roofy

515 West 42 Street

Manhattan, NY 10036BBL 1-01071-0023Map

Owner of record: R.born Assoc.

515 West 42 Street is a hotel built in 1962 in Manhattan, 10036. The owner of record is R.born Assoc.. HPD has recorded 10 housing violations here, most recently on April 29, 2026. 1 of the 10 most recent violations are still open.

HPD violations
10
DOB violations
66
ECB violations
54
HPD complaints
35

What to know

Concern
1 open Class C

Immediately hazardous issues among recent violations are still open.

Good
Last violation Apr 29, 2026

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 10

  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Apr 29, 2026

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 17, 2025

    Closed — Violation dismissed
  • C

    Provide hot water at all hot water fixtures in the room located at b-room 371, 3rd story

    Oct 26, 2023 · Apt 371

    Closed — Violation closed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Mar 15, 2023

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 3, 2022

    Closed — Violation dismissed
  • C

    Abate the infestation consisting of mice in the room located at b-room 728, 7th story, 1st b-room from north at east

    May 20, 2021 · Apt 728

    Open — Notice of issuance sent to tenant
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Oct 25, 2019

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 6, 2017

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Oct 26, 2016

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Feb 3, 2015

    Closed — Violation dismissed

DOB building violations · 66

  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 9c technical report by 2/21/2024

    Feb 22, 2024

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 24, 2024

    Dob violation - dismissed
  • Construction other optional

    Failure to maintain building in code complaint manner. throughout parking garage 1st & 2nd levels, observed areas of spalled concrete from concrete slab (floor & ceiling) exposing rusted rebar. at both vehicle access ramps & throughout 2nd level noted several heavily rusted & deteriorated structural steel beams. nyspe report request

    Nov 16, 2023

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 10, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 10, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 10, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 10, 2020

    Dob violation - resolved
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
Show 40 more ↓
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 3, 2017

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 6, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 6, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 6, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 6, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 26, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 26, 2012

    Dob violation - resolved
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Jan 1, 2012

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 4, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 4, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 4, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 4, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 4, 2011

    Dob violation - resolved
  • Construction other optional

    C-construction other optional

    Apr 1, 2010

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 22, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 22, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 22, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 22, 2008

    Dob violation - resolved
  • Emergency power none

    Ll2604e-emergency power none

    Mar 31, 2008

    Dob violation - dismissed
  • Facade facade required

    L1198-local law 11/98 - facade facade required

    Jun 25, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 29, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 29, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 29, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 29, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 18, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 18, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 18, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 18, 2006

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed

ECB violations · 54

  • Class - 1

    Class 1 c/u: in-car stop switch damaged/inoperative, as per asme a17.1 2.26.2.21. remedy: repair/replace in-car stop switch and restore to proper operating condition. email elevator division at [email protected]

    Sep 28, 2026 · Penalty $1,250

    Active
  • Class - 1

    Class 1 cease use: door zone restrictor device found inoperative as per code asme a17.1/csa b44 - section 2.26.5. elevator car doors can be opened when the car is not within the designated door zone, creating a

    Sep 28, 2026 · Penalty $1,250

    Active
  • Class - 2

    Class 2: top-of-car inspection switch malfunctioning; intermittently fails to return to normal operation, as per asme a17.1 2.26.1.4. remedy: repair or replace top-of-car inspection switch and restore proper no

    Sep 28, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. observed security chairs obstructing passageways/hallways. located throughout the building. potential fire hazard., repair and/or replace

    Oct 14, 2025 · Penalty $6,250

    Active
  • Class - 2

    Observed at 8th floor roof level, sheet metal covering to stand pipe valve posing a risk of a severe laceration., repair and/or replace

    Nov 18, 2024

    Resolve
  • Class - 2

    Exit door not self-closing. observed non self closing doors throughout building. incase of fire this is a hazard conidition., repair/replace door

    Nov 18, 2024

    Resolve
  • Class - 2

    Observed at basement fernco coupling and jim cap installed on 2 inch waste pipe also 2 inch pipe being supported with electrical cord. as per 308 of the plumbing code 308.4 structural attachment. hangers and an

