10-45 Nameoke Street

Queens, NY 11691BBL 4-15557-0025Map

Owner of record: NYC Department Of Education

10-45 Nameoke Street is a school building built in 1935 in Queens, 11691. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
35
ECB violations
71
HPD complaints
1

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 35

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 25, 2019

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 28, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 17, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 2, 2016

    Dob violation - resolved
Show 25 more ↓
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 11, 2012

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 4, 2011

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Vcat1-elevator annual inspection / test elevatorrequired

    Oct 8, 2010

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 8, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 31, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 27, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 20, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 15, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 20, 2003

    Dob violation - resolved
  • Elevator elevatorrequired

    4p4779

    Sep 24, 2002

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 29, 1990

    Dob violation - dismissed
  • Elevator elevatorrequired

    (28)clean oil..(51)provide in cab capacity plate 3500lbs (52)clean car top (47)remove all non elevator storage

    Apr 19, 1989

    Dob violation - resolved

ECB violations · 71

  • Class - 2

    Reissue #35691652z. date of issue: 03/31/2025. failure to maintain building in code-compliant manner. lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.1; 27-542. at the tim

    Mar 24, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35678721r. date of issue: 04/18/2024. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspectio

    Mar 24, 2026 · Penalty $3,125

    Active
  • Class - 2

    Exit door not self-closing properly. at the time of inspection observed and noted at 2nd floor stairway "b" 2 exit doors, at 2nd floor one corridor exit door near rm-210, at 1st floor one exit door near stairwa

    Mar 24, 2026 · Penalty $625

    Active
  • Class - 2

    Reissue 35678722z. failure to maintain building in code-compliant manner: lack of emergency lighting for exits, exit dishcharges and public corridors per bc 1006.1; 27-542 emg lights not working in dance room a

    Mar 31, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue #3564966z. failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per 1006.1; 27-381. noted: the following emergency exit lighting found inop

    Apr 18, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35654966z failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per 1006.1,27-381.noted:the following emergency exit lighting found inoperatio

    Apr 18, 2024 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.lack of emergency lighting for exits,exit discharges and public corridors per bc 1006.1,27-542.noted:at 4th floor dance room#405 and at cafeteria one of the

    Apr 18, 2024 · Penalty $1,250

    Active
  • Class - 2

    Reissue35415053x noted:@4fl smoke by elevator bank,2fl smoke by 214&cellar level smoke leading to boiler rm;exit doors arent working properly.repair/replace door.

    Apr 8, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.noted:@4fl exitsign by 475(fan rm),em#43 by 368,#41@auditorium,#37&38 by 3fl staira,2

    Apr 8, 2022 · Penalty $625

    Active
  • Class - 2

    28-301.1 reissue #35207938r failure to provide ventilation to gas meter room per p 115.6(1968 code),fgc appendix e(e4)(2014 code). noted: nofresh air ventilation to gas meter room. remedy: comply w/ nov

    Apr 19, 2019

    Resolve
Show 40 more ↓
  • Class - 2

    Exit door not self-closing. noted: at cellar, exit door leading to theboiler room not self-closing. remedy: repair/replace door

    Apr 19, 2019

    Resolve
  • Class - 2

    28-301.1 re-issue #35207938r failur eto provide ventilation to gas meter room per 115.6 (1968 code) fgc appendix e (e4) (2014 code) noted:no fresh air ventilation @gas meter room.rem:comply w/notice of vio.

    Jun 1, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg lack of emergency lighting. note: at main public assembly areas gym,auditorium & cafeteria defective emergency lighting. remedy: comply w/the notice of violation.

    Jun 16, 2017

    Resolve
  • Class - 2

    27-766 reissue 35148001k no fresh air vent at gas meter room.noted: at cellar at gas meter room. there is no fresh air ventilation. rmdy: provide ventilation.

    Oct 13, 2016

    Resolve
  • Class - 2

    Construction

    Sep 25, 2015

    Resolve
  • Class - 2

    Reissue 35012344j no fresh air ventilation gas meter room.rem:provide ventilation.

    Jul 22, 2014

    Resolve
  • Class - 2

    27-765 reissue 34958309p no ventilation to occupeid room 366 multiple kids in palce. rmdy: provide ventilation or discontinue use.

    Apr 17, 2013

    Resolve
  • Class - 2

    34958310m reissued. exterior siding blown off inner courtyard parapet level also sagging in middle section some loose. rmdy: make safe!

    Apr 17, 2013

    Resolve
  • Class - 2

    Reissue 34941723j no fai gas meter room. rmdy: provide ventilation.¦

    Apr 17, 2013

    Resolve
  • Class - 1

    Spalling concrete at courtyard decorative stone above windows. large pcs missing/loose exposing rebar. rmdy: partial vacate courtyard or provide protection.

    Apr 17, 2013

    Resolve
  • Class - 2

    Sec. 27-766. reissue: 34918123k, 34839140r, 34791837r. no fresh air intake in gas meter room. remedy: provide fai.

    May 21, 2012

    Resolve
  • Class - 2

    Guardrail missing from inner courtyard entrance at 2 flr. missing guardrail. remedy: provide guardrail!

    May 21, 2012

    Resolve
  • Class - 2

    Sec. 27-765. failure to provide ventilation into room 366, room occupied at time of inspection. remedy: provide ventilation into room.

