2930 8 Avenue
Manhattan, NY 10039BBL 1-02105-0001Map
Owner of record: NYC Department Of Homeless Services
2930 8 Avenue is a care facility built in 1954 in Manhattan, 10039. The owner of record is NYC Department Of Homeless Services. HPD has recorded 1 housing violation here, most recently on April 11, 2017.
- HPD violations
- 1
- DOB violations
- 18
- ECB violations
- 61
- HPD complaints
- 7
What to know
No open immediately-hazardous violations among recent records.
Date of the most recent HPD inspection that found a problem.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 1
- CImmediately hazardous
M/d law abate the nuisance consisting of scalding hot water at community bathroom, 3rd story
Apr 11, 2017
Closed — Violation closed
DOB building violations · 18
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed
Show 8 more ↓
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 18, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 18, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 18, 1993
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 18, 1993
Dob violation - dismissed
ECB violations · 61
- Class - 1
Failure to maintain building in code-compliant manner. observed ceiling chipped and falling off ceiling. this is a overhead hazard. located in auditorium/ lunchroom., repair and/replace
Nov 19, 2024 · Penalty $1,250
Active - Class - 2
Observed gas leaf blowers being stored in room adjacent from the boiler room. no gas fired equipment shall be stored inside of building., repair and/or replace
Nov 19, 2024 · Penalty $625
Resolve - Class - 2
Observed non self closing doors throughout building. incase of emergency this is a fire or evacuation hazard., repair/replace door
Nov 19, 2024 · Penalty $625
Resolve - Class - 1
Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed hole penetrations at 2nd floor mens bathroom. incase of emergency this i
Nov 19, 2024 · Penalty $2,500
Resolve - Class - 1
Unlawful acts: failure to comply with commissioner's orders as stated in ecb# 39077703p issued on 01/11/2023 and file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01 for failure to ground elec
Jun 3, 2024 · Penalty $4,800
Active - Class - 1
Failure to comply with commissioner's orders as stated in ecb# 39077701l issued on 01/11/2023 for improper fusing of electrical conductors and file a certificate of correction as pursuant to 28-201.1 and 1rcny
Jun 3, 2024 · Penalty $2,500
Active - Class - 1
I observed in the main electrical room the service disconnect switch improper fusing. the switch has (2) 300 amp fuses and (1) 400 amp fuse. all fuses in a disconnect shall be coordinated., provide protection a
Jun 3, 2024 · Penalty $4,800
Active - Class - 1
Unlawful acts: failure to comply with commissioner's orders as stated in ecb # 39077701l issued on 01/11/2023 and file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. failure to safeguard per
Mar 7, 2024 · Penalty $2,500
Active - Class - 1
Unlawful acts: failure to comply with commissioner's orders as stated in ecb # 39077703p issued on 01/11/2023 and file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. failure to safeguard per
Mar 7, 2024 · Penalty $2,500
Active - Class - 1
Unlawful acts: failure to comply with commissioner's orders as stated in ecb # 39077698j issued on 01/11/2023 and file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. failure to safeguard per
Mar 7, 2024 · Penalty $2,500
Active
Show 40 more ↓
- Class - 1
Unlawful acts: failure to comply with the commissioners order contained in summons/violation# 39077703p issued on 01/13/23 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01., comply
Dec 20, 2023 · Penalty $2,500
Active - Class - 1
Unlawful acts: failure to comply with the commissioners order contained in summons/violation# 39077698j issued on 01/11/23 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01., comply
Dec 20, 2023 · Penalty $2,500
Active - Class - 1
Unlawful acts: failure to comply with the commissioners order contained in summons/violation# 39077701l issued on 08/03/23 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01., comply
Dec 20, 2023 · Penalty $2,500
Active - Class - 1
I observed in the main electrical room the installation of the ground bar for the service disconnects with no main conductor from the water main. a supplemental ground rod is providing the primary ground., prov
Oct 25, 2023 · Penalty $4,800
Active - Class - 1
I observed in the main electrical room the installation of (2) 300 amp fuses and (1) 400 amp fuse. this is not permitted all fusing of conductors shall be the same rating. photos taken., provide protection agai
Oct 25, 2023 · Penalty $4,800
Active - Class - 2
-emergency exit roof doors do not self-close located on roof, both staircases/buldheads. emergency exit door and door #5, fire proof self-closing does not shut and latch located in corridor of staircase a., rep
Aug 3, 2023 · Penalty $625
Resolve - Class - 2
Missing handrail on handicap ramp lacated at the front entrance., repair and/or replace
Aug 3, 2023 · Penalty $625
Resolve - Class - 1
I observed in the electrical service room the installation of a ground bar for the service disconnects with no main ground electrode conductor from the water main. a supplemental ground rod is supplying the pri
Jan 13, 2023 · Penalty $4,800
Active - Class - 1
I observed in the main electrical room the installation of (2) 300 amp fuses and (1) 400 amp fuses. this not permitted all fusing of conductors are to be of the same rating. photos taken., provide protection ag
Jan 11, 2023 · Penalty $4,800
Active - Class - 2
Observed: fire proof self-closing door at second fl, smoke door near rm 213 & first fl, exit doors # 3,4,2, library (obstruction exit way) & cafeteria (3 doors) also, cafeteria/ exit door are missing push bars.
