roofy

1 Tudor City Place

Manhattan, NY 10017BBL 1-01333-0023Map

Owner of record: Windsor Owners Corp Co Tudor Realtysvcs Corp

1 Tudor City Place is an elevator apartment building built in 1930 in Manhattan, 10017. It has 799 residential units across 26 floors. The owner of record is Windsor Owners Corp Co Tudor Realtysvcs Corp. HPD has recorded 101 housing violations here, most recently on September 10, 2025. 42 of the 50 most recent violations are still open. City tax records listed 9 rent-stabilized apartments here in 2024.

HPD violations
101
DOB violations
108
ECB violations
69
HPD complaints
715

What to know

Concern
4 open Class C

Immediately hazardous issues among recent violations are still open.

Good
Last violation Sep 10, 2025

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

Rent-stabilized units in 2024
9
About 1% of the building's 799 apartments
Down from 14 in 2018

Counts come from owners' rent-stabilization filings shown on NYC Department of Finance tax bills, as extracted by JustFix. They tell you a building has stabilized apartments, not which ones.

Stabilized units by tax-bill year

Think your apartment is stabilized? Request its rent history from HCR (free), then check your renewal with the renewal calculator.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 101

  • C

    Repair the broken or defective plastered surfaces and paint in a uniform color the ceiling in the 1st room from east located at apt 434, 4th story, 3rd apartment from north at east

    Sep 10, 2025 · Apt 434

    Open — Nov sent out
  • C

    Replace or repair the self-closing doors that is missing or defective hinges in the entrance located at apt 434, 4th story, 3rd apartment from north at east

    Sep 10, 2025 · Apt 434

    Open — Nov sent out
  • A

    Cleanse to the satisfaction of this department the grout at south wall in the bathroom located at apt 415, 4th story, 4th apartment from north at east

    May 29, 2025 · Apt 415

    Open — Nov sent out
  • B

    Remove all obstructions and repair all defects in sink in the kitchen located at apt 1139, 11th story, 5th apartment from west at north

    May 6, 2025 · Apt 1139

    Open — Nov sent out
  • B

    Remove all obstructions and repair all defects in wash/basin in the bathroom located at apt 1139, 11th story, 5th apartment from west at north

    May 6, 2025 · Apt 1139

    Open — Nov sent out
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at north wall in the kitchen located at apt 1139, 11th story, 5th apartment from west at north

    May 6, 2025 · Apt 1139

    Open — Nov sent out
  • B

    Properly repair the source and abate the evidence of a water leak at ceiling and north wall in the kitchen located at apt 1139, 11th story, 5th apartment from west at north

    May 6, 2025 · Apt 1139

    Open — Nov sent out
  • B

    Properly repair the source and abate the evidence of a water leak at ceiling in the kitchen located at apt 1139, 11th story, 5th apartment from west at north

    May 6, 2025 · Apt 1139

    Open — Nov sent out
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling in the foyer located at apt 1824, 18th story, 1st apartment from east at south , section ''south''

    Aug 5, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Properly repair or replace the broken or defective ventilation system at west wall in the bathroom located at apt 1824, 18th story, 1st apartment from east at south , section ''south''

    Aug 5, 2024 · Apt 1824

    Open — Nov sent out
Show 40 more ↓
  • B

    Properly repair with similar material the broken or defective caulking around bathtub in the bathroom located at apt 1824, 18th story, 1st apartment from east at south , section ''south''

    Aug 5, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Repair or replace the carbon monoxide detecting device(s). defective in the entire apartment located at apt 1824, 18th story, 1st apartment from east at south , section ''south''

    Aug 5, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Repair or replace the smoke detector defective in the entire apartment located at apt 1824, 18th story, 1st apartment from east at south , section ''south''

    Aug 5, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Properly repair with similar material the broken or defective wood floor in the 2nd room from east located at apt 1824, 18th story, 1st apartment from east at south , section ''south''

    Aug 5, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at west, north and south wall in the bathroom located at apt 1824, 18th story, 1st apartment from east at south , section ''south''

    Aug 5, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Properly repair with similar material the broken or defective wooden floors in the 1st room from east located at apt 1824, 18th story, 1st apartment from east at south

    Aug 4, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at south and west walls in the bathroom located at apt 1824, 18th story, 1st apartment from east at south