    Nov 18, 2024

    Resolve
  • Class - 1

    I observed on the 6th floor in the bathroom next to the "b" stairs the electrical panels open with exposed and energized wiring and parts with no covers to protect against shock hazard. photos taken, comply wit

    Nov 18, 2024 · Penalty $1,600

    Resolve
  • Class - 1

    Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed hole penetrations throughout building. incase of emergency this is a fir

    Nov 18, 2024 · Penalty $2,500

    Resolve
  • Class - 2

    I observed in the 6th floor bathroom, the elevator motor room and the main electrical room the failure to provide gfci protection as required. photos taken., install gfc1 protection

    Nov 18, 2024 · Penalty $1,200

    Resolve
Show 40 more ↓
  • Class - 1

    I observed in the kitchen/pantry in the rear building a defective extension cord in use and an extension passing across an open doorway to supply power to the appliances, also noted in the main electrical room

    Nov 18, 2024 · Penalty $400

    Resolve
  • Class - 1

    Failure to maintain building in code compliant manner. noted throughout parking garage 1st & 2nd levels, several areas of spalled concrete from ceiling & floor concrete slab, exposing corroded rebar. at both ve

    Nov 16, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted at exp#3 (west 43rd st side) facade with missing bricks above lintel of vehicle access gate. additionally, at exp#4 (east) roof level, brick wall adj

    Nov 16, 2023

    Resolve
  • Class - 2

    No emergency lighting from 2nd fl to 7th fl, corridors of both buildings. (emergency lighting is required to illuminate and identify hallways, stairwells and exits to facilitate a safe / orderly evacuation)., r

    Aug 2, 2023

    Resolve
  • Class - 2

    Observed residential gas flex installed on commercial dryers. as per fgc 411 1. rigid metallic pipe and fittings. space heaters and water heaters within dwelling units shall be connected using rigid piping and

    Jan 13, 2023 · Penalty $312

    Resolve
  • Class - 2

    Observed. at cellar level,electrical rm, storage rms near gas meter, gas meter area, also storage closet through the building and staircase a,b,c,& d several holes through the fireproof walls due pipes/cables/h

    Jan 11, 2023 · Penalty $3,125

    Resolve
  • Class - 2

    Observed: at cellar level, corridor, fire proof walls/ storage rooms and water heater room, several cracks ,missing blocks and holes., repair and/or replace

    Jan 11, 2023

    Resolve
  • Class - 2

    I observed on the roof level of the 1st building the unpermitted use of emt through concrete wall supplying power to a wall heater. emt is not allowed to be embedded in concrete. photos taken., comply with ec c

    Jan 11, 2023 · Penalty $250

    Resolve
  • Class - 1

    I observed in the basement area of the rear building the installation of a temporary blower fan to the boiler disconnect switch with permit on file in dob records. photos taken., obtain permit

    Jan 11, 2023 · Penalty $800

    Resolve
  • Class - 1

    I observed in the pool area the use of flexible cords through a glass and metal frame wall to supply power to appliances and office equipment. the use of flexible cords through the metal frame walls is not perm

    Jan 11, 2023 · Penalty $1,600

    Resolve
  • Class - 1

    I observed in the 6th floor "c side" linen closet in improper installation of a temporary light socket, also noted in the basement electrical area of the rear building the improper termination of conductors to

    Jan 11, 2023 · Penalty $1,600

    Resolve
  • Class - 1

    I observed temporary wiring installed through the opened cover of an 3phasedisconnect, this fails to protect the wiring from improper contact, any attempt to close the door will cause an electrical short circui

    Jan 11, 2023 · Penalty $1,600

    Resolve
  • Class - 2

    Observed: from 2nd fl to 7th fl, corridors and stair case a,b,c & d, emergency lighting are required to illuminate and identify hallways, stairwells and exits to facilitate a safe / orderly evacuation. also, th

    Jan 11, 2023 · Penalty $625

    Resolve
  • Class - 1

    Rope gripper defective will not close after governor switch open or pulling the main line in the off position. must provide capacity plus 125% for the retest(cu). main line missing the elevator provider informa

    Apr 13, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    I observed in the corridors on all floors convenience receptacles not of the tamper-resistant type nor tamper-proofed, as per ll 39 of 2015. photos taken; ec 406.11, comply with ec code; make receptacles tamper