Jan 11, 2023 · Penalty $1,562
Active - Class - 1
I observed on rooftop a the use of flexible rubber cord through the concrete wall and improperly spliced with exposed and energized wiring supplying power to the down light. as ec 400.8 flexible cords are not p
Jan 11, 2023 · Penalty $1,600
Active - Class - 2
I observed in the main disconnect switches the electrical room the improper termination of the conductors .for the termination of two conductors under a single lug it shall be of the type designed for such inst
Jan 11, 2023 · Penalty $1,200
Active - Class - 2
I observed on the rooftop "a" side 8(#s 5-6-8-9-10-11-13-14) defective/inoperable exhaust fans. photos taken, comply with ec; repair/or replace defective equipment.
Jan 11, 2023 · Penalty $800
Active - Class - 2
Observed: at second floor corridor, fire proof walls, several cracks near rms, 214/215/212/206/202/201. also, at cellar level, corridor near maintence rm and electrical room., repair and/or replace
Jan 11, 2023 · Penalty $625
Resolve - Class - 2
Observed: at ground level, maint entrance starir (right side) & ramp (left side) missing handrails, repair and/or replace
Jan 11, 2023 · Penalty $625
Resolve - Class - 2
Fire proof self-closing door at 3rd fl, smoke door stair a, smoke door near rm 313, at second fl, smoke door near rm 213 & first fl, exit doors # 3,4,2 & cafeteria (3 doors) also, cafeteria/ exit door are missi
Jun 6, 2022 · Penalty $1,562
Resolve - Class - 2
Repair clamp used to stop leak-corrosion on valve boiler no. 2-piping uncapped at mixing valve and piping capped w/waste fitting-electrical connection box for fire switch w/o a cover-no shut-off valve fuel oil
May 13, 2022 · Penalty $625
Active - Class - 1
I observed in the main electrical room, an excessive amount of water leaking from above onto the main electrical equipment. equipment is currently being deteriorated, and the water pooling can lead to a shock h
Dec 7, 2021 · Penalty $1,250
Active - Class - 2
I observed an active water leak from the laundry room to the electric meter room that is located in the basement., repair and/or replace
Nov 24, 2021 · Penalty $625
Resolve - Class - 2
Noted: observed fire proof self closing doors at all floors in stairwell "a" and "b" are racked, and damaged door closer hardware and are excessively rubbing on the floors not allowing the doors to self close.,
Nov 24, 2021 · Penalty $1,562
Resolve - Class - 2
Found fitzgibbon boiler active with defects. combustion air fan sail switch defective. correct all violating conditions and submit a certificate of correction.
Sep 22, 2021 · Penalty $625
Active - Class - 1
An unlawful act.failure to comply with an order of the commissioner.failure to correct and certify summons#35253004k issued on 4/12/2017,forfailure to ground the electrical service in the basement.also summons#
Aug 27, 2021 · Penalty $2,500
Active - Class - 2
Noted: exit doors at 3rd and 2nd floor stairway a, and 1st floor stairway b, do not self close, doors are rubbing on the floor. , repair/replace door
Sep 23, 2019
Active - Class - 1
I observed in the electrical service room the installation of a ground bar for the service disconnects with no main grounding electrode conductor from the water main. a supplemental ground rod conductor is supp
Sep 23, 2019
Active - Class - 2
I observed in the electrical equipment room the installation of two service switches with conduits and wiring to supply power to the kitchen and a second unspecified location. the connections to provide power a
Sep 23, 2019
Active - Class - 2
Noted: operating a place of assembly at 1st floor cafeteria/gym, without a valid certificate to operate, tables and chairs arranged for seating 93 persons., obtain place of assembly certificate of operation
Sep 23, 2019
Active - Class - 1
I observed in the electrical room, service switches with improper fusing , , provide protection against overcurrent; install fuses uniformly.
