8-15 Lanett Avenue is a school building built in 1962 in Queens, 11691. The owner of record is NYC Department Of Parks And Recreation. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
17
ECB violations
81
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 17

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Jan 17, 2020

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
Show 7 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed

ECB violations · 81

  • Class - 2

    28-301.1 unlawful placement of furnishing decorations or other defectsthat obstruct access to egress from or visibility there of per fdny 2008 code;fc 1027.4.noted egress partially blocked at cellar corridor by

    Apr 2, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissued ecb #35717222l. failure to maintain building in code-compliant manner. noted: at 3rd floor classroom 321 running cracks on walls and over doorway. remedy: repair and/or replace.

    Apr 2, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissued ecb #35717221j. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridorsper bc 1006.1; 27-381. noted emergency lights #3, 13, 14, 15, 16, 24,

    Apr 2, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissued ecb #35717220h. exit door not self-closing. noted: exit door #4 and #6 not self-closing. remedy: repair/replace door.

    Apr 2, 2026 · Penalty $1,562

    Active
  • Class - 2

    Reissued ecb #35717219k. failure to maintain building in code-compliant manner. noted missing ansul system above commercial gas stove in kithchen at cafeteria. remedy: repair and/or replace.

    Apr 2, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissued ecb #35717218z. failure to maintain building in code-compliant manner. noted at 1st floor hallway front of gym, cellar front of cafeteria and 2nd floor corridor missing ceiling tiles. remedy: repair an

    Apr 2, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissued ecb #35717217r. failure to maintain building in code-compliant manner. noted at exp. #3 retaining wall has vertical cracks approx. 10' long-2 locations by park area. remedy: repair and/or replace.

    Apr 2, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35678774k. failure to maintain building in code-compliant manner. noted at expo #3 retaining wall has vertical cracks approx. 10' long 2 locations in park area. remedy: repair and/or replace wall.

    Apr 15, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35678773z. failure to maintain building in code-compliant manner. noted 1 floor hallway in front of gym ceiling leaking from roof. remedy: repair and/or replace.

    Apr 15, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35678771p. failure to maintain building in code-compliant manner. noted at cafeteria commercial gas stove missing fire suppression system ansul. remedy: repair and/or replace.

    Apr 15, 2025 · Penalty $3,125

    Active
Show 40 more ↓
  • Class - 2

    Exit door not self-closing. noted at smoke 102 and 106 and exits 4 and5 doors not closing properly. remedy: repair/replace door.

    Apr 15, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges on public corridors per bc 1006.1(2014 code).noted at 1 floor boxes #14, 15, 21, 23, 63 and auditorium emergency li

    Apr 15, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at classroom 321 3rd floor interior southwakk and over doorway running cracks. remedy: repair and/or replace.

    Apr 15, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at cellarelectrical room has illegal miscellaneous items of clutter. remedy: repair and/or replace cutter.

    Apr 15, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances. noted: at firstfloor hallway in front of the gym, ceiling leak due to defective roof.remedy: make necessary repairs.

    Apr 25, 2024 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35671765r. failure to maintain building in code-compliant manner. noted: at cafeteria 10 burner gas commercial stove do not have fire suppression system(ansul system). remedy: provide ansul system to g

    Apr 25, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue #35671764p. failure to maintain building wall(s) or appurtenances. noted: exterior wall at exp. #2, by exit #7, brick facade wall has step crack approx. 8'long. remedy: maintain exterior wall/make neces

    Apr 25, 2024 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances. noted: at exp. #3, retaining wall has vertical cracks approx. 10' long at 2 locations.-remedy: make necessary repairs.

    Apr 25, 2024 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35654963n(4/18/22)failure to maintain building in code-compliant manner:outside of exit 3 courtyard,facade wall show deteriorated condition with cracks,spalling,exposure of brick surfaces in multiple ar

    Apr 13, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35654961j(4/8/2022)failure to maintain building in code-compliant manner:at cafeteria kitchen commercial gas stove does not provide asul system installed.rem:repair and/or replace.

    Apr 13, 2023 · Penalty $1,562

    Active
  • Class - 2

    Reissue35546419l noted:@cellar level,cafeteria kitchen has commerical gas stove w/o asul system installed.repair &or replace.

    Apr 8, 2022 · Penalty $1,562

    Active
  • Class - 2

    Exit door not selfclosing.noted:smoke&exterior door@exit5&auditorium right rear exterior door arent working properly.repair/replace door

    Apr 8, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:facade outside of exit3 has excessive spalling masonry stucco in various areas thruout.repair &or replace.

    Apr 8, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.noted:emergencylight #28@3fl stairwelle& #7a by exit6 are inop.repair/replace lightin

    Apr 8, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35495341h(5/26/2020)failure to maintain bldg in code-compliant manner.at the time of inspection & observed at kitchen gas commercial stove w/no fire suppression systems(aka ansul system)remedy:provide

    Feb 4, 2021 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35422174h failure to maintain bldg. observed at time of inspection,the kitchen has a gas burning stove w/no ansul system for fire protection. remedy: provide ansul system.

