HPD housing violations · 10
- ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 29, 2026
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 17, 2025
Closed — Violation dismissed - CImmediately hazardous
Provide hot water at all hot water fixtures in the room located at b-room 371, 3rd story
Oct 26, 2023 · Apt 371
Closed — Violation closed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Mar 15, 2023
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 3, 2022
Closed — Violation dismissed - CImmediately hazardous
Abate the infestation consisting of mice in the room located at b-room 728, 7th story, 1st b-room from north at east
May 20, 2021 · Apt 728
Open — Notice of issuance sent to tenant - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Oct 25, 2019
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 6, 2017
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Oct 26, 2016
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Feb 3, 2015
Closed — Violation dismissed
DOB building violations · 66
- No report and / or late filing (facade) facade required
Failed to file fisp cycle 9c technical report by 2/21/2024
Feb 22, 2024
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jan 24, 2024
Dob violation - dismissed - Construction other optional
Failure to maintain building in code complaint manner. throughout parking garage 1st & 2nd levels, observed areas of spalled concrete from concrete slab (floor & ceiling) exposing rusted rebar. at both vehicle access ramps & throughout 2nd level noted several heavily rusted & deteriorated structural steel beams. nyspe report request
Nov 16, 2023
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 10, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 10, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 10, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 10, 2020
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed
Show 40 more ↓
- Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
May 3, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 6, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 6, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 6, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 6, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 26, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 26, 2012
Dob violation - resolved - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Jan 1, 2012
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 4, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 4, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 4, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 4, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 4, 2011
Dob violation - resolved - Construction other optional
C-construction other optional
Apr 1, 2010
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 22, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 22, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 22, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 22, 2008
Dob violation - resolved - Emergency power none
Ll2604e-emergency power none
Mar 31, 2008
Dob violation - dismissed - Facade facade required
L1198-local law 11/98 - facade facade required
Jun 25, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 29, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 29, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 29, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 29, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 18, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 18, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 18, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 18, 2006
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed
ECB violations · 54
- Class - 1
Class 1 c/u: in-car stop switch damaged/inoperative, as per asme a17.1 2.26.2.21. remedy: repair/replace in-car stop switch and restore to proper operating condition. email elevator division at [email protected]
Sep 28, 2026 · Penalty $1,250
Active - Class - 1
Class 1 cease use: door zone restrictor device found inoperative as per code asme a17.1/csa b44 - section 2.26.5. elevator car doors can be opened when the car is not within the designated door zone, creating a
Sep 28, 2026 · Penalty $1,250
Active - Class - 2
Class 2: top-of-car inspection switch malfunctioning; intermittently fails to return to normal operation, as per asme a17.1 2.26.1.4. remedy: repair or replace top-of-car inspection switch and restore proper no
