roofy

200 Wardwell Avenue

Staten Island, NY 10314BBL 5-00423-0009Map

Owner of record: NYC Department Of Education

200 Wardwell Avenue is a school building built in 1931 in Staten Island, 10314. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
6
ECB violations
50
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 6

  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed

ECB violations · 50

  • Class - 2

    Re-issue #35692174h. failure to maintain building in code-compliant manner. noted: a structural girder beam at the stair landing near rm/door #153 is exposed from deterioration of the outer/cover materials. thi

    Feb 10, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35692173x. failure to maintain building in code-compliant manner. no fire stopping per bc 712.3; 27-345. noted: at the boiler rm, outside the electric room, there are several penetrations thru walls t

    Feb 10, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35692172y. failure to maintain building in code-compliant manner. noted: in the music rm., the door leading to the blower rm. and the smoke door at the 4th floor stair f are not closing properly. reme

    Feb 10, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits discharges and public corridors per bc 1006.1; 27-381. noted: at t. o. i. there were several emergency lites that were not operation

    Feb 7, 2025 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at t. o.i. the door to the blower rm. inside the music room and the smoke doorat 4th floor stair f are not closing. properly. remedy: repair/replace

    Feb 7, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3; 27-345. noted: at the boiler rm, outside the electric room there are several penetrations that require fire stopping. remedy

    Feb 7, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at t. o.i. there is a girder/beam that can be seen on the landing of the staircase thru room/door #153. the beam is exposed from ceiling at the land

    Feb 7, 2025 · Penalty $625

    Active
  • Class - 2

    28-301.1 unlawful display of artwork in corridors or classrms >20% perfdny2008code;fc803.3.2.observed atoi theres excessive display of combustible materials thruout bldg.hanging on walls&ceilings,near or on lig

    May 4, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.observed atoi there were several emergency lights that werent op when tested.location

    May 4, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardwadre per inspection, several classroom doors on all floors were equipped with illegal kick stops. rem: provide legal har

    Jun 28, 2018

    Resolve
Show 40 more ↓
  • Class - 3

    Work w/o permit. noted: at time of inspection i observed apprx 200' of side walk shed in place w/o permit or job filings. rmdy: obtain permit.

    May 20, 2017

    Resolve
  • Class - 2

    Re-issue ecb.#35094128r.foundation water penetration.@ cellar,water penetrating from foundation walls into oil tank room + brick wall of boiler room.rem:water proof sections of foundation walls.

    Feb 11, 2015

    Resolve
  • Class - 2

    Re-issue.ecb 35094132j facade water penetration.water penetrating into room 311.stair case d of bulkhead walls due to no waterproofing of facade.rem:water proof section of facade.

    Feb 11, 2015

    Resolve
  • Class - 2

    Roof leaking. at roof above classrooms 403,405 & 411, water penetrating from roof to ceiling. remedy: repair sections of roof.

    Apr 11, 2014

    Resolve
  • Class - 2

    Defective door check. at 2nd floor staircase doors a & b: door check on 1 door defective not allowing door to close fully. remedy: replace door check.

    Apr 11, 2014

    Resolve
  • Class - 2

    Water penetration. at 4th floor & 3rd floor, there is water penetration, coming from facade & roof, onto ceiling & walls in rooms 311,411,405 & 403 and in bulkhead of staircase d above window. remedy: repair wa

    Apr 11, 2014

    Resolve
  • Class - 2

    Water penetration from facade. water penetrating from facade onto walls in room 311 & staircase d of bulkhead. remedy: waterproof facade where water is penetrating from.

    Apr 11, 2014

    Resolve
  • Class - 2

    Re-issue # 34896073r. water penetration. at basement, water penetrating into oil tank room & backwall of boiler room from foundation walls. remedy: waterproof foundation walls.

    Apr 11, 2014

    Resolve
  • Class - 2

    Sec. 28-301.1 reissue 34987867m doors racked,wont properly close at stairs a,b,d,e,f various locations fls 2,3,4 & at bulkhead stair d-e. remedy: maintain bldg.

    May 10, 2013

    Resolve
  • Class - 2

    Sec. 28-301.1 reissue 34987866k water penetration into boiler room & oil tank room along wardwell ave side of school,& at location where water main enters bldg. remedy: maintain bldg.

    May 10, 2013

    Resolve
  • Class - 2

    Doors racked at stairs a,b,d & e on 2nd,3rd & 4th flrs preventing themffrom closing properly and gym door drags on flr. remedy: repair/replace doors.

    Aug 8, 2012

    Resolve
  • Class - 2

    Reissue 34896073r. at cellar water penetrating through foundation wallwhere water main enters, standing water present at time of insp. remedy: provide water proofing to foundation wall.

    Aug 8, 2012

    Resolve
  • Class - 2

    Re-34830845x.@ cellar level open area leading towards gas meter rm.foundation wall has become porous allowing water into cellar.rem:restore weatherproof integrity to exteriorof foundation walls @ cellar level

    Mar 1, 2011

    Resolve
  • Class - 2

    @ south end of bldg stair not labeled. remedy: post (alphabet) stair resignation @ each floor inside & outside of landing.

    May 7, 2010

    Resolve
  • Class - 2

    Storm/ground water penetrates @ transfer pump room & oil tank room. remedy: prevent penetration of storm/ground water.

