227 West 61 Street

Manhattan, NY 10023BBL 1-01154-0108Map

Owner of record: 61 Owner LLC

227 West 61 Street is a school building built in 1927 in Manhattan, 10023. The owner of record is 61 Owner LLC. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
51
ECB violations
96
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 51

  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 13, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 1, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Residential elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Jun 1, 2016

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2012 inspection report

    May 15, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 6, 2014

    Dob violation - resolved
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2010 inspection report

    Dec 13, 2011

    Dob violation - dismissed
Show 40 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 29, 2011

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 13, 2011

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 13, 2011

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 13, 2011

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 13, 2011

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 7, 2009

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 28, 2008

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Dec 4, 2007

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Oct 31, 2007

    Vw*-violation - work w/o permit dismissed
  • Construction other optional

    C-construction other optional

    Oct 31, 2007

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Oct 31, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 10, 2006

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 6, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 10, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 10, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 1996

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 17, 1995

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Jan 20, 1995

    Vp-violation unserved ecb-active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - active
  • Elevator elevatoroptional

    1

    Jun 28, 1993

    Dob violation - active

ECB violations · 96

  • Class - 2

    Exit door not self-closing properly. at the time of inspection at 2nd floor near rm-no 212 one exit door at 1st floor near rm 123 one exit door not self-closing properly. at 1st floor cafeterior in main entranc

    Apr 11, 2025 · Penalty $625

    Resolve
  • Class - 2

    Observed in west end secondary school on the second floor in the staff toilet room 231 sink not working no water coming out of faucet which contrary to code sections pc 301.4 and pc 416.5, repair and/or replace

    Nov 13, 2024 · Penalty $3,125

    Active
  • Class - 2

    Reissue 35491026p failure to maintain bldg in code compliant manner:lack of emergency lighting for exits,exit discharges & public corridors per bc1006.1;27-345 note at 1st fl auditorium having no emergency ligh

    Mar 8, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner no fire stoppingper bc712.3/27-345.noted:at cellar gas and electric meter rooms fire stopping missing/none throughout in various locations.remedy:provide ma

    Apr 14, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Failuer to maintain building in code compliant manner.noted:at(2nd fl)gym and (1st fl)cafeteria doors in disrepair/cracked.remedy:repair andor replace.

    Apr 14, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.lack of emergency lighting for exits,exit dishcarges and public corridors per bc1006.127-542.noted:at(1st fl)auditorium with having no emergency lighting in

    Apr 14, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue#35317156j.failure to maintain building in code compliant manner.no fire stopping.per bc712.3,27.345 at cellar meter and mechanical rooms.remedy:provide and maitain adequate fire stoppage.

    Oct 7, 2019 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue #35235929n failure to maintain building in code compliant manner.at cellar gas meter room,storage of school maintenance. equipment and materials. remedy: repair/replace comply with code.

    Feb 13, 2018

    Resolve
  • Class - 2

    Reissue 352359275 failure to maintain building in code compliant manner no fire stopping per bc 712. 3.27.345 at cellar electrical room no fire stopping over door.remedy: provide maintain fire stopping

    Feb 13, 2018

    Resolve
  • Class - 2

    28-301.1 reissue #35235928l at cellar gas meter room no ventilation for gas meter room. rmdy: comply with notice of violation.

    Feb 13, 2018

    Resolve
Show 40 more ↓
  • Class - 2

    B-206,2. 28-31.1. re-issued vio # 34779613x for failure to provide ventilation to gas meter room per p115.6(1968 code),fgc appendix e/(e4)(2014 code). noted: at gas meter room,bsmt no fresh air intake was obser

    Mar 31, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: storage consisting of paints, several cans & gallons was observed at gas meter room @ bsmt level. remedy: repair &/or replace.

    Mar 31, 2017

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:noted:water penetration throughout roof was observed at 3 flr in the room 312,321 and at south corridor.concealed water leak from celing causing damage of d

    Mar 31, 2017 · Penalty $500

    Resolve
  • Class - 2

    Re-issued vio # 35147653l for failure to maintain bldg in code compliant manner. no fire stopping per bc 712.3' 27-345. noted: inside electrical room above door at bsmt level is lacking of fire stopping. remedy

    Mar 31, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg: missing fire stopping. noted: missing fire stopping from wall of electrical room b-42 & on others side of same wall in passageway below to stairs to 1st fl. remedy: comply w/notice of

    Sep 15, 2016 · Penalty $1,250

    Resolve
  • Class - 2

    Reissued ecb 35093858y altered/changed building occupied w/o a valid cert of occupancy. reissued ecb #35019150n altered, changed bldg occu pied w/o a valid cert of occupancy bldg altered under job #102278269.