    Aug 23, 2021

    Resolve
  • Class - 2

    I observed in the elevator motor room the improper fusing of the elevator motors the load side was fused at 100 amps with undersized conductors. the conductors on the load side are no larger than # 6 which has

    Aug 23, 2021 · Penalty $1,200

    Resolve
  • Class - 2

    I observed in the electrical / janitor's closet convenience receptacles not of the gfci type nor gfci protected. photos taken, install gfc1 protection

    Aug 23, 2021 · Penalty $1,200

    Resolve
  • Class - 2

    Observed. at the basement level, mechanical rooms, several holes in the concrete slab, block walls due to the penetration of pipes and cables or loss of concrete blocks. also, electrical closets throughout the

    Aug 23, 2021

    Resolve
  • Class - 2

    -observed. at the basement level, mechanical rooms, emergency exit corridors, several cracks between 6-7 feet, openings of 1"-2", at first floor exit stairway b vertical crack, 15 feet appx, 1" opening . at the

    Aug 23, 2021

    Resolve
  • Class - 2

    I observed in basement/ cellar sanitary piping severely corroded causing piping to start flaking and chipping., repair and/or replace

    Aug 23, 2021

    Resolve
  • Class - 2

    - observe: at roof level, exposure # 2, loss of flashing, approximate length of 90 feet, drains not working due to erroneous pooling of water on drainage slopes. also water leaks that run through the pipes and

    Aug 23, 2021

    Resolve
  • Class - 2

    - observed: self-closing fireproof on stairs a, b, c & d 90% of doors do not close automatically due to door leaves overlapping the frame, excessive corrosion and other failures. also, exit door to 43 street do

    Aug 23, 2021

    Resolve
  • Class - 2

    B254,32a,50a,50b,50c. as per class 2 (b254) 28.301.1 failure to main tain: 32a=exposed electrical wiring; 50a-"u" rated chemical feed tank,no safety valve. 50b-safety relief vale boiler #1 leaking; 50c-no manu

    Jul 3, 2018

    Resolve
  • Class - 2

    59bb15,68b7. 59bb15 brake maintenance tag expired.68b7 brake maintenance not logged as per a17.1 2003 & appendix k3 8.6.4.6.

    Nov 21, 2017

    Resolve
  • Class - 2

    60x10,59bb15,68b7,39x10,100l10,70o2. 60 motor room lights inoperative.59 brake maint tag expired.68 brake maintenance not logged.39 car top lights inoperative.100 car top fire service light constantly on.70 pit

    Nov 21, 2017

    Resolve
  • Class - 1

    Door monitoring system is inoperative-repair;rope gripper was disassembled-repair;top of car has oil-clean;hoist motor is leaking oil-clean

    Nov 16, 2017 · Penalty $1,000

    Resolve
  • Class - 1

    6b10:26y2;56y2:door restrictor monitoring system is inoperative,repairtojp of car has oil-clean;hoist machine/motor is leaking oil,clean

    Nov 16, 2017 · Penalty $1,000

    Resolve
  • Class - 2

    40b10- checking main line disconnect (fuses) once pulled rope gripper sets & stays set when main line disconnect is put back on. check rope girder & controller.

    Oct 18, 2013

    Resolve
  • Class - 2

    56b10:vibration, noise coming from machine.

    Nov 30, 2012

    Resolve
  • Class - 2

    40o02,40d06,40b10,52o02. 40d-provide missing fluorescent bulbs and covers. 40b-patch, repair floors, remove existing machinery from machine room.

    Nov 5, 2012

    Resolve
  • Class - 2

    52k02,61g11,40d06,40o02. 2k-cables have rust(rouge) clean & monitor ropes.40d-secure gfci outlet, provide covers on fluorescent bulbs & electrical covers.

    Nov 5, 2012

    Resolve
  • Class - 2

    Failure to file an architect/engineer report certifying exit/directional signs are connected to emergency power source/storage battery equipment. remedy: file architect/engineer report.

    Jan 27, 2010

    Resolve
  • Class - 2

    Failure to file an amended sixth round report acceptable to this departmetn indicating correction of unsafe conditions described in initial local law 11/98 report. rem: file an amended report following remedial

    May 22, 2009

    Resolve
  • Class - 2

    Failure to file an amended sixth round report acceptable to this department indicating correction of unsafe conditions described in initial local law 11/98 report rem: file an amended report following remedial

    Jan 9, 2009

    Resolve
  • Non-hazardous

    38o02,55y13,59q3,17h07.38-clean car top.55-clean & seal machine.59-missing guards onlights.17-hall gibs.