    May 7, 2010

    Resolve
  • Class - 2

    Emergency lighting does not respond to test switch. 2) @ auditorium rear (left & right) @ stage. 3) exit from auditorium 4) @ south stair 2nd fl. main entry left & right 2nd fl. remedy: repair/replace defective

    May 7, 2010

    Resolve
  • Class - 3

    @ room 311, loose/stained plaster. remedy: scrape/replace & paint

    May 7, 2010

    Resolve
  • Class - 2

    Plexiglass installed in corridor door location room 403 rem: replace w/ wire glass

    Jun 24, 2009

    Resolve
  • Class - 2

    Emergency lighting not working location: near 305 rem: repair em light

    Jun 24, 2009

    Resolve
  • Class - 2

    Roof leak location above rm 411 plaster damage is in 311 rem: confirm source repair leak

    Jun 24, 2009

    Resolve
  • Class - 3

    Loose spalled stained plaster location ceiling @ 311 note 4th fl room 411 has no damage but roof leak is still prime suspect rem: scrape & repair plaster repair roof leak

    Jun 24, 2009

    Resolve
  • Hazardous

    28c 28c-hazardous ten (1) boiler tubes over 10% total replacement necessary

    Aug 31, 2005

    Resolve
  • Non-hazardous

    Failure to maintain noted:4 story roof damaged & missing sections of base flashing along interior parapet reissue 34421562z remedy:repair defects

    Jan 11, 2005

    Resolve
  • Non-hazardous

    Failure to maintain noted cellar boiler & old coal bunker rooms activewater infiltration through foundation slab system re-issue "34275630z 34421564m remedy:provide engineer's report repair defects

    Jan 11, 2005

    Resolve
  • Non-hazardous

    Failure to maintain noted leonard & wardwell avents-drain discharcing directly onto street (curb side) drains installed below sidewalk & through curb re-issue "34421567h remedy:comform to building code

    Jan 11, 2005

    Resolve
  • Non-hazardous

    Failure to maintain bldg.interior/exterior noted:sanitary facilities throughout school need upgrade.remedy:maintain bldg-make all necessary repairs

    Feb 3, 2004

    Resolve
  • Non-hazardous

    Failure to maintain bldg defect:noted:at curb 3 locations 2 on wardwell ave and 1 on leonard st.a 4" pvc pipe visible routed under side walkfrom bldg discharging onto street.remedy:connect drainage to bldg

    Jan 14, 2004

    Resolve
  • Non-hazardous

    Failure to maintain bldg defect noted.at following locations plaster spalling (1)exit g at 4th flr. interior of exterior wall (2)at room 311 ceiling and part of wall toward rear of room (3) at room 214 at

    Jan 14, 2004

    Resolve
  • Non-hazardous

    Failure to maintain bldg noted:at cellar boiler room,sump pump pit has no steel cover.pit approx 2x2x2 deep.remedy:provide cover

    Jan 14, 2004

    Resolve
  • Non-hazardous

    Failure to maintain bldg,defect noted at cellar.boiler room area.at old coal storage area at east foundation at floor level.water penetrating thru foundation with pools of water present and also east foudation

    Jan 14, 2004

    Resolve
  • Non-hazardous

    Failure to maintain bldg,defect noted:at stair #8,stair landings from 2nd flr to 1st flr,surface covering has extensive veining effect of 1/2 inch high to 1 inch high on 5ft x 5ft landings,veining /uplifting

    Jan 14, 2004

    Resolve
  • Non-hazardous

    Failure to maintain bldg defect, noted at roof of 4 story portition of school,flashing on north 1 west papapet wall. open portitions approx 4 ft,also at north/east a 15 ft section.hole in flashing and at east

    Jan 14, 2004

    Resolve
  • Non-hazardous

    Failure to carry out permitted work in accordant with appliance laws and regulations in that construction activities ie. replacing windows and guards being performed other than weekdays between the hours of 2:0

    Sep 1, 2002

    Resolve
  • Non-hazardous

    Failure to carry out permitted work in accordance with applicable lawsand regulation in that construction actiuities ic replacing windows ace being performed other than on weekdays between the hours of 7"00 am

    Jun 15, 2002 · Penalty $200

    Active
  • Non-hazardous

    Failure to maintain defect is:in the gymnasium the paint on the ceiling is peeling off.remedy:repair the ceilings.

    Feb 15, 2001

    Resolve
  • Non-hazardous

    Failure to maintain defect is:the east side foundation wall within the old coal bunker,is leaking water.remedy:repair and/or water proof the foundation wall,check areaway drains.

    Feb 15, 2001

    Resolve
  • Non-hazardous

    Failure to maintain defect is:the exit doors west side,leading to playground are rotted at the base.remedy:replace and or repair doors.

    Feb 15, 2001

    Resolve
  • Non-hazardous

    Failure to maintain defect is:1.two gates are missing from the perimeter fence,on the south side of bldg.2.two perimeter fence gates are broken on west side of playground.3.two sections of the perimeter fence,a

    Feb 15, 2001

    Resolve
  • Hazardous

    Supervision and use of rigging equipment without a special riggers license. operation of hoisting equipment in an unsafe manner. a) sand used as counterweights. b) no tieback on hoist.

    Aug 3, 1999 · Penalty $6,250

    Resolve
  • Non-hazardous

    Failure to maintain bldg interior/exterior. noted: concrete walk at entrances need repair. various windows need repair. poraas roof due for repair (7/8/99). sanitary facilities throughout school need upgrad

    Jun 11, 1999

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1931
Floors
4
Residential units
—
Building area
58,660 ft²
Lot area
51,750 ft²
Zoning
R3X
Community board
501
Council district
50
Block / lot
423 / 9
Assessed value
$4,197,600
Landmark / historic district
No

Questions about 200 Wardwell Avenue

Who owns 200 Wardwell Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 200 Wardwell Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 200 Wardwell Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 200 Wardwell Avenue built?

City records list 1931 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.