Sep 28, 2026 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. observed security chairs obstructing passageways/hallways. located throughout the building. potential fire hazard., repair and/or replace
Oct 14, 2025 · Penalty $6,250
Active - Class - 2
Observed at 8th floor roof level, sheet metal covering to stand pipe valve posing a risk of a severe laceration., repair and/or replace
Nov 18, 2024
Resolve - Class - 2
Exit door not self-closing. observed non self closing doors throughout building. incase of fire this is a hazard conidition., repair/replace door
Nov 18, 2024
Resolve - Class - 2
Observed at basement fernco coupling and jim cap installed on 2 inch waste pipe also 2 inch pipe being supported with electrical cord. as per 308 of the plumbing code 308.4 structural attachment. hangers and an
Nov 18, 2024
Resolve - Class - 1
I observed on the 6th floor in the bathroom next to the "b" stairs the electrical panels open with exposed and energized wiring and parts with no covers to protect against shock hazard. photos taken, comply wit
Nov 18, 2024 · Penalty $1,600
Resolve - Class - 1
Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed hole penetrations throughout building. incase of emergency this is a fir
Nov 18, 2024 · Penalty $2,500
Resolve - Class - 2
I observed in the 6th floor bathroom, the elevator motor room and the main electrical room the failure to provide gfci protection as required. photos taken., install gfc1 protection
Nov 18, 2024 · Penalty $1,200
Resolve
Show 40 more ↓
- Class - 1
I observed in the kitchen/pantry in the rear building a defective extension cord in use and an extension passing across an open doorway to supply power to the appliances, also noted in the main electrical room
Nov 18, 2024 · Penalty $400
Resolve - Class - 1
Failure to maintain building in code compliant manner. noted throughout parking garage 1st & 2nd levels, several areas of spalled concrete from ceiling & floor concrete slab, exposing corroded rebar. at both ve
Nov 16, 2023 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code compliant manner. noted at exp#3 (west 43rd st side) facade with missing bricks above lintel of vehicle access gate. additionally, at exp#4 (east) roof level, brick wall adj
Nov 16, 2023
Resolve - Class - 2
No emergency lighting from 2nd fl to 7th fl, corridors of both buildings. (emergency lighting is required to illuminate and identify hallways, stairwells and exits to facilitate a safe / orderly evacuation)., r
Aug 2, 2023
Resolve - Class - 2
Observed residential gas flex installed on commercial dryers. as per fgc 411 1. rigid metallic pipe and fittings. space heaters and water heaters within dwelling units shall be connected using rigid piping and
Jan 13, 2023 · Penalty $312
Resolve - Class - 2
Observed. at cellar level,electrical rm, storage rms near gas meter, gas meter area, also storage closet through the building and staircase a,b,c,& d several holes through the fireproof walls due pipes/cables/h
Jan 11, 2023 · Penalty $3,125
Resolve - Class - 2
Observed: at cellar level, corridor, fire proof walls/ storage rooms and water heater room, several cracks ,missing blocks and holes., repair and/or replace
Jan 11, 2023
Resolve - Class - 2
I observed on the roof level of the 1st building the unpermitted use of emt through concrete wall supplying power to a wall heater. emt is not allowed to be embedded in concrete. photos taken., comply with ec c
Jan 11, 2023 · Penalty $250
Resolve - Class - 1
I observed in the basement area of the rear building the installation of a temporary blower fan to the boiler disconnect switch with permit on file in dob records. photos taken., obtain permit
Jan 11, 2023 · Penalty $800
Resolve - Class - 1
I observed in the pool area the use of flexible cords through a glass and metal frame wall to supply power to appliances and office equipment. the use of flexible cords through the metal frame walls is not perm
Jan 11, 2023 · Penalty $1,600
Resolve - Class - 1
I observed in the 6th floor "c side" linen closet in improper installation of a temporary light socket, also noted in the basement electrical area of the rear building the improper termination of conductors to
Jan 11, 2023 · Penalty $1,600
Resolve - Class - 1
I observed temporary wiring installed through the opened cover of an 3phasedisconnect, this fails to protect the wiring from improper contact, any attempt to close the door will cause an electrical short circui
Jan 11, 2023 · Penalty $1,600
Resolve - Class - 2
Observed: from 2nd fl to 7th fl, corridors and stair case a,b,c & d, emergency lighting are required to illuminate and identify hallways, stairwells and exits to facilitate a safe / orderly evacuation. also, th
