196 Cross Bay Boulevard
Queens, NY 11693BBL 4-15313-0485Map
Owner of record: NYC Department Of Education
196 Cross Bay Boulevard is a school building built in 1950 in Queens, 11693. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 27
- ECB violations
- 66
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 27
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 25, 2019
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 12, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 27, 2016
Dob violation - resolved - Residential elevator periodic inspection/test elevatorrequired
Failure to perform category 5 inspection
Jun 1, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed
Show 17 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Nov 6, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 4, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 9, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 7, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 15, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 6, 2007
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Nov 19, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Elevator elevatorrequired
4p5805
Sep 27, 2002
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 1996
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
May 31, 1994
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 28, 1993
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 7, 1992
Dob violation - dismissed
ECB violations · 66
- Class - 2
In responding to an incident reported by superintendent that worker was installing metal box when his hands slip and he hit his head on a metal stud causing a laceration to his forehead, upon review of pre shi
May 10, 2023
Resolve - Class - 1
Bc 3307.2.1 miscellaneous violations. in responding to an incident reported by superintendent that worker was installing metal box when his hands slip and he hits his head on a metal stud causing a laceration
May 10, 2023
Resolve - Class - 1
In responding to an incident reported by superintendent that worker was installing metal box when his hands slip and he hit his head on a metal stud causing a laceration to his forehead, upon review of the ori
May 10, 2023
Resolve - Class - 2
At time of inspection due to an incident of a worker injury, to his knee after tripping and falling into an open 4 inch hole while performing stripping operations, and was sent to the hospital. the open and unc
Nov 8, 2022
Resolve - Class - 1
At the time of inspection i observed on 9 power rd, the sidewalk was closed and covered by the construction fence. there was no signage in place for pedestrians for the closed sidewalk. dot permits and code req
Nov 8, 2022 · Penalty $625
Resolve - Class - 1
Work does not conform to approved construction documents and/or approved amendements.note:at time of inspection of 2 story building full demolitions working in progress observed building demolished by mechanica
Aug 17, 2021 · Penalty $2,500
Resolve - Class - 1
Housekeeping.note:at time of inspection of 2 story building ful demolitions working activity observed building demolition by mechanical equpment adequate housekeeping has not been maintained as required.large a
Aug 17, 2021 · Penalty $625
Resolve - Class - 1
Failure to provide sidewalk shed where required.note:at time of inspection of 2 story building full demolition working in progress observed two attached building building demolished without sidewalk shed as req
Aug 17, 2021 · Penalty $2,400
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. observed at time ofinspection,the electric meter room has missing ceiling tiles making fire stopping non compliance. also unnecessary iteams are being stored
Jun 8, 2020 · Penalty $625
Resolve - Class - 2
Reissue#:35326219m failure to maintain building in code compliant manner. noted:at 2nd fl corridor,adjacent to room 203,water damage to the ceiling tiles due to active leak from the roof. remedy:make necessary
Apr 16, 2019
Resolve
Show 40 more ↓
- Class - 2
Reissue #35226376h failure to maintain building in code compliant manner. noted: at electrical room at 1st fl., open ceiling tiles and unpatched sheet rock at top of the wall. remedy: repair and/or replace
Apr 16, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner. noted: at electrical room, illegal storage of misc. items, sheetrock, boxes, computer, etc. remedy: comply with notice of violation
Apr 16, 2019
Resolve - Class - 2
Emergency signs at elevator call stations missing. noted: emergency sign at elevator call station are missing at all floors. remedy: installsigns
Apr 16, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner. use of prohibited door and/or hardware per bc 1008.1.8;27-371(j). noted:kick down door holders are attached to the doors throughout the building. remedy:re
Apr 16, 2019
Resolve - Class - 2
Reissue: 35226376h failure to maintain building in code compliant manner. no fire stopping per bc 712.3; 27-345. noted: at electrical room open ceiling tile and holes w/no fire stopping. rmdy:provide/mainta
May 22, 2018
Resolve - Class - 2
Reissue: 35226375x failure to maintain building in code compliant manner. noted: at 2nd floor corridor adjacent to room 203, water damage to the ceiling tiles and active leak from the roof. rmdy:repair and/
May 22, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. no fire stopping per bc 712.3;27-345. note: at 1st fl level in electrical room open ceiling tiles & unpatched sheet rocl at top of walls. remedy: comply w/the
Jun 15, 2017
Resolve - Class - 2
Failure to maintain building in code-compliant manner. note: at 2nd flr level in rooms 203,203b and corridor adjacent from rooms missing ceiling files and water damage active leak was told by school personnel
Jun 15, 2017
Resolve - Class - 2
Failure to maintain building in code compliant manner. noted: at electrical room, metal safe, tables, chairs, boxes, books being stored. rmdy: remove combustible material.