    May 26, 2020 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code compliant manner. noted: at cafeteria, gas stove have no fire suppression system (ansul system). remedy: provide ansul system

    Apr 30, 2019

    Active
  • Class - 2

    Reissue #35329328p failure to maintain building in code compliant manner. noted: at 3rd floor, ceiling leak in classroom 317, 102 104, 106, 108 at 1st floor. remedy: make necessary repairs

    Apr 30, 2019

    Resolve
  • Class - 2

    Reissue #35329325j failure to maintain building in code compliant manner. noted: at 3rd floor corridor, cracks throughout and in classrooms at 3rd floor. remedy: make necessary repairs

    Apr 30, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted:the following doors do not operate properly due to hardware problem/missing. at3rd fl room 315,at 1st fl exit f,exit 4 next to room 101,exit 5,at aud

    Apr 30, 2019

    Resolve
  • Class - 2

    Reissue: 35271622r failure to maintain building in code compliant manner. noted: at roof level material is in poor condition with soft spot to the touch throughout. rmdy: make necessary repair.

    May 24, 2018

    Resolve
  • Class - 2

    Reissue: 35271621p failure to maintain building in code compliant manner. noted: active leak in auditorium, gym and room 301,102,104,106and 108. rmdy: make necessary repairs.

    May 24, 2018

    Resolve
  • Class - 2

    Reissue: 35271876r failure to maintain building in code compliant manner. noted: at third floor level ear room 319,317 and throughout the 3rd floor corridor, vertical and horizontal step cracks. rmdy: mak

    May 24, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: at gas meter room, illegal storage of carboard boxes. rmdy: comply with notice of violation.

    May 24, 2018

    Resolve
  • Class - 2

    Failure to maintain building in a code compliant manner. note: at inspection active leaks in auditorium, gym and room 301. as also in rooms 102, 104 106 & 108 signs of mold. rem: comply with the notice of viola

    Jun 19, 2017

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. note: at inspection at roof level material is in poor condition with soft spot to the touch throughout. as also hvac room below roof/above the auditorium l

    Jun 19, 2017

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. note: at inspection at 3rd floor level near 319, 317 and through out the 3rd floor corridors vertical and horizontal step cracks. as also on 1st floor entr

    Jun 19, 2017

    Resolve
  • Class - 2

    Reissue#35148004x failure to maintain bldg walls or appurtenances. noted: water peneration through facade into rooms#102,104,106,108,317,322,301,306. remedy: make necessary repairs.

    Nov 4, 2016

    Resolve
  • Class - 2

    Reissue#35148003y failure to maintain bldg in code compliant manner. noted: spalling plaster on classroom wall in room#102,104,106,108,3107,322,301,306 due to water penetration. remedy: make necessary repair.

    Nov 4, 2016

    Resolve
  • Class - 2

    Construction

    Sep 25, 2015

    Resolve
  • Class - 2

    Construction

    Sep 25, 2015

    Resolve
  • Class - 2

    Construction

    Sep 25, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code complaint manner.noted:@ cellar level@ cafeteria @ b19 one door is missing.rem:comply w/ the code

    Sep 25, 2015

    Resolve
  • Class - 2

    Construction

    Sep 25, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner failure to provide wired glass vision panles per 27-371(b)noted:@ cellar level @ cafeteria@ b19 one door missing wired vision panels.rem:comply w/ the code.

    Sep 25, 2015

    Resolve
  • Class - 2

    Water penetration from roof into school ceiliing @ 3 fl stair d,hallway outside 322,in rooms 301,304,306.also @ 1fl main entry vestible.rem:maintain bldg.

    Jul 22, 2014

    Resolve
  • Class - 2

    Water penetration through facade into rooms 102,104,106,108,317.rem:maintain bldg.

    Jul 22, 2014

    Resolve
  • Class - 2

    Spalling plaster on classroom wall in rooms 102,104,106,108 & 317.rem:maintain bldg.

    Jul 22, 2014

    Resolve
  • Class - 2

    @ first fl,main entry doors(north)&entry doors west side bind,rub on saddle.door difficult to operate.rem:maintain bldg.

    Jul 22, 2014

    Resolve
  • Class - 3

    Reissue 34941713x. defective doros noted at 3 fllr stair g 2 floor stair d,g,1 floor stair g and cafeteria door slam shut. rmdy: repair/replace doors.

    Apr 17, 2013

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1962
Floors
4
Residential units
—
Building area
95,000 ft²
Lot area
100,500 ft²
Zoning
R4-1
Community board
414
Council district
31
Block / lot
15597 / 1
Assessed value
$7,748,100
Landmark / historic district
No

Questions about 8-15 Lanett Avenue

Who owns 8-15 Lanett Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Parks And Recreation.

Does 8-15 Lanett Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 8-15 Lanett Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 8-15 Lanett Avenue built?

City records list 1962 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.