    Mar 22, 2007

    Resolve
  • Non-hazardous

    38o02,55y13,59q3,17h07.38-clean car top.55-clean & seal machine.59-missing guards on lights.07-hall gabs worn-provide.

    Mar 22, 2007

    Resolve
  • Non-hazardous

    36. 36- ao smith lp boiler (model number hw 420 892) not registered with nyc dept of buildings.

    May 9, 2000 · Penalty $350

    Resolve
  • Non-hazardous

    36. 36- ao smith water boiler (model numbe bc 420 780) not registered with nuc dept of buildings.

    May 9, 2000 · Penalty $350

    Resolve
  • Non-hazardous

    Failure to submit a fourth round technical round technical report: periodic inspection of exterior walls and appurtenances as required by local law 10 of 1980 and the department of buildings rules and regulatio

    Aug 18, 1998

    Resolve
  • Hazardous

    Failure to submit a 4th round technical report: periodic inspection ofexterior walls & appurtenances as required by ll 10 of 1980 & the deptof bldgs rules & regulations. remedy: file the require report.

    May 28, 1998

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Mar 30, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Mar 23, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Feb 18, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 8, 2025 · Apt 520

    Close
  • Heat/hot water

    Entire building

    Apr 2, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Mar 16, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Mar 16, 2025 · Apt 375

    Close
  • Heat/hot water

    Entire building

    Mar 13, 2025 · Apt 375

    Close
  • Heat/hot water

    Entire building

    Mar 13, 2025 · Apt SUITE3

    Close
  • Heat/hot water

    Entire building

    Jan 6, 2024 · Apt BLDG

    Close
Show 25 more ↓
  • Heat/hot water

    Entire building

    Oct 26, 2023 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Oct 20, 2023 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Oct 20, 2023 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Oct 15, 2023 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Oct 15, 2023 · Apt BLDG

    Close
  • Water leak

    Heavy flow

    Sep 6, 2023 · Apt 13C

    Close
  • Heat/hot water

    Entire building

    May 11, 2023 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Apr 19, 2023 · Apt 738

    Close
  • Heat/hot water

    Entire building

    Apr 14, 2023 · Apt 392

    Close
  • Heat/hot water

    Entire building

    Apr 12, 2022 · Apt 203

    Close
  • Heat/hot water

    Entire building

    Apr 11, 2022 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 24, 2021 · Apt BLDG

    Close
  • Unsanitary condition

    Pests

    Apr 24, 2021 · Apt 728

    Close
  • Heat/hot water

    Entire building

    Mar 13, 2021 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Mar 13, 2021 · Apt 516

    Close
  • Heat/hot water

    Entire building

    Mar 1, 2021 · Apt 516

    Close
  • Heat/hot water

    Entire building

    Mar 1, 2021 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 8, 2020 · Apt 629

    Close
  • Heat/hot water

    Entire building

    Oct 26, 2019 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Oct 7, 2019 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    May 15, 2017 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    May 14, 2017 · Apt 402

    Close
  • Heat/hot water

    Entire building

    Feb 21, 2017 · Apt 640

    Close
  • Heat/hot water

    Entire building

    Feb 19, 2017 · Apt 640

    Close
  • Nonconst

    Vermin

    Jan 17, 2012 · Apt 420

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Hotel (H3)
Year built
1962
Floors
7
Residential units
—
Building area
122,050 ft²
Lot area
23,425 ft²
Zoning
C6-4
Community board
104
Council district
3
Block / lot
1071 / 23
Assessed value
$8,338,500
Landmark / historic district
No

HPD registration #138455, last renewed Dec 4, 2025.

Questions about 515 West 42 Street

Who owns 515 West 42 Street?

The owner of record in NYC Department of City Planning PLUTO data is R.born Assoc..

Does 515 West 42 Street have violations?

Yes. NYC HPD has recorded 10 housing violations at this property.

Is 515 West 42 Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 515 West 42 Street built?

City records list 1962 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.