    Aug 4, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at east wall in the foyer located at apt 1824, 18th story, 1st apartment from east at south

    Aug 4, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at east wall in the 1st room from east located at apt 1824, 18th story, 1st apartment from east at south

    Aug 4, 2024 · Apt 1824

    Open — Nov sent out
  • C

    Replace or repair the self-closing doors that is missing or defective hinges to door in the terrace located at apt 1824, 17th story, 1st apartment from east at south

    Jun 25, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color ceiling and all walls in the bathroom located at apt 1824, 17th story, 1st apartment from east at south

    Jun 25, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color ceiling and all walls in the private hallway located at apt 1824, 17th story, 1st apartment from east at south

    Jun 25, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Properly repair or replace the broken or defective rubber gasket in door in the terrace located at apt 1824, 17th story, 1st apartment from east at south

    Jun 25, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color ceiling and all walls in the kitchen located at apt 1824, 17th story, 1st apartment from east at south

    Jun 25, 2024 · Apt 1824

    Open — Nov sent out
  • C

    Properly repair with similar material the broken or defective hardwood floor in the 1st room from east located at apt 1824, 17th story, 1st apartment from east at south

    Jun 25, 2024 · Apt 1824

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color ceiling and all walls in the 1st room from east located at apt 1824, 17th story, 1st apartment from east at south

    Jun 25, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Repair or replace the carbon monoxide detecting device(s). missing in the entire apartment located at apt 1824, 18th story, 1st apartment from east at south

    May 31, 2024 · Apt 1824

    Open — Nov sent out
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling, west and south wall in the bathroom located at apt 1824, 18th story, 1st apartment from east at south

    May 31, 2024 · Apt 1824

    Open — Nov sent out
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Apr 1, 2024

    Closed — Violation dismissed
  • C

    Replace or repair the self-closing doors that is missing or defective at stair at north at public hall, 4th story

    Jul 12, 2023

    Closed — Violation closed
  • C

    Replace or repair the self-closing doors that is missing or defective at compactor closet at north at public hall, 4th story

    Jul 12, 2023

    Closed — Violation closed
  • C

    Replace or repair the self-closing doors that is missing or defective at compactor closet at south at public hall, 4th story

    Jul 12, 2023

    Closed — Violation closed
  • A

    Refit door at stair at south at public hall, 4th story

    Jul 12, 2023

    Open — Nov sent out
  • C

    Replace or repair the self-closing doors that is missing or defective at stair at south at public hall, 4th story

    Jul 12, 2023

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling and all walls in the bathroom located at apt 1029, 10th story, 5th apartment from east at south

    Jan 18, 2023 · Apt 1029

    Open — Nov sent out
  • B

    Repair or replace the carbon monoxide detecting device(s). defective in the entire apartment located at apt 1029, 10th story, 5th apartment from east at south

    Jan 18, 2023 · Apt 1029

    Open — Nov sent out
  • B

    Repair or replace the smoke detector defective in the entire apartment located at apt 1029, 10th story, 5th apartment from east at south

    Jan 18, 2023 · Apt 1029

    Open — Nov sent out
  • A

    § 329, m/d law and dept. rules and regs. provide a completed certificate of inspection visits in a proper frame at or near mailboxes, bottom edge of frame between 48-62 inches above floor missing at public hall, 1st story

    Feb 7, 2021

    Open — Nov sent out
  • A

    Post and maintain a proper notice on wall of the entrance story in english and spanish on the availability of the agencys housing information guide. a sample notice can be found at www.nyc.gov/hpd. at public hall, 1st story

    Feb 7, 2021

    Open — Nov sent out
  • C

    Post notice, in form approved by the department, stating the name and location of the person designated by the owner to have key to buildings heating system missing at public hall, 1st story

    Feb 7, 2021

    Open — Nov sent out
  • A

    Post a proper notice of smoke detector requirements, in a form approved by the commissioner, at or near the mail box missing at public hall, 1st story

    Feb 7, 2021

    Open — Nov sent out
  • A

    Post sign on wall of entrance story bearing name, address including apartment number if any, and telephone number of superintendent, janitor or housekeeper. at public hall, 1st story

    Feb 7, 2021

    Open — Nov sent out
  • A

    Post and maintain a proper sign on wall of entrance story showing the registration number assigned by the department and the address of the building. at public hall, 1st story

    Feb 7, 2021

    Open — Nov sent out
  • A

    Post a proper notice of carbon monoxide detecting device requirements, in a form approved by the commissioner, in a common area of a class a multiple dwelling near inspection certificate or provide notice to tenants in a private dwelling.

