91 Henderson Avenue

Staten Island, NY 10301BBL 5-00073-0064Map

Owner of record: NYC Department Of Education

91 Henderson Avenue is a school building built in 1925 in Staten Island, 10301. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
10
ECB violations
39
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 10

  • Construction other optional

    Matters not provided

    Sep 3, 2011

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Public assembly none

    Pa-public assembly none

    Mar 20, 1989

    Dob violation - dismissed

ECB violations · 39

  • Class - 2

    Re-issue#35654948p failure to maintain building in code compliant manner. the water infiltration at basement cellar level continues at t.o.i., at times of rain weather, there are several areas of cellar where w

    May 16, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:all3 doors thatlead to auditorium@exit6 door on left.all these doors werent closing properly bc of defective hardware.repair&replace.

    May 4, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue35546223j failure to maintain bldg in codecompliant manner.noted:@bsmt level theres water penetration@various locations thruout.repair &/ replace.

    May 4, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issued #35447978y. failure to maintain building.observed at t.o.i the ongoing infilitration of water from main continues at the cellar level in several areas.water leaks through the foundation at various loc

    May 27, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.illumination for exits exit discharges and public corridors per bc 1006.;27-381.several emergency lights are not operational when tested.remedy:repair/repla

    May 27, 2021 · Penalty $625

    Resolve
  • Class - 2

    Re-issue #35346991x failure to maintain building wall(s) or appurtenances. noted:at time of inspection,at basement level,water damage and signs of water infiltration at several areas due to leaks in the foundat

    Aug 5, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: @ basement level,boiler room,water damaged to walls @ various locations due to water penetration through retaining walls. rem: repair or replace.

    Aug 13, 2018

    Resolve
  • Class - 2

    Re-issue ecb.#35085876h.water penetration.water penetration into boiler room from foundation walls.rem:repair water penetration.

    Feb 12, 2015

    Resolve
  • Class - 2

    Re-issue ecb#.spalling ceilings + walls.in rooms 311, 312,+ 314, ceiling and/or walls are spalling due to water damage.rem:repair ceilings and or walls.

    Feb 12, 2015

    Resolve
  • Class - 2

    Defective door checks.main entrance door exit,door check not operating properly.stair case 7, 1st fl.door b,door check not operating properly.rem:repair/replace door checks.

    Feb 12, 2015

    Resolve
Show 29 more ↓
  • Class - 2

    Water penetrating foundation wall.rem:foundation wall allows water penetration into boiler room.rem:water proof foundation walls.

    Feb 12, 2015

    Resolve
  • Class - 2

    Re-issue ecb.35085877j step cracks.between 3rd fl.+ parapet wall,step cracks in brick work above(turn)34.rear playground near exit 6 stairs,step cracks.rem:repair step cracks.

    Feb 12, 2015

    Resolve
  • Class - 2

    Re-issue ecb 35085875x.defective doors.exit doors 1 & 7 are racked + not closing properly.rem:repair or replace doors.

    Feb 12, 2015

    Resolve
  • Class - 2

    Defective window.in room 310,window will not close and lock properly.rem:repair window.

    Feb 12, 2015

    Resolve
  • Class - 2

    Facade water penetration.facade allows water penetration to some classrooms on the 3rd fl.rem:water proof section of facade.

    Feb 12, 2015

    Resolve
  • Class - 2

    Reissue.ecb.35016986j spalling + cracked plaster walls and ceiling due to water penetration from facade in rooms 311,312,314.rem:make necessary repairs.

    Mar 3, 2014

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s)or appurtenances exterior.step cracks @ parapit wall above room 311 windows.corner of bldg has vertical stepcracks approx.20'high @ rear by playground.exit 6 stairs:metal trends

    Mar 3, 2014

    Resolve
  • Class - 2

    Failure to maintain bldg in code- compliant manner:interior room 8 b had water leaks in ceiling.rem:repair leaks.

    Mar 3, 2014

    Resolve
  • Class - 2

    Re-issue ecb 35016987l @ certification,three fpsc doors raked & wont properly close @ exits 2 & 4. rem:repair and/or replace doors.

    Mar 3, 2014

    Resolve
  • Class - 2

    Failure to maintain bldg in code-complaint manner:interior water penetrating from walls into boiler room. rem:repair walls.

    Mar 3, 2014

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s) or appurtenances.exterior.water leaking from roof into room 8b. rem:repair roof.

    Mar 3, 2014

    Resolve
  • Class - 2

    Spalling,cracked plaster on walls and/or ceiling rooms 311,312,314. rmdy: maintain building.