    Sep 16, 2015

    Resolve
  • Class - 2

    Re-issued ecb #35093860n.failure to maintain building wall(s) or appurtenances exterior.failure to maintain building wall(s) or appurtenances roof leaking at several areas into 3rd fl. hallway and classroom.rem

    Sep 16, 2015 · Penalty $500

    Resolve
  • Class - 2

    Reissued ecb #35093858y failure to maintain building in code compliantmanner no fire stopping per bc 7123; 27-345. reissue ecb 35019453k failure to maintian bldg in code compliant manner no fire stopping per bc

    Sep 16, 2015

    Resolve
  • Class - 2

    27-776 reissued ecb 35093857m fresh air in gas meter room rs 16p115.4 and gtppn 1 of 1964. 27-776 reissue ecb #35019455y fresh air in gas meter room no fresh air gas meter room in basement.rmdy:comply w/code

    Sep 16, 2015

    Resolve
  • Class - 2

    Re-issue ecb #35019150n altered/changed bldg occupied w/o a valid cert of occupancy bldg altered under job #102278269. no new certif of occupancy issued. remedy: obtain valid c of o or discontinue illegal occup

    Apr 2, 2014

    Resolve
  • Class - 2

    Re-issue ecb #35019453k failure to maintain bldg in code compliant manner no fire stopping per bc712.3; 27-345 inside electrical rm above door @ basement level is lacking fire stopping. rem:provide/maintain fir

    Apr 2, 2014

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances. roof leaking atseveral areas into 3rd fl hallway & classroom. remedy: maintain exterior of building

    Apr 2, 2014 · Penalty $500

    Resolve
  • Class - 2

    27-776 reissue ecb #35019455y fresh air in gas meter rm no fresh air in gas meter room in basement. remedy: provide fresh air in gas meter room.

    Apr 2, 2014

    Resolve
  • Class - 2

    Reissue: 34941402z. the gas meter room is lacking fresh air ventilation at the basement level. remedy: provide/maintain fresh air ventilation in gas meter room.

    May 6, 2013

    Resolve
  • Class - 2

    Reissue: 34941404m. the electrical room is lacking fire stopping abovethe entry door at the basement level. remedy: provide/maintain fire stopping.

    May 6, 2013

    Resolve
  • Class - 2

    Reissue: 34941403k. altered bldg occupied w/o a valid c/o required by job #102278269. remedy: obtain c/o.

    May 6, 2013

    Resolve
  • Class - 2

    The corridor/hallway flr is rising causing a tripping hazard located adjacent to room b-48. remedy: repair/replace flr.

    May 6, 2013

    Resolve
  • Class - 2

    Reissue # 34921718r. gas meter room & electrical room are being used for storage of maintenance & construction material. remedy: remove all storage from gas meter & electrical rooms.

    Mar 6, 2012

    Resolve
  • Class - 2

    27-766. reissue # 34921715l. no fresh air vent in gas meter room. remedy: provide fresh air vent.

    Mar 6, 2012

    Resolve
  • Class - 2

    Reissue # 34921714j. bldg altered under job # 102278269 & no new c/o issued. basement is being occupied without a valid c of o. (34 to 191 persons) remedy: obtain valid c of o or discontinue illegal occupancy.

    Mar 6, 2012

    Resolve
  • Class - 2

    Holes in wall of electrical room above door at pipe penetration. remedy: provide/maintain fire stopping.

