420 Beach 51 Street

Queens, NY 11691BBL 4-15974-0003Map

Owner of record: NYC Department Of Parks And Recreation

420 Beach 51 Street is a school building built in 1950 in Queens, 11691. The owner of record is NYC Department Of Parks And Recreation. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
6
ECB violations
68
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 6

  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed

ECB violations · 68

  • Class - 2

    Exit door not self-closing properly. at the time of inspection observed and noted at 1st fl cafeteria 2 exit doors and at 1st floor at gym two exit doors not self-closing properly at the time of inspection when

    Mar 23, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection observed and noted at 1st floor gym 3 emergen

    Mar 23, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue 35678763p. failure to maintain building in code-compliant manner. illumination for exits. emg lights not working when checking many areas. remedy: repair/replace lighting.

    Mar 28, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances. noted: at cellar, foundation wall and concrete pad has become porous allowing the rain water and ground water seeping through the concrete pad. approx. y"

    Apr 23, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances-noted: spalling plaster and damage to the ceiling noted at following locations due to roof leak: hallway in front of room #319, 320, 322, 324 ceiling in roo

    Apr 23, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue #35672978p. failure to maintain building in code-compliant manner: illumination for exits discharges and public corridors per 1006.1; 27-381. noted: the following emergency exit lighting found inoperati

    Apr 23, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35636335n(4/14/2022)failure to maintain building in code-compliant manner.exp#1 left side handrail on group is loose/missing fasteners on plate to concrete etc.rem:repair and/or replace.

    Apr 25, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35636333j(4/14/2022)failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381 not operational when tested at gymnasium entran

    Apr 25, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at exp #1 on left side handicap ramp railing on left side is loose.remedy:repair and/or replace.

    Apr 14, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted the door to the upper roof at stair a bulkhead is not working properly.remedy:repair and/or replace.

    Apr 14, 2022 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Exit door not self-closing.noted:at 1st floor gymnasium entrance by 124 auditorium entrance & left rear, smoke at stair c exterior door at exit 1 & smoke at main entrance to building; exit doors are not working

    Apr 14, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted:fence door to gas meter enclsure missing at exp #1.remedy:repair and/or replace.

    Apr 14, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.noted:at 1st floor exit sign by stair a by 126,124, above gymnasium entrance

    Apr 14, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue35495332l issued5/18/20.failure to maintain bldg in codecompliant manner:@corridor b/w rm321&322 cutting date missing&signs of leaks&garbage bin filled w/water.repair &/or replace.

    Feb 18, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35415071j failure to maintain building at time of inspection of inspection observed at the boiler room obvious signs of water penetration thru foundationi was informed that after substantial rain the wa

    May 18, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner observed at time of inspection the roof leaks somewhere above rooms #322 and 321 the corridor just outside these 2 rooms shows very obvious signs of th leak

    May 18, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances. noted:at boilerroom,foundation wall have become porous allowing the rain water into the boiler room. at the time of inspection,approx. 1/2" water puddle ob

    Apr 25, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:use of prohibited door and/or hardware per bc 1008.1.8;27-371(j). noted:at auditorium main entrance,kick down door holders are attached to all 4 doors. reme

    Apr 25, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: at electrical room, illegal storage of electrical wires spools, cart, ladders etc. remedy: comply with notice of violations

    Apr 25, 2019

    Resolve
  • Class - 2

    Exit door not self-closing. noted: at 1st fl - room 111 adjacent to boiler room, exit double door open into the playground, not self-closing. remedy: repair/replace door

    Apr 25, 2019

    Resolve
  • Class - 3

    Failure to maintain bldg walls or appurtenances. note: at inspection on corner of school premises(beach 51 st & beach channel drive)flag pole is in poor condition rusted throughout including the base.

    Jul 10, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. no fire stopping per bc 712.3; 27-345 reissue #35207949m issued on 10/17/16 note: at cellar level in gas meter room holes penetrating the walls no fire

    Jul 10, 2017

    Resolve
  • Class - 2

    Reissue #35147741l.failure to maintain bldg in code-compliant manner:no fire stopping per bc 712.3;27-345.noted:@gas meter room.big holes 1"-8" w.no fire stopping.rem:provide/maintain fire stopping.

    Oct 17, 2016

    Resolve
  • Class - 2

    Fail maintain bldg in compliant manner:lack emergency light for exits.note:three emergency exit lights above the egress doors in the gym are inoperative. rem: comply w/nov

    Oct 1, 2015

    Resolve
  • Class - 2

    Fail maintain bldg compliant manner: no fire stopping. note:holes penetrating the walls in the gas meter room. fire stopping is *not* adequate. rem: comply w/nov.

    Oct 1, 2015

    Resolve
  • Class - 2

    Water penetration into boiler room & basement through floor slab &/or foundation wall. remedy: maintain building.

    Aug 19, 2014

    Resolve
  • Class - 2

    Reissue 34953861x defective lighting fixtures throughout gym 1 floor fixture covers loose/hanging. rmdy: make safe.

