1581 Victory Boulevard
Staten Island, NY 10314BBL 5-00331-0001Map
Owner of record: NYC Department Of Education
1581 Victory Boulevard is a school building built in 2011 in Staten Island, 10314. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 27
- ECB violations
- 43
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 27
- Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed
Show 17 more ↓
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Construction other optional
C-construction other optional
Apr 20, 1992
Dob violation - dismissed
ECB violations · 43
- Class - 2
Work after hrs w/o variance permit,contrary to 28-105.12.5.noted:premises a public school w/const. observed@rear (slossin ave) to include earthwork&interior work@cellar level w/removal of section of concrete.pi
Dec 1, 2022 · Penalty $1,280
Resolve - Class - 2
28-301.1 unlawful display of artwork in corridors&classrms >20% per fdny2008code;fc803.3.2.observed atoi excessive amt of combustible materials on walls,hanging from ceilings&near or attached to lighting&coveri
May 3, 2022 · Penalty $1,250
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.observed atoi there were several emergency lights located about bldg,esp auditorium t
May 3, 2022 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner. note: in room 302, the ceiling shows signs of water damage from leak in roof above. paint is flaking and peeling. rmdy: repair/replace/fix leak, repair ro
May 9, 2019
Resolve - Class - 3
Failure to maintain bldg in code-compliant manner. the following areashave water penetration. basement: west crawl space; east fan room; electric panel room 1st flr: auditorium walls; hallway near room 209.
Apr 10, 2017
Resolve - Class - 2
Re-issue # 35019414h. failure to maintain bldg: exterior. -at bulkhead for stairway g, water penetration from bulkhead facade. -at boiler room in cellar, foundation leakage causing water to enter from ceiling
Apr 1, 2014
Resolve - Class - 2
Re-issue # 35019412y. failure to maintain bldg: interior. -at boiler room in cellar, f.p.s.c. door at gas meter room not self closing & drags on floor. -at 1st floor auditorium, doors adjacent to stage & stairw
Apr 1, 2014
Resolve - Class - 2
Failure to maintain bldg wall(s) or appurtenances: exterior. retaining wall of school yard on slosson ave side cracked & crumbling. remedy: repair &/or replace retaining wall.
Apr 1, 2014
Resolve - Class - 2
Re-issue # 35019413x. failure to maintain bldg: interior. -at bulkhead of stairway g, walls spalling & crumbling due to water damage. -at 1st floor auditorium, wall at east of auditorium spalling from water
Apr 1, 2014
Resolve - Class - 2
At auditorium - piano removed from platform at stage front left & relocated to aisle at stage front right,reducing required front aisle width to exit door. remedy: remove obstruction - relocated piano back to
May 9, 2013
Resolve
Show 33 more ↓
- Class - 2
F.p.s.c. door at gas meter room not self closing & drags on floor. at auditorium,doors adjacent stage to stairwells & at e2,closers removed.at gym-new gym entry doors - no underwriter tags at testing to fire
May 9, 2013
Resolve - Class - 3
Water penetration through exterior wall/at stair g level 2 & 3,plasterwet. also through ceiling at boiler room at west court,minor ponding at time of insoection. remedy: maintain bldg.
May 9, 2013
Resolve - Class - 3
Spalling plaster at auditorium east wall adjacent left window - right side. at stair g,level 2,3,bulkhead. remedy: maintain bldg.
May 9, 2013
Resolve - Class - 2
Doors at exit 4 stick requiring excessive force to open. remedy: repair/replace doors.
Aug 7, 2012
Resolve - Class - 2
(misc)27-371(b)fail to provide required fire rated door between classrooms & corridor.plexiglass installed @ vision panels for classrooms throughout various areas from 1st & 3rd flrs.rem:provide required visio
Feb 25, 2011
Resolve - Class - 3
Plaster loose/cracked/spalling @ 303 behind radiator @ 303 ceiling near window.rem:scrape/repair/replace plaster
Feb 5, 2010
Resolve - Class - 2
Emergency lights not working @ 325;@ 213.rem:insure all emergency lighting respond to test
Feb 5, 2010
Resolve - Class - 1
@ boiler rm, actuators for combustion-air louvres broken off.rem:insure combustion-air louvres open with boiler operation
Feb 5, 2010
Resolve - Non-hazardous
Failure to maintain. noted: playground retaining wall (along slossah ave) is in disrepair with large spalls and cracks. "re-issue" #34286744k remedy: repair defects.
Jan 7, 2005
Resolve - Hazardous
Failure to maintain. noted: cellar paint shop and storage (flanking tank room) rooms concrete ceilings have spalled and cracked exposing steel members. lower portion of concrete cover along ceiling beam is
Jan 7, 2005
Resolve - Hazardous
6a/50 (6a)discharge of saftty value exceedsis psi.discharge of value on left side is 17 1\2 psi discharge of value on right side is 18 psi 50 needs dicharge pipes from safety values to a safety location.
Nov 16, 2004
Resolve - Non-hazardous
50a/50b 50a) install a pipe down on the safety valve discharge. 50b) replace the leaking quick closing valve on the bottom blow down line.