    May 21, 2012

    Resolve
  • Class - 2

    Exterior siding blown off inner courtyard. at parapet level. remedy: make safe.

    May 21, 2012

    Resolve
  • Class - 2

    Reissue 34791837r,34839140r missing fai in gas meter room. remedy: install fai.

    Jun 29, 2011

    Resolve
  • Class - 2

    Shifting decorative cornice @ rear of bldg adjacent to entrance parking lot. remedy : secure stone

    Apr 23, 2010

    Resolve
  • Class - 2

    Reissue # 34791837r missing fai in gas meter room. remedy : provide f.a.i

    Apr 23, 2010

    Resolve
  • Class - 2

    No fresh air vent gas meter room. remedy: provide ventilation.

    Jun 17, 2009

    Resolve
  • Class - 2

    Reissue: 34724131p. firestopping missing in gas and electrical meter rooms and over entry door into boiler room. remedy: provide firestopping.

    Jun 17, 2009

    Resolve
  • Class - 1

    Use of prohibited door hardware. stop button on overhead stops of stairwell and smoke corridor doors has been removed and re-installed in opposite side of closer arm, being used as a "hold-open" & not allowing

    Jun 17, 2009

    Resolve
  • Class - 2

    Reissue: 34724133z. water penetration in cellar corridor outside roomsb8 & b10. remedy: waterproof bldg.

    Jun 17, 2009

    Resolve
  • Class - 2

    Reissue: 34724134k. skylights leaking in rooms 447a,347,323,327,331,335,305,247a,261,235,209,211. remedy: stop water penetration.

    Jun 17, 2009

    Resolve
  • Class - 2

    Number 4 on 40 yardline of athletic field missing. trip hazard exists.remedy: replace missing number.

    Jun 17, 2009

    Resolve
  • Class - 2

    34420950x sky lights leaking in rms 447a & 3rd fl rm 347,323,327,331,335 & 305 2nd fl 247a,261,235,209,211 remedy:stop leaks in sky lights

    Nov 18, 2008

    Resolve
  • Class - 2

    34586205x no fire stopping provided in walls @ electrical rm & gas meter rm around pipes remedy:provide fire stopping

    Nov 18, 2008

    Resolve
  • Class - 2

    Column in girls locker rm has missing loose & cracked concrete reissue34586207j remedy:repair concrete

    Nov 18, 2008

    Resolve
  • Class - 2

    Water penetration in bsmt corridor in front of rm b8 & b1v reissue 34586206h remedy:water proof foundation walls

    Nov 18, 2008

    Resolve
  • Class - 2

    In stairway '2' 4th fl leaking from deck flashing remedy:repair flashing

    Nov 18, 2008

    Resolve
  • Hazardous

    Water penetration through exterior wall into basement corridor in front of room b8 & b10.remedy:stop water penetration & make all necessary repairs.

    Jul 25, 2007

    Resolve
  • Hazardous

    Defective brickwork.mortar loose,missing,spalling & bricks cracked & missing location: east facade at main entrance & @ end of large lintel (cracked missing brick).remedy:make all necessary repairs to masonry

    Jul 25, 2007

    Resolve
  • Hazardous

    Defective concrete column.column has missing,loose,cracked concrete located @ 1st floor against exterior wall in girls locker room.remedy:repair defective concrete.

    Jul 25, 2007

    Resolve
  • Hazardous

    Reissue #34514623x.no fire stopping provided in walls @ electrical room & gas meter room.remedy:provide / maintain fire stopping.

    Jul 25, 2007

    Resolve
  • Hazardous

    No fire stopping provided in walls electrical room & gas meter room. remedy:provide/maintain fire stopping.

    Apr 7, 2006

    Resolve
  • Non-hazardous

    50a/50b 50a-repair rear tube sheet holes 50b-pipe down saftey valve discharge to a safe point to prevent scalding

    Oct 14, 2005

    Resolve
  • Non-hazardous

    50 50- pipe down the saftey valve discharge to a safe point to preven t scalding

    Oct 14, 2005

    Resolve
  • Non-hazardous

    50/ 50 -pipe down saftey valve discharge to a safe pont prevent scalding

    Oct 14, 2005

    Resolve
  • Non-hazardous

    05l10 05l10 33o02 66o02 05l10 repair (fasten) electric eye 05l10 repair rigth car door strike pavel

    Oct 1, 2004

    Resolve
  • Non-hazardous

    Failure to maintain defect is stage needs resurfacing remedy make all necessary repairs

    Nov 20, 2003

    Resolve
  • Non-hazardous

    Failure to maintain defect is gymnasium auditorium very poor lighting remedy make all necessary repairs

    Nov 20, 2003

    Resolve
  • Non-hazardous

    Failure to maintain defect is ventilation in all bathrooms non existing remedy maintain bldg make all necessary repairs

    Nov 20, 2003

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Jan 17, 2020 · Apt BLDG

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1935
Floors
4
Residential units
—
Building area
163,623 ft²
Lot area
128,000 ft²
Zoning
R5
Community board
414
Council district
31
Block / lot
15557 / 25
Assessed value
$9,593,100
Landmark / historic district
No

Questions about 10-45 Nameoke Street

Who owns 10-45 Nameoke Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 10-45 Nameoke Street have violations?

NYC HPD has no housing violations on record for this property.

Is 10-45 Nameoke Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 10-45 Nameoke Street built?

City records list 1935 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.