Sep 23, 2019
Active - Class - 2
Piping on feed water leak-smoke alarm defective-backflow drain not connected-surface blow down drain not piped-body drains not installed on safety valves-flame glass missing-low water cutoff valve defective; co
May 8, 2019
Active - Class - 2
Work without a permit. observed in cellar plumbing work done to remove two temporary avl pipes line from two boilers without a permit. rem: obtain all required permits.
Apr 17, 2019
Active - Class - 2
B254,42,50a-50f 50a-need sump pump to be repaired or replaced; 50b- smoke alarm not working; 50c-fresh air fan not working and missing sail switch; 50d- no open ball valves; 50e-missing adder and platform
Aug 21, 2018
Active - Class - 2
Failure to maintain bldg in code compiant manner. observed on 4218 at above address active leak on water piping in water/sprinkler room. rmdy: repair and/or replace. photos taken.............................
Apr 2, 2018
Active - Class - 1
Branch circuit conductors are not of proper sized.branch circuit conductors providing power to 2 commercial grade heating ovens are not of proper size;visible burn marks on conductors noticed.note:maintenance &
Apr 2, 2018
Resolve - Class - 1
Unlawful acts. failure to comply with an order of the commissioner. in august 21, 2017, 28, 17, april 12, 2017. four electrical violations was issued to the respondent. the respondent failed to comply with (nyc
Feb 2, 2018
Active - Class - 2
Operation of a place of assembly without a current certificate of operation.noted: no current certificate of operation for 1st story cafeteria with maximum occupancy sign for 365 person.remedy:obtain a place
Aug 28, 2017
Active - Class - 2
Fail to maintain building in code compliant manner.rc:installation/maintenance of plumbing materials/equipment per p.c. 102.3;27-902. observed on 8/28/17 at above address jim caps installed in basement outside
Aug 28, 2017
Active - Class - 2
Failure to maintain building in code compliant manne:no fire stopping per bc 712.3:27-345. noted: at cellar in gas meter room,openings around plumbing eliminating fire stopping.remedy:provide/maintain fire stop
Aug 28, 2017
Active - Class - 2
Fail to provide effective electrical continuity for metal raceways/ enclosures/cable armor.observed sealtite in kitchen disconnected from fixed appliance waith wiring exposed.remedy:comply with code/provide
Aug 28, 2017
Active - Class - 2
Failure to maintian /provide access/work space about electrical equipment. observed in kitchen equipment disconnected switch behind pressuregauge.this gauge prevent the opening of the door to the switch. also
Aug 28, 2017
Resolve - Class - 1
110.4 conductors not properly installed /terminated . observed prior condition not rectified as per previous ecb #35253006y. two conductors terminated under a single lug terminal not designed for installation
Aug 28, 2017
Active - Class - 1
Unlawful acts.failure to comply w/an order of the commissioner.in april 12,2017, june 26,2017.three electrical vios was issue to the respondent.the respondent failed to comply w/(nyc) electrical code #250.4,110
Aug 21, 2017
Active
Complaints
- Heating
Heat related
Mar 23, 2013 · Apt NA
Close - Nonconst
Vermin
Feb 24, 2012 · Apt 315
Close - Plumbing
Radiator
Jul 7, 2010 · Apt 3FL
Close - Plumbing
Water supply
Mar 30, 2010 · Apt PH
Close - Heating
Heat related
Apr 2, 2009 · Apt BLDG
Close - Plumbing
Water supply
Oct 7, 2007 · Apt 3
Close - Heating
Heat related
Jan 19, 2006 · Apt BLDG
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Care facility (N2)
- Year built
- 1954
- Floors
- 3
- Residential units
- —
- Building area
- 41,446 ft²
- Lot area
- 192,975 ft²
- Zoning
- PARK
- Community board
- 110
- Council district
- 9
- Block / lot
- 2105 / 1
- Assessed value
- $9,601,650
- Landmark / historic district
- No
Questions about 2930 8 Avenue
Who owns 2930 8 Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Homeless Services.
Does 2930 8 Avenue have violations?
Yes. NYC HPD has recorded 1 housing violations at this property.
Is 2930 8 Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 2930 8 Avenue built?
City records list 1954 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.