Oct 15, 2004
Resolve - Non-hazardous
50 50) pipe down the safety valve discharge to a safe point to preventscalding persons and damaging equipment.
Oct 15, 2004
Resolve - Non-hazardous
36 19b 50 bq9-raydale hot water boiler model #250 50-missing discharge pipe on safety value
Sep 3, 2004
Resolve - Non-hazardous
*reissue* failure to maintain bldg.at boiler room concrete ceilings atstorage areas to left and right of tank room are badly.deteroirated from water penetration pieces of cement have loosened and fallen off
Jan 27, 2004
Resolve - Non-hazardous
Exit passage or corridor:required width decreased.by obstruction (1)at3rd flr hall corridor outside rm 308 a desk and 4 chairs present,(2)outside rm 325 5 chairs and desks (3)2nd flr outside 217 from interior
Jan 27, 2004
Resolve - Non-hazardous
Failure to maintain at boiler room noted: concrete ceilings at stprage areas to left & right of tank room are badly deteriorated from water penetration pieces of cement have loosened & fallen off exposing steel
Jan 15, 2003
Resolve - Non-hazardous
Failure to maintain. noted: large cracks and missing pieces of concrete of retaining walls at playground (nearest to school/slosson ave side) remedy: repair retaining wall.
Jan 11, 2002
Resolve - Non-hazardous
Failure to maintain. noted: cracks and damage in plaster of ceiling beams at plaster damage at corner of room 108. remedy: repair cracks and plaster damage.
Jan 11, 2002
Resolve - Non-hazardous
Failure to maintain. noted: ventication floor grates in auditorium are cracked/worn. some are loose and have become a trip hazard. remedy: repair or replace floor grates.
Jan 11, 2002
Resolve - Non-hazardous
Failure to maintain. noted: section of flooring is buckling and has lifted up about 3 inches in room 103. remedy: repair floor.
Jan 11, 2002
Resolve - Non-hazardous
Failure to provide emergency light fixture within stair # 11 and adjoining corridor on 1 floor also on stair #11 and corridor on floor 2 & 3eresot portion of corridor near classroom #225 & 325. stair on 3 floor
Jun 21, 2001
Resolve - Non-hazardous
Failure to maintain defect is:the perimeter fence gate, is missing at the south east corner of buidling.remedy:replace perimeter fence gate.
Feb 15, 2001
Resolve - Non-hazardous
Failure to maintain:the hot water stack has cracked brick and mortor joints.remedy:re-point hot water stack.
Feb 15, 2001
Resolve - Non-hazardous
Failure to maintain defect is;in the front of the building to the right of the main entry the terra cotta decorative tiles are spalling.remedy:repair terra cotta.
Feb 15, 2001
Resolve - Non-hazardous
Failure to maintain.defect is:in stairway #9,the plaster on the walls is deteriorated.rem:repair plaster as needed.
Feb 15, 2001
Resolve - Non-hazardous
Failure to maintain : defect iw: 1- in the front of building ,to the right of main entry ,the terra cotta decorative tiles are spalling 2- the conrete fan room at roof level is spalling concrete .3- the hot wat
May 5, 2000
Resolve - Non-hazardous
Failure to maintain : defect is: 1- perimeter fence at front of school is missing .2- perimeter fence gats are missing at south side of playground and at east corner of school .3- stairway # 11 has extensive pl
May 5, 2000
Resolve - Hazardous
Failure to maintain building. interior and exterior noted. egress doors jamed in position, hazardous, rotted etc. water penetration into boiler area and ask hoist pit. new flag pole design, water penetration
Jun 8, 1999
Resolve - Non-hazardous
No sidewalk shed permit. noted at time of inspection no sidewalk shed permit posted or available. make sidewalk shed permit available.
Jun 8, 1999
Resolve - Hazardous
Failure to maintain building interior and exterior. noted one boiler unit inoperable, front entrance railing needs repair weld. concrete walks need repair. coal chute inoperable, ask hoist doors rotted, area
Jun 8, 1999
Resolve - Non-hazardous
Failure to maintain noted the exit signs on 2nd floor at various locations to yard and street are missing and some not of approved type remedy install ixit signs on first floor exits where needed to dept regula
Nov 1, 1993 · Penalty $1,000
Resolve - Hazardous
Operation of a pa without current permit. failure to have pa plan available pa plans.
Jan 17, 1989
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 2011
- Floors
- 2
- Residential units
- —
- Building area
- 27,648 ft²
- Lot area
- 82,500 ft²
- Zoning
- R1-2
- Community board
- 501
- Council district
- 50
- Block / lot
- 331 / 1
- Assessed value
- $4,961,250
- Landmark / historic district
- No
Questions about 1581 Victory Boulevard
Who owns 1581 Victory Boulevard?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 1581 Victory Boulevard have violations?
NYC HPD has no housing violations on record for this property.
Is 1581 Victory Boulevard rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 1581 Victory Boulevard built?
City records list 2011 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.