    Feb 7, 2021

    Open — Nov sent out
  • A

    Post, in a form approved by the commissioner, and maintain a notice in a common area of the building regarding the procedures that should be followed when a gas leak is suspected at public hall, 1st story

    Feb 7, 2021

    Open — Nov sent out
  • B

    Properly repair with similar material the broken or defective corroded metal facade at front areaway, 1st story

    Dec 14, 2019

    Open — Nov sent out
  • B

    Properly repair the broken or defective lock at south service entrance door at public hall, 1st story

    Sep 29, 2019

    Closed — Violation dismissed
  • A

    § 329, m/d law and dept. rules and regs. provide a completed certificate of inspection visits in a proper frame at or near mailboxes, bottom edge of frame between 48-62 inches above floor , frame missing at public hall, 1st story

    Oct 19, 2018

    Closed — Violation dismissed
  • A

    Paint with light colored paint to the satisfaction of this department at ceiling of mail room at public hall, 1st story

    Oct 15, 2018

    Open — Nov sent out
  • A

    § 329, m/d law and dept. rules and regs. provide a completed certificate of inspection visits in a proper frame at or near mailboxes, bottom edge of frame between 48-62 inches above floor frame missing at public hall, 1st story

    Oct 15, 2018

    Open — Nov sent out

DOB building violations · 108

  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 3, 2024

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 15, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 15, 2021

    Dob violation - resolved
  • Construction other optional

    Motorcycle impacting sidewalk shed

    Jun 4, 2021

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
Show 40 more ↓
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 1, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 1, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 1, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 1, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 1, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 1, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 1, 2016

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 27, 2016

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 27, 2016

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 27, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 17, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 17, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 17, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 17, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 17, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 17, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 17, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    This pvt replaces pvt 506717

    Mar 21, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 21, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 21, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 21, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 21, 2014

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 21, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    This pvt replaces pvt 506715

    Mar 21, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 19, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 19, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 19, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 19, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 18, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 18, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 18, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 9, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 9, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 9, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 9, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 9, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 9, 2012

    Dob violation - resolved

ECB violations · 69

  • Class - 2

    Observed in why biscuits & bath animal facility on the ground floor no sprinkler system in place which contrary to code refer to section bc 903.2.2.2; bc 903.2.2.2, comply with code

    Mar 18, 2024

    Resolve
  • Class - 2

    At the time of inspection i observed 8 ft sleeve to be used on the outrigger beams not complied with manufacturer specs on exposure#2 north west courtyard and exposure #4 south side. stop all use of suspended

    Nov 14, 2022

    Resolve
  • Class - 1

    Work does not conform to p/e/ approved design drawings at time of inspection of a 26 story buildingunder facade renovation i observed a materials hoist at exp 1 with the following conditions wire rioe attached

    Nov 25, 2019

    Resolve
  • Class - 1

    3314.1=failure to maintain supproted scaffold in code compliant at tim eof inspection fo a 26 story buidling under facade restoration i observed supproted scaffold in ,multiple location with the followwing cond

    Nov 25, 2019 · Penalty $2,500

    Resolve
  • Class - 1

    Failure to mainatin display on site documents required by chapter 33 at tim eof inspection of a 26 tsory building under facade renovation i observed c hook and outrigger beam suspended scaffolds with parapet cl

    Nov 25, 2019

    Resolve
  • Class - 1

    Work does not cofnorm to approved construction documenst and or approved amendments at time of insepction fo a 26 story building under facade restortaioni observed the following conditiosn no caz established on

    Nov 25, 2019 · Penalty $2,500

    Resolve
  • Class - 1

    Work does not con form to approved construction documents and or approved amendments at time fo inspection of a 26 story building under facade restoration i observed teh folllowing conditiona platform hanging f

    Nov 25, 2019 · Penalty $2,500

    Resolve
  • Class - 1

    Work does not conform to p.e. approved deisgn armings at time of inspection of a 26 story building under facade restortaion i observed suspended scaffolds back to wall .i observed th efollowing conditions ancho