    Apr 30, 2013

    Resolve
  • Class - 2

    At cafeteria, three fpsc doors racked, won't properly close/operate @ exits 2 and 4. rmdy: maintain bldg.

    Apr 30, 2013

    Resolve
  • Class - 2

    Sec. 27-371(b). failure to provide the required fire rated door between classrooms - and corridor plexiglass installed @ various classrooms throughout the 2nd & 3rd flrs. remedy: provide the required material @

    Feb 18, 2011

    Resolve
  • Class - 2

    Signs not present/not conforming @ exits/flrs/or stairs.i.e. all exitshave unique numerical designation.all stairwells have unique alphabetical designation.all flrs & landings are 1/p/d/ (floor & stairs alpha)

    Jan 21, 2010

    Resolve
  • Class - 2

    Failure to provide/post a sign at job site pursuant to subsection. noted:upon inspection no contractors sign posted on fence or site.remedy:poste contractors sign. post on fence.

    Aug 19, 2009 · Penalty $400

    Resolve
  • Class - 2

    Wire glass missing @ stairwell doors/demising partitions. (approx 20 panels needed) locations: doors: stair -a- 2nd flr/opposite rm 309/stair -b- 1st flr. partition: stair -a-,2nd & 3rd flr (plexi present) stai

    Jun 18, 2009

    Resolve
  • Class - 3

    Plaster spalling or cracked or flaking locations. near room 354 insidestair/ceiling of stair -a- bulkhead (roof level)/room 312/hall ceilingoutside 357/inside rooms 305 & 352/stair -b- 3rd flr/. remedy: scrape

    Jun 18, 2009

    Resolve
  • Class - 2

    Water leaking into boiler room where ceiling meets the wall (beneath the main entry doors. remedy: repair leak.

    Jun 18, 2009

    Resolve
  • Class - 2

    Exit doors not self-closing noted: 3 doors @ exit 9 are defective in that (1) does not open at all & 2 are not easty to open & do not close.remedy:repair/replace doors.

    Oct 2, 2008

    Resolve
  • Non-hazardous

    Failure to maintain. noted: school yard asphalt pavement surface is cracked and has depression at various locations. "re-issued" 34297479m. remedy: repair defects.

    Jan 6, 2005

    Resolve
  • Non-hazardous

    Failure to provide adequate emergency power exit lights on the 2nd, 3rd floors and stairs fialure to provide emergency power to exit lights on the 2nd,3rd, floor and stairs remedy:provide emergency power

    May 22, 2001

    Resolve
  • Non-hazardous

    Failure to maintain: defect is: the two sets of entry steps on the north side, have cracked brick and mortor joints. the concrete stairs at north-west side of school, are cracked and spalling. remedy: maintai

    Apr 26, 2001

    Resolve
  • Non-hazardous

    Failure to maintain: defects is: on the north side of building, above the rear boiler room entry door, the brick and mortor joints are cracked and loose. remedy: maintain bldg. make all necessary repairs forth

    Apr 26, 2001

    Resolve
  • Non-hazardous

    Failure to maintain: defects is: on the third floor level, the upper walls and ceilings, have peeling paint that is pulling away. remedy: maintain bldg., make all necessary repairs forthwith.

    Apr 26, 2001

    Resolve
  • Hazardous

    Supervision and use of rigging equipement without a special riggers license.

    Oct 7, 2000 · Penalty $500

    Resolve
  • Non-hazardous

    Failure to maintain.defect is:the perimeter fence gates are missing at the s.w.lot.the north side entry steps have cracked brick and mortor joints.the areaway gratings are rusted and corroded.the north east and

    May 31, 2000

    Resolve
  • Non-hazardous

    Failure to maintain.defect is:the bulkhead has cracked brick and mortor joints.the coping stones have cracked,loose and missing caulking.the wooden windows ills are rotted and deteriorated.at stairway #6 at the

    May 31, 2000

    Resolve
  • Non-hazardous

    Failure to maintain.defect is:in the boiler room,the north side pilaster has cracked brick and mortor joinst.the poured concrete bases of the north,south and east entry steps,are cracked and spalling into the b

    May 31, 2000

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1925
Floors
3
Residential units
—
Building area
36,308 ft²
Lot area
79,050 ft²
Zoning
R3X
Community board
501
Council district
49
Block / lot
73 / 64
Assessed value
$4,828,500
Landmark / historic district
No

Questions about 91 Henderson Avenue

Who owns 91 Henderson Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 91 Henderson Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 91 Henderson Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 91 Henderson Avenue built?

City records list 1925 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.