by more than 50%. remedy: remove

    Jul 28, 2010

    Resolve
  • Class - 3

    Reissue 34646195n cellar corridor used for storage of boxes tables chairs,books, tv and cabinets remedy:maintain clear egress

    May 12, 2009

    Resolve
  • Class - 3

    Failure to maintain bldg exterior at 4 fls roof leaks in all four claeerooms and skylight in center corridor water stained 1 x 1 tiles in classrooms remedy:repair roof leaks

    May 12, 2009

    Resolve
  • Class - 3

    Failure to maintain exterior bldg wall at 4th fl flaking peeling waterstained plaster at exterior walls in all classrom due to leaking exte erior brick masonary remedy:maintain exterior bldg wall repair leaks

    May 12, 2009

    Resolve
  • Non-hazardous

    Boxes, tables, chairs, books in the corridor hallway at cellar. remedyremove obstruction in the corridors.

    Jun 11, 2008

    Resolve
  • Hazardous

    Failure to provide panic hardware where required by law. no panic hardware provided on door. the locking pins for the panic hardware are stuck in the floor and in the head of the door. the door is in a stuck.

    May 30, 2006

    Resolve
  • Non-hazardous

    Noted: east elevation handicap ramp & landing at street level have approx. 2"-3" differences in elevation with sidewalk settling creating the variation & making ramp inaccessible.remedy:repair/maintain ramp & s

    Feb 15, 2005 · Penalty $2,500

    Resolve
  • Non-hazardous

    Noted: basement electric room wall penetrations not properly fire-stopped-avove entry door. remedy: provide/maintain fire stopping.

    Feb 15, 2005 · Penalty $2,500

    Resolve
  • Non-hazardous

    Failure to maintain building defect noted: defective closer (does not close properly)- 3rd flr. stair "b" remedy: maintain building / repairas required.

    Mar 31, 2004

    Resolve
  • Non-hazardous

    Failure to post capacity sign noted: no occupancy signage posted in cafeteria. remedy: provide capacity signage.

    Mar 31, 2004

    Resolve
  • Non-hazardous

    Reissue: failure to maintain building defects roof leaks above classrooms.402,403,407. remedy: maintain building repair roof as needed.

    Feb 3, 2003

    Resolve
  • Non-hazardous

    Failure to maintain building defects; broken door checks at 4 floor exit b 3 rd boys room. 2 floor girls room. remedy: maintain building repair replace door checks.

    Feb 3, 2003

    Resolve
  • Non-hazardous

    9h12/ 2l11/ 57h12/ 57h12 = piston packing leaks

    May 3, 2002

    Resolve
  • Non-hazardous

    Failure to maintain building defects noted water penetration from roof causing the ceiling tiles loose and hanging from class rms ceiling #402-403-and 407 remedy repair and replace defective ceiling

    Jan 22, 2002

    Resolve
  • Non-hazardous

    Reissue failure to maintain building defect noted leaks freom roof causing water penetrating into classrooms numbers 402/403/407/ remedy repair defect

    Jan 22, 2002

    Resolve
  • Non-hazardous

    Failure to maintain defects, leaking ceiling into building. location cafeteria at north exits. remedy do repairs

    Apr 23, 2001 · Penalty $2,500

    Resolve
  • Hazardous

    Failure to maintain defects missing ornamental dental soffit, open soffit. location: south soffits. remedy do repair.

    Apr 23, 2001 · Penalty $2,500

    Resolve
  • Non-hazardous

    Failure to maintain defects chimniey cracked, loose bricks at (lamp) location roof west. remedy do repairs.

    Apr 23, 2001 · Penalty $2,500

    Resolve
  • Non-hazardous

    Failure to maintain defects, cracked coping on roof parapet wall allowing water in building. location: 182 st and wadsworth ave. remedy: do repairs.

    Apr 23, 2001 · Penalty $2,500

    Resolve
  • Non-hazardous

    Failure maintain defects, leaking ceilings into building rm's. location: 407,402,402closet, 403 e/s. remedy: do repairs.

    Apr 23, 2001 · Penalty $2,500

    Resolve
  • Non-hazardous

    Failure to maintain. defect: no emergency lighting in stairways or anyother part of building. remedy: obtain permit(s) and install emergencylighting throughout building as per n.y.c. building code.

    Mar 1, 1999 · Penalty $2,500

    Resolve

Complaints

  • General

    Cooking gas

    Oct 14, 2021 · Apt BLDG

    Close
  • Heat/hot water

    Apartment only

    Jan 18, 2016 · Apt 5

    Close
  • Door/window

    Door

    Jun 24, 2015 · Apt 3C

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1900
Floors
4
Residential units
—
Building area
17,528 ft²
Lot area
6,579 ft²
Zoning
R7-2
Community board
112
Council district
10
Block / lot
2164 / 32
Assessed value
$1,727,550
Landmark / historic district
No

Questions about 180 Wadsworth Avenue

Who owns 180 Wadsworth Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 180 Wadsworth Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 180 Wadsworth Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 180 Wadsworth Avenue built?

City records list 1900 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.