    Nov 25, 2019

    Resolve
  • Class - 1

    Work does not conform to appoved construction documents and or approved amendments at time fo inspection fo a 26 story building under facade restoration i observed supported scaffold at exp 1 from the sidewlak

    Nov 25, 2019 · Penalty $625

    Resolve
  • Class - 1

    3314.1=failure to miantain suspended scaffold in code compliant at time of inspection of a 26 story building under facade resporation i observed suspended scaffold in multiple exposures with the following condi

    Nov 25, 2019

    Resolve
Show 40 more ↓
  • Class - 1

    3301.2=failure to nstistute.maintain sfatey measures at time of inspection of a 26 story building under facade restoration i observed the following conditions mateirals equipment such as scaffold frames stacked

    Nov 25, 2019 · Penalty $625

    Resolve
  • Class - 1

    Housekeeping note at time of inspection at a 26 stroy building on an actiev job site i observed inadequate housekeeping conissting of large amount of debris and construction materials being stoved and scattered

    Aug 19, 2019 · Penalty $625

    Resolve
  • Class - 1

    3306.9.12.1:holes on the floor (longer than 2") note at time of inspection of a 26 stroy building actiev job site i observed holes/penetrations longer that 2 inches at the attic a trip waterproofing is taking

    Aug 19, 2019

    Resolve
  • Class - 2

    Failure to post or distribute notice of tenant proetction plan note at time of inspection i observed no tenenat proettcion plan p¢osted failure to post or distribute tenant protetcion plan in an occupied buildi

    Aug 19, 2019

    Resolve
  • Class - 2

    Failure to post or distribute safe construction bill of right note:failure to post safe construction bill of rights job #123108216 pertaining to an occupied building with mean methods of construction to an occu

    Aug 19, 2019

    Resolve
  • Class - 2

    Pedestrian protection does not meet code spefication 3307.6.5.3.note at time of inspection observed aheazy duty sidewalk shed at exposure one and exposure foure with permit #140580057 pedestrian walking under t

    Aug 19, 2019

    Resolve
  • Class - 1

    Failure to maintain and institute safety measures and temporary construction note at time of my inspection at a 26 tory building working progress at expo 1,2,3 and 4 i observed no control access zone were provi

    Aug 19, 2019

    Resolve
  • Class - 1

    3314.1:supported scaffold does not meet building code specifications tsop work note at time of inspection on a 26 story building i observed supported scaffold installed at expo 3 and 4 there were no guardrails

    Aug 19, 2019

    Resolve
  • Class - 2

    No storage on shed note at time of inspection i observed site walk shed in place at expo 1 main entrance of the building being used for storage and equipment storage of the building allowed on top of sit walk s

    Aug 19, 2019 · Penalty $2,400

    Resolve
  • Class - 1

    Work does not conform to approved comstruction documents or approved amendments note at time of my inspection of 26 stroy building upon further review i observed that there was no mention of electrical c hooks

    Aug 19, 2019

    Resolve
  • Class - 1

    3301.2:control access zone note atime of inspection on a 26 stroy building acove job site i observed open area unprotected near leading edge on expo 4 with no control acess zone which is (causing) a hazardous

    Aug 19, 2019

    Resolve
  • Class - 2

    Failure to notify the department prior to commencement of work that required test protection plan note the owner shall notify the department writing at least 72 hours prior to commencement any work that require

    Aug 19, 2019

    Resolve
  • Class - 1

    Failure to comply w/the comm's order contained in nov's 35159070h;35159446r & 35159447z issued on 3-16-16 & to file a c of c pursuant to 28-201.1;28-204.4 & 1rcny 102-01. nov 35159070h electrical work w/o a per

    Jul 5, 2016 · Penalty $800

    Resolve
  • Class - 1

    Unlawful acts. failure to comply w/an order of the commissioner. on 10/30/15. a electrical violation was issue to the respondent. the respondent failed to comply w/the local laws #27-3018(b),27-3018(b),250.70,

    Mar 16, 2016 · Penalty $800

    Resolve
  • Class - 1

    Sec. 250.30 separately derived systems. separately derived systems as covered in 250.20(a) or (b) shall be grounded as specified in 350.30(a). cellar boiler room,co. generation systems: no water main ground con

    Oct 30, 2015

    Resolve
  • Class - 1

    Electrical work w/o a permit. cellar boiler room co. generation systems: 3-75kw generators,3 feeders 400mcm,3-400amp disconnect. not on file. please note. remedy: obtain permit this is not a final inspection.