Jan 11, 2023 · Penalty $625
Resolve - Class - 1
Rope gripper defective will not close after governor switch open or pulling the main line in the off position. must provide capacity plus 125% for the retest(cu). main line missing the elevator provider informa
Apr 13, 2022 · Penalty $1,250
Resolve - Class - 2
I observed in the corridors on all floors convenience receptacles not of the tamper-resistant type nor tamper-proofed, as per ll 39 of 2015. photos taken; ec 406.11, comply with ec code; make receptacles tamper
Aug 23, 2021
Resolve - Class - 2
I observed in the elevator motor room the improper fusing of the elevator motors the load side was fused at 100 amps with undersized conductors. the conductors on the load side are no larger than # 6 which has
Aug 23, 2021 · Penalty $1,200
Resolve - Class - 2
I observed in the electrical / janitor's closet convenience receptacles not of the gfci type nor gfci protected. photos taken, install gfc1 protection
Aug 23, 2021 · Penalty $1,200
Resolve - Class - 2
Observed. at the basement level, mechanical rooms, several holes in the concrete slab, block walls due to the penetration of pipes and cables or loss of concrete blocks. also, electrical closets throughout the
Aug 23, 2021
Resolve - Class - 2
-observed. at the basement level, mechanical rooms, emergency exit corridors, several cracks between 6-7 feet, openings of 1"-2", at first floor exit stairway b vertical crack, 15 feet appx, 1" opening . at the
Aug 23, 2021
Resolve - Class - 2
I observed in basement/ cellar sanitary piping severely corroded causing piping to start flaking and chipping., repair and/or replace
Aug 23, 2021
Resolve - Class - 2
- observe: at roof level, exposure # 2, loss of flashing, approximate length of 90 feet, drains not working due to erroneous pooling of water on drainage slopes. also water leaks that run through the pipes and
Aug 23, 2021
Resolve - Class - 2
- observed: self-closing fireproof on stairs a, b, c & d 90% of doors do not close automatically due to door leaves overlapping the frame, excessive corrosion and other failures. also, exit door to 43 street do
Aug 23, 2021
Resolve - Class - 2
B254,32a,50a,50b,50c. as per class 2 (b254) 28.301.1 failure to main tain: 32a=exposed electrical wiring; 50a-"u" rated chemical feed tank,no safety valve. 50b-safety relief vale boiler #1 leaking; 50c-no manu
Jul 3, 2018
Resolve - Class - 2
59bb15,68b7. 59bb15 brake maintenance tag expired.68b7 brake maintenance not logged as per a17.1 2003 & appendix k3 8.6.4.6.
Nov 21, 2017
Resolve - Class - 2
60x10,59bb15,68b7,39x10,100l10,70o2. 60 motor room lights inoperative.59 brake maint tag expired.68 brake maintenance not logged.39 car top lights inoperative.100 car top fire service light constantly on.70 pit
Nov 21, 2017
Resolve - Class - 1
Door monitoring system is inoperative-repair;rope gripper was disassembled-repair;top of car has oil-clean;hoist motor is leaking oil-clean
Nov 16, 2017 · Penalty $1,000
Resolve - Class - 1
6b10:26y2;56y2:door restrictor monitoring system is inoperative,repairtojp of car has oil-clean;hoist machine/motor is leaking oil,clean
Nov 16, 2017 · Penalty $1,000
Resolve - Class - 2
40b10- checking main line disconnect (fuses) once pulled rope gripper sets & stays set when main line disconnect is put back on. check rope girder & controller.
Oct 18, 2013
Resolve - Class - 2
56b10:vibration, noise coming from machine.
Nov 30, 2012
Resolve - Class - 2
40o02,40d06,40b10,52o02. 40d-provide missing fluorescent bulbs and covers. 40b-patch, repair floors, remove existing machinery from machine room.
Nov 5, 2012
Resolve - Class - 2
52k02,61g11,40d06,40o02. 2k-cables have rust(rouge) clean & monitor ropes.40d-secure gfci outlet, provide covers on fluorescent bulbs & electrical covers.
Nov 5, 2012
Resolve - Class - 2
Failure to file an architect/engineer report certifying exit/directional signs are connected to emergency power source/storage battery equipment. remedy: file architect/engineer report.
Jan 27, 2010
Resolve - Class - 2
Failure to file an amended sixth round report acceptable to this departmetn indicating correction of unsafe conditions described in initial local law 11/98 report. rem: file an amended report following remedial
May 22, 2009
Resolve - Class - 2
Failure to file an amended sixth round report acceptable to this department indicating correction of unsafe conditions described in initial local law 11/98 report rem: file an amended report following remedial
Jan 9, 2009
Resolve - Non-hazardous
38o02,55y13,59q3,17h07.38-clean car top.55-clean & seal machine.59-missing guards onlights.17-hall gibs.