    Mar 6, 2012

    Resolve
  • Class - 1

    3314 supporterd scaffold does not meet dob specifications missing toe boards missing netting do not remove equipment make repairs call for reinsp rem: comply w/ code partial stop work order on supported scaffol

    Nov 3, 2011

    Resolve
  • Class - 2

    Gas meter room service at bsmt lvl gas meter room w/ storage of various maintenance and construction material rem; remove all items maintaingas meter room storage free

    Jul 26, 2011

    Resolve
  • Class - 2

    Partial obstruction at 1fl entry partial corridor obstruction w/ furniture tables chairs boxes rem; remove all items maintain corridor width clear

    Jul 26, 2011

    Resolve
  • Class - 2

    Reissue #34779614h altered bldg occupied w/o valid c/o bsmt altered under job#102278269 alt1 occupied w/o a valid cert of occupancy classrooms offices and restrooms rem: obtain valid cert of occupancy

    Jul 26, 2011

    Resolve
  • Class - 2

    27-766 reissue #34779613x no fresh air vent at gas meter room at bsmt lvl gas meter room no fresh air ventilation rem: provide fresh air vent

    Jul 26, 2011

    Resolve
  • Class - 2

    Reissue #34195102p no place of assembly certificate of operation. no p/a issued for gym #153,drama studio #157,cafeteria #173. no bases for occupancy limits posted. remedy: obtain place of assembly c of o.

    Jul 26, 2011

    Resolve
  • Class - 3

    Failure to maintain bldg in code-compliant manner. defects noted: 3rd flr water damage ceiling tiles at various locations on 3rd flr. remedy: repair/replace.

    Jun 14, 2011

    Resolve
  • Class - 2

    Failure to comply w/ commissioners order to file a cert of correction for nov#34878547r.rem:file cert of correction.

    Jan 20, 2011

    Resolve
  • Class - 2

    Failure to comply w/ commissioners order to file a cert of correction for nov#34879257r.rem:file cert of correction.

    Jan 20, 2011

    Resolve
  • Class - 1

    Failure to provide unobstructed exit passageway.defect noted:@ time of inspection @ 3story stairwell there is bags of roofing material & workers clothes on stairwell landing obstructing egress.rem:remove obstru

    Nov 12, 2010 · Penalty $1,200

    Resolve
  • Class - 1

    Failure to safeguard all persons & property affected by construction operations.defects noted:@ time of inspection men working on roof chipping roof membrane & concrete for vent installation/repair causing conc

    Nov 12, 2010 · Penalty $2,400

    Resolve
  • Class - 1

    Failure to maintain bldg wall(s) or appurtenances. defects noted: at time of inspection there is spalling brick at exp 3 and spalling stucco at exp 2. missing mortar joints observed at exp 1. parapet walls

    Oct 6, 2010 · Penalty $1,000

    Resolve
  • Class - 2

    Missing fresh air intake inside gas meter room.rem:install f.a.i

    Aug 17, 2010 · Penalty $500

    Active
  • Class - 2

    Altered bldg occupied w/o a current cofo 102278269 exp 8-11-2004 noted:bldg occupied as public school.bsmt level# of persons has changed from 34 to approx 200.rem:obtain valid cofo

    Aug 17, 2010 · Penalty $500

    Active
  • Class - 1

    Operation of place of assembly w/o a current p.a. permit appl#1046355441 gym disapproved approx 150 persons.rem:obtain permit!

    Aug 17, 2010 · Penalty $1,600

    Active
  • Class - 1

    Operation of place of assembly w/o a currrent p.a. permit appl#1046355450 drama studio disapproved aaprox 100 person seated.rem:obtain permit

    Aug 17, 2010 · Penalty $1,600

    Active
  • Class - 1

    Operation of place of assembly w/o a current p.a. permit.appl#104635469 cafeteria disapproved. approx 170 person seating.rem:obtain permit

    Aug 17, 2010 · Penalty $1,600

    Active
  • Class - 2

    Reissue: 34711729r brick foundation wall has water damage in sprinklerroom at basement level. remedy: repair exterior foundation wall.

    May 20, 2009

    Resolve
  • Class - 2

    No file stopping per bc 713.3 - 27-345 holes in walls of boiler room & electrical room. remedy: provide fire stopping at above locations.

    May 20, 2009

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1927
Floors
3
Residential units
—
Building area
75,325 ft²
Lot area
22,525 ft²
Zoning
R8
Community board
107
Council district
6
Block / lot
1154 / 108
Assessed value
$14,121,900
Landmark / historic district
No

Questions about 227 West 61 Street

Who owns 227 West 61 Street?

The owner of record in NYC Department of City Planning PLUTO data is 61 Owner LLC.

Does 227 West 61 Street have violations?

NYC HPD has no housing violations on record for this property.

Is 227 West 61 Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 227 West 61 Street built?

City records list 1927 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.