    Oct 30, 2015 · Penalty $1,600

    Resolve
  • Class - 1

    Electrical work does jot conform to approved submitted document/amendment. cellar boiler room co. generation systems: no advisory board approval provided. please note. the existing service equipment are over

    Oct 30, 2015

    Resolve
  • Class - 1

    Failure to provide site safety manager.noted: at time of inspection there was no site safety manager as required.the last entree was on 2-5-13.inspection was from 1pm until 3pm.site safety failed to carry out

    Feb 6, 2013 · Penalty $1,200

    Resolve
  • Class - 2

    28-105-12.2supported scaff contrary to plans.noted:at time of inspect ion supported scaffold was contrary to approved plans.pipe scaffold was erected on roof wrapping around bulkhead on the south side support b

    Feb 6, 2013

    Resolve
  • Class - 1

    Bc3310.6)failure to provide designated site safety manger.examination of site safety logs show that various site safety managers have recorded their entries.dept records show that no pw2 has been filed for this

    Jul 7, 2011

    Resolve
  • Class - 2

    Sec. bc3310.6. failure to provide designated site safety manager at time of inspection observed (site) safety manager log book recorded w/various site safety managers there is no set designated site safety

    Mar 21, 2011

    Resolve
  • Class - 2

    Sec. bc3310.6. failure to provide designated site - safety manager. attime of inspection observed site safety manager log book recorded w/various site safety managers. there is no set designated site safety

    Mar 21, 2011 · Penalty $800

    Resolve
  • Class - 1

    Partial swo - issued pursuant to 28-207.2 and posted at premises. workdoes not conform to approved construction documents and/or approved amendments. noted: at time of inspection scaffold erected along 41 st.

    Mar 21, 2011 · Penalty $500

    Resolve
  • Class - 1

    Unlawfully continued work while on notice of a stop work order. (suspended scaffold relocated to exposure #4 from exposure #1) rem: comply with stop work order.

    Jul 21, 2009 · Penalty $2,400

    Resolve
  • Class - 2

    Failed to notify dept/obtain permit prior to use/inst of c-hooks in connection w/suspended scaffold. expired c-hook notification. remedy: notify the dept.

    Jul 8, 2009 · Penalty $800

    Resolve
  • Class - 1

    Licensed rigger failed to ensure scaffold worker met minimum requirements. (worker on two pt suspended scaffold w/no certificate of fitness). remedy: comply w/code.

    Jul 8, 2009 · Penalty $1,600

    Resolve
  • Class - 1

    Inadequate safety measures. operation of hoisting equipment in unsafe manner. (rails missing on suspended scaffold platform). remedy: discontinue use.

    Jul 8, 2009

    Resolve
  • Class - 2

    Working w/o a plumbing permit in apt 614: upon inspection at above location subject was performing unlicensed plumbing work. he was working on the radiator in apt 614. he installed new fitting w/mixture of

    Jul 8, 2009

    Resolve
  • Class - 1

    Failure to maintain building wall(s) or appurtenances. noted: @ apt 1738 on the 17th fl a window pane full onto 1 ave damaging a black chrysler jeep. remedy: make all neccessary repairs, maintain bldg

    Sep 25, 2008 · Penalty $1,000

    Resolve
  • Non-hazardous

    Sec. 27-1020. failure to post dot permit for street/sidewalk closing (permit expired). at time of inspection there is a large closure on 1stave w/sidewalk shed in it w/a scaffold tower on shed. no updated dot

    Apr 8, 2008 · Penalty $800

    Resolve
  • Non-hazardous

    Sec. 27-146. approved plans not available for inspection. at time of inspection no approved plan for pipe scaffold approx 70' high located in road closure on sidewalk shed on 1st ave. remedy: stop use of

    Apr 8, 2008 · Penalty $800

    Resolve
  • Non-hazardous

    Work w/o a permit. upon inspection a sidewalk shed is erected on 1st ave approx 50 in length w/o a permit. a permit is shown for shed on tudor city pl only. remedy: stop all work (exterior on 1st ave) remove