    Apr 17, 2013

    Resolve
  • Class - 2

    Defective lighting fixtures throughout gym 1st floor fixtures covers loose hanging lights not working properly rem; repair replace fixtures

    Apr 25, 2012

    Resolve
  • Class - 2

    Defective door at exit #1 door dragging along saddle hard to open rem: repair replace door

    Apr 25, 2012

    Resolve
  • Class - 3

    Water penetration into kitchen office with evident signs of water fromduct wrapped w/possible(acm)rem:seal/penetration

    May 19, 2011

    Resolve
  • Class - 3

    Defective hood in kitchen above stoves no power to unit.rem:repair/replace unit!

    May 19, 2011

    Resolve
  • Class - 3

    Defective a/c units in kitchen not blowing cool air.rem:maintain units

    May 19, 2011

    Resolve
  • Class - 2

    Defective doors @ exit doors 1, & exit 2 (4 door total)stuck shut.rem:repair/replace doors

    May 19, 2011

    Resolve
  • Class - 2

    Exit passageway obstruction on 2flr with multiple tables,chairs in corridor also fan room 2 means of egress sealed shut(hatch door)rem:remove obstructions

    May 19, 2011

    Resolve
  • Class - 2

    Sidewalk shed does not meet code specifications. defect is top deck & 4ft top side enclosure is missing,loose & defective @ northside sidewalk shed. shed materials have collapsed onto public walkway & street (a

    Feb 19, 2011

    Resolve
  • Class - 1

    Exit passageway obstructed on 2 fl tables chairs remedy: remove obstructions

    Apr 23, 2010

    Resolve
  • Class - 2

    Reissue: 34724161x interior bulkhead walls damaged due to exterior water penetration. remedy: repair wall.

    Jun 18, 2009

    Resolve
  • Class - 2

    Reissue: 34724160y water penetration of all bulkhead through exterior wall/roof. remedy: provide waterproofing.

    Jun 18, 2009

    Resolve
  • Class - 2

    Reissue: 34724158p. bulkhead doors locked by dead bold. remedy: provide proper hardware.

    Jun 18, 2009 · Penalty $2,500

    Resolve
  • Class - 2

    Reissue: 34724156l. exterior fire glass windows rooms 220, 221,222, 223, 224, 225 and 320,321,322,323,324,325 overland leaks allowing water to enter in b/w double glazing w/ several windows detaching from bldg

    Jun 18, 2009

    Resolve
  • Class - 2

    Rear hatch in boiler room allowing water to enter space. remedy: waterproof hatch.

    Jun 18, 2009

    Resolve
  • Class - 2

    Exterior windows w/ fiber glass curtain wall attached located at 2nd rms 220.221.222.223.224.225. & 3rd fl 320.321.322.323.324.325.are detached at side from bldg note:approx 3/8 space between window frame &

    Nov 14, 2008

    Resolve
  • Class - 2

    Nort facade horizontal cracks in brick missing & displaced mortar above 2nd fl window east & north side at 2nd fl set-back brick damaged w/ vertical stresss cracks 2nd & 3rd fl bulging peeling at parapet wall

    Nov 14, 2008

    Resolve
  • Class - 2

    Stwy 192 4 & 5 & 6 bulkhead cylender locks on all doors at roof level no panic bar at corridor door or window in door that provide exiting from security office gym & room at cellar no door check on corridor on

    Nov 14, 2008

    Resolve
  • Class - 1

    2 means of egress was provided in fan rm marked exit hatch sealed at rear of fan rm for egress marked exit remedy:remove obstruction

    Nov 14, 2008

    Resolve
  • Class - 2

    All bulkheads have leaks from roof 3 thats damaged walls & ceilings due to water penetration remedy:repair/replace

    Nov 14, 2008

    Resolve
  • Class - 2

    Water penetration in roof causing damage in bulkhead at exits stwy 1& 2 & 4,5 & 6 remedy: stop water penetration

    Nov 14, 2008

    Resolve
  • Hazardous

    Storage in electrical room on 1st floor (wooden door & leafs).reissue #34517492z.remedy:remove & keep clear of storage.

    Jul 18, 2007

    Resolve
  • Hazardous

    Ceramic brick loose,missing & displaced mortar located at 1st floor exit 3 vestibule.remedy:repair brick work.

    Jul 18, 2007

    Resolve
  • Hazardous

    Defective brickwork (parapet) located 1-2nd floor parapet @ north middle section brick bulging,peeling.2-3rd floor parapet @ north side middle cracked.note:all defects on interior of parapet.remedy:repair

    Jul 18, 2007

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1950
Floors
3
Residential units
—
Building area
141,500 ft²
Lot area
160,300 ft²
Zoning
R4
Community board
414
Council district
31
Block / lot
15974 / 3
Assessed value
$8,870,400
Landmark / historic district
No

Questions about 420 Beach 51 Street

Who owns 420 Beach 51 Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Parks And Recreation.

Does 420 Beach 51 Street have violations?

NYC HPD has no housing violations on record for this property.

Is 420 Beach 51 Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 420 Beach 51 Street built?

City records list 1950 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.