Mar 22, 2007
Resolve - Non-hazardous
38o02,55y13,59q3,17h07.38-clean car top.55-clean & seal machine.59-missing guards on lights.07-hall gabs worn-provide.
Mar 22, 2007
Resolve - Non-hazardous
36. 36- ao smith lp boiler (model number hw 420 892) not registered with nyc dept of buildings.
May 9, 2000 · Penalty $350
Resolve - Non-hazardous
36. 36- ao smith water boiler (model numbe bc 420 780) not registered with nuc dept of buildings.
May 9, 2000 · Penalty $350
Resolve - Non-hazardous
Failure to submit a fourth round technical round technical report: periodic inspection of exterior walls and appurtenances as required by local law 10 of 1980 and the department of buildings rules and regulatio
Aug 18, 1998
Resolve - Hazardous
Failure to submit a 4th round technical report: periodic inspection ofexterior walls & appurtenances as required by ll 10 of 1980 & the deptof bldgs rules & regulations. remedy: file the require report.
May 28, 1998
Resolve
Complaints
- Heat/hot water
Entire building
Mar 30, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Mar 23, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Feb 18, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Dec 8, 2025 · Apt 520
Close - Heat/hot water
Entire building
Apr 2, 2025 · Apt BLDG
Close - Heat/hot water
Entire building
Mar 16, 2025 · Apt BLDG
Close - Heat/hot water
Entire building
Mar 16, 2025 · Apt 375
Close - Heat/hot water
Entire building
Mar 13, 2025 · Apt 375
Close - Heat/hot water
Entire building
Mar 13, 2025 · Apt SUITE3
Close - Heat/hot water
Entire building
Jan 6, 2024 · Apt BLDG
Close
Show 25 more ↓
- Heat/hot water
Entire building
Oct 26, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 20, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 20, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 15, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 15, 2023 · Apt BLDG
Close - Water leak
Heavy flow
Sep 6, 2023 · Apt 13C
Close - Heat/hot water
Entire building
May 11, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Apr 19, 2023 · Apt 738
Close - Heat/hot water
Entire building
Apr 14, 2023 · Apt 392
Close - Heat/hot water
Entire building
Apr 12, 2022 · Apt 203
Close - Heat/hot water
Entire building
Apr 11, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Nov 24, 2021 · Apt BLDG
Close - Unsanitary condition
Pests
Apr 24, 2021 · Apt 728
Close - Heat/hot water
Entire building
Mar 13, 2021 · Apt BLDG
Close - Heat/hot water
Entire building
Mar 13, 2021 · Apt 516
Close - Heat/hot water
Entire building
Mar 1, 2021 · Apt 516
Close - Heat/hot water
Entire building
Mar 1, 2021 · Apt BLDG
Close - Heat/hot water
Entire building
Nov 8, 2020 · Apt 629
Close - Heat/hot water
Entire building
Oct 26, 2019 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 7, 2019 · Apt BLDG
Close - Heat/hot water
Entire building
May 15, 2017 · Apt BLDG
Close - Heat/hot water
Entire building
May 14, 2017 · Apt 402
Close - Heat/hot water
Entire building
Feb 21, 2017 · Apt 640
Close - Heat/hot water
Entire building
Feb 19, 2017 · Apt 640
Close - Nonconst
Vermin
Jan 17, 2012 · Apt 420
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Hotel (H3)
- Year built
- 1962
- Floors
- 7
- Residential units
- —
- Building area
- 122,050 ft²
- Lot area
- 23,425 ft²
- Zoning
- C6-4
- Community board
- 104
- Council district
- 3
- Block / lot
- 1071 / 23
- Assessed value
- $8,338,500
- Landmark / historic district
- No
HPD registration #138455, last renewed Dec 4, 2025.
Questions about 515 West 42 Street
Who owns 515 West 42 Street?
The owner of record in NYC Department of City Planning PLUTO data is R.born Assoc..
Does 515 West 42 Street have violations?
Yes. NYC HPD has recorded 10 housing violations at this property.
Is 515 West 42 Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 515 West 42 Street built?
City records list 1962 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.