    Apr 8, 2008

    Resolve
  • Hazardous

    Failure to post dot permit for street closing.as noted:upon inspection1 lane closed on 1st ave front of above address.there is no dot permitposted.at time of inspection facade work in progress.remedy:post permi

    Sep 10, 2007

    Resolve
  • Non-hazardous

    44b10.44-governor noise

    Apr 16, 2007

    Resolve
  • Non-hazardous

    01l10,02l10.01-alarm bell does not ring when run/stop switch pulled.02-alarm bell-defective.

    Apr 16, 2007

    Resolve
  • Non-hazardous

    Work contrary to approved dob plans & application. observed hoisting equipment on bldg that was not on plans.

    Mar 27, 2007 · Penalty $500

    Resolve
  • Non-hazardous

    Failure to post sign on shed as required by local law 33/91.as noted:sidewalk erected on e. 40th st.w/no permit holder sign posted.no activity upon inspec.permit # not posted on shed located on 1st ave.

    Oct 16, 2006 · Penalty $200

    Resolve
  • Hazardous

    Failure to have site safety manager present as required. noted:at time of inspection men were working at east elevation of a suspended scaffold on the exterior of the bldg at the 21-22 fl.

    Apr 28, 2006 · Penalty $2,000

    Resolve
  • Non-hazardous

    No design drawing at time of insp. alt 2 #101902292. at insp. out rigging two point suspension scaffold graded on east face of bldg. no certificate or design drawing provided for insp. remedy: "stop all work "

    Feb 8, 2006 · Penalty $500

    Resolve
  • Hazardous

    No permit for sidewalk shed. upon inspection at the above property. sidewalk shed erected at 1st ave dept record shows no permit issued. remedy: obtain permit as per code.

    Feb 7, 2006 · Penalty $200

    Resolve

Complaints

  • Paint/plaster

    Wall

    Sep 2, 2026 · Apt 37

    Open
  • Water leak

    Heavy flow

    Jul 12, 2026 · Apt 923

    Close
  • Water leak

    Slow leak

    Jul 11, 2026 · Apt 923

    Close
  • Unsanitary condition

    Pests

    May 26, 2026 · Apt A18

    Close
  • Door/window

    Door

    Apr 2, 2026 · Apt 1824

    Close
  • Door/window

    Door frame

    Mar 12, 2026 · Apt 1824

    Close
  • Heat/hot water

    Apartment only

    Feb 8, 2026 · Apt 818

    Close
  • Unsanitary condition

    Pests

    Feb 8, 2026 · Apt 923

    Close
  • Heat/hot water

    Apartment only

    Jan 30, 2026 · Apt 1504

    Close
  • Plumbing

    Radiator

    Jan 30, 2026 · Apt 1504

    Close
Show 40 more ↓
  • Heat/hot water

    Apartment only

    Jan 29, 2026 · Apt 331

    Close
  • Heat/hot water

    Apartment only

    Jan 27, 2026 · Apt 1504

    Close
  • Heat/hot water

    Entire building

    Jan 25, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 26, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 23, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 23, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 10, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 9, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Apartment only

    Dec 5, 2025 · Apt 235

    Close
  • Unsanitary condition

    Pests

    Nov 14, 2025 · Apt 415

    Close
  • Heat/hot water

    Entire building

    Nov 14, 2025 · Apt 2505

    Close
  • Unsanitary condition

    Pests

    Oct 19, 2025 · Apt 2139

    Close
  • Unsanitary condition

    Mold

    Sep 5, 2025 · Apt 434

    Close
  • Door/window

    Door

    Jun 27, 2025 · Apt 1824

    Close
  • Door/window

    Door

    Jun 27, 2025 · Apt 1824

    Close
  • Paint/plaster

    Wall

    May 31, 2025 · Apt 1018

    Close
  • Unsanitary condition

    Pests

    May 28, 2025 · Apt 415

    Close
  • Unsanitary condition

    Pests

    May 28, 2025 · Apt 415

    Close
  • Unsanitary condition

    Mold

    May 28, 2025 · Apt 415

    Close
  • Paint/plaster

    Wall

    May 28, 2025 · Apt 415

    Close
  • Unsanitary condition

    Pests

    Apr 28, 2025 · Apt 415

    Close
  • Paint/plaster

    Wall

    Apr 28, 2025 · Apt 415

    Close
  • Unsanitary condition

    Mold

    Apr 28, 2025 · Apt 415

    Close
  • Door/window

    Door

    Apr 28, 2025 · Apt 415

    Close
  • Flooring/stairs

    Floor

    Apr 28, 2025 · Apt 415

    Close
  • Unsanitary condition

    Pests

    Apr 28, 2025 · Apt 415

    Close
  • Paint/plaster

    Wall

    Apr 28, 2025 · Apt 415

    Close
  • Paint/plaster

    Ceiling

    Apr 25, 2025 · Apt 1139

    Close
  • Door/window

    Window frame

    Apr 25, 2025 · Apt 1139

    Close
  • Water leak

    Slow leak

    Apr 25, 2025 · Apt 1139

    Close
  • Plumbing

    Toilet

    Apr 25, 2025 · Apt 1139

    Close
  • Paint/plaster

    Wall

    Apr 25, 2025 · Apt 1139

    Close
  • Plumbing

    Basin/sink

    Apr 25, 2025 · Apt 1139

    Close
  • Unsanitary condition

    Pests

    Mar 24, 2025 · Apt 415

    Close
  • Paint/plaster

    Wall

    Mar 24, 2025 · Apt 415

    Close
  • Paint/plaster

    Wall

    Mar 24, 2025 · Apt 415

    Close
  • Heat/hot water

    Entire building

    Jan 4, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 23, 2024 · Apt BLDG

    Close
  • Flooring/stairs

    Floor

    Jul 31, 2024 · Apt 1824

    Close
  • Paint/plaster

    Wall

    Jul 31, 2024 · Apt 1824

    Close

Sales history

DatePriceTypeUnits
Sep 14, 2026$330,000Coops - elevator apartments—
Sep 3, 2026$322,500Coops - elevator apartments—
Aug 31, 2026$310,000Coops - elevator apartments—
Aug 24, 2026$322,500Coops - elevator apartments—
Aug 19, 2026Non-market transferCoops - elevator apartments—
Aug 12, 2026$285,000Coops - elevator apartments—
Aug 3, 2026$337,000Coops - elevator apartments—
Jul 8, 2026Non-market transferCoops - elevator apartments—
Jun 25, 2026$295,000Coops - elevator apartments—
Jun 17, 2026$560,000Coops - elevator apartments—
Jun 15, 2026$290,000Coops - elevator apartments—
Jun 3, 2026Non-market transferCoops - elevator apartments—
May 28, 2026$525,000Coops - elevator apartments—
May 27, 2026$275,000Coops - elevator apartments—
May 14, 2026$545,000Coops - elevator apartments—
May 11, 2026Non-market transferCoops - elevator apartments—
Apr 27, 2026$523,000Coops - elevator apartments—
Mar 12, 2026$520,000Coops - elevator apartments—
Feb 18, 2026Non-market transferCoops - elevator apartments—
Jan 15, 2026$269,000Coops - elevator apartments—

Building details

Building type
Elevator apartment building (D4)
Year built
1930
Floors
26
Residential units
799
Building area
418,312 ft²
Lot area
21,330 ft²
Zoning
R10
Community board
106
Council district
4
Block / lot
1333 / 23
Assessed value
$47,042,550
Landmark / historic district
Tudor City Historic District

HPD registration #102658, last renewed Aug 23, 2025.

Questions about 1 Tudor City Place

Who owns 1 Tudor City Place?

The owner of record in NYC Department of City Planning PLUTO data is Windsor Owners Corp Co Tudor Realtysvcs Corp.

Does 1 Tudor City Place have violations?

Yes. NYC HPD has recorded 101 housing violations at this property.

Is 1 Tudor City Place rent stabilized?

NYC Department of Finance tax bills listed 9 rent-stabilized units here in 2024 (about 1% of its 799 apartments). To confirm a specific apartment, request its rent history from NYS Homes and Community Renewal.

When was 1 Tudor City Place built?

City records list 1930 as the year it was built.

How many apartments are in 1 Tudor City Place?

It has 799 residential units and 811 units in total.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.