Oct 14, 2016
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted:at 2nd flor ceiling leak next to room 203b due to roof leak. rmdy: make necessary repairs.
Oct 14, 2016
Resolve - Class - 2
Construction
Sep 28, 2015
Resolve - Class - 2
Water penetration from roof into rm 206 & hallway outside rm 206.rem:maintain bldg.
Jul 29, 2014
Resolve - Class - 2
Spalling,broken concrete @ side walk of entrance steps on shad creek rd side of school.rem:maintain school perimeter.
Jul 29, 2014
Resolve - Class - 2
27-765 no ventilation into room 203a 2fl room was designed as storage room now occupied as office.rmdy: provide ventilation.
May 1, 2013
Resolve - Class - 2
Partial obstruction exit passageway/floor front of room 109,and exit 4 with computer carts,printers. rmdy: remove obstruction.
May 1, 2013
Resolve - Class - 2
Reissue: 34724141z,34791897z,34846388x,34918151h. storage of combustible material inside electrical panel room,& oil tank room. remedy: remove all storage.
Jul 11, 2012
Resolve - Class - 2
Defective exit door frame at exit #4,bottom of frame rotted out,not connected at base. remedy: replace frame.
Jul 11, 2012
Resolve - Class - 2
Missing drop ceiling throughout 2 floor. remedy: repair ceiling.
Jun 29, 2011
Resolve - Class - 2
Reissue 34724141z,34791897z,34846388x storage of combustible material inside electrical panel room/oil tank room. remedy: remove all storage.
Jun 29, 2011
Resolve - Class - 2
Reissue 34791899m,34846390p water penetration from roof into 60 multiple rooms in on 2nd floor & into 2 fl corridor,also in tunnel wall 1st floor. remedy: seal leaks.
Jun 29, 2011
Resolve - Class - 2
Re: 34791828p corridor width decreased by obstruction on 1st fl rear corridor. remedy: remove obstructions.
Jun 29, 2011
Resolve - Class - 2
Exterior wall slightly shifting along driveway also cracks along parapet with missing loose mortar joints.also gutters througout falling/loose.remedy:make safe/repairs.
May 28, 2010
Resolve - Class - 3
Defective windows throughout bldg approx 60%.remedy:repair windows.
May 28, 2010
Resolve - Class - 2
Reissue 34724141z.storage inside electrical panel room and oil tank room.remedy:remove storage!
May 28, 2010
Resolve - Class - 1
Haz:reissue #34724142k,34791828p exit passageway obstructed a 1fl in front of exit doors,also througout corridor on 1st floor.remedy:removeobstruction forthwith!!!
May 28, 2010
Resolve - Class - 2
Water penetration throughout 2 floor also 1st floor tunnel around window.remedy:seal penetration.
May 25, 2010
Resolve - Class - 2
Gutters located in schoolyard behind room 2 (cafeteria) bulging and loose. remedy: repair/replace gutters.
Jun 17, 2009
Resolve - Class - 2
Reissue: 34724143m. broken glass block rm #2 multi-purpose rm. remedy:replace broken glass block.
Jun 17, 2009
Resolve - Class - 2
Reissue 34724140r. water entering bldg from roof at first floor connecting tunnel & second fl hallway in front of elevator. remedy: repair/maintain bldg .
Jun 17, 2009
Resolve - Class - 2
Reissue 34724142k. hallway corridor used for storage of school furniture & supplies. remedy:remove obstructions to clear egress.
Jun 17, 2009
Resolve - Class - 2
Reissue 34724141z. electrical room used for storage of school furniture & books.remedy:discontinue illegal use - need electrical room clear.
Jun 17, 2009
Resolve - Class - 3
Retaining wall along chad creek road several 4'vertical cracks & two areas.at top broken out concrete at fence posts. remedy:repair / maintain wall.
Jun 17, 2009
Resolve - Class - 2
Reissue: 34724145x. leak around drain from roof rm 12. remedy: repair roof.
Jun 17, 2009
Resolve - Class - 2
Cracked, spalling brick at exterior bldg corners, parapet level to left & right of glass block area. remedy: repair brick wall.
Jun 17, 2009
Resolve - Class - 2
Sec. 1017.1;27-369. reissue: 34724144y. main corridor used for storageof school furniture and supplies. remedy: remove obstruction.
Jun 17, 2009
Resolve - Class - 2
Corridor between both bldgs leaking on east side at roof that damaged ceiling tile on 1st fl remedy:stop leak in roof
Nov 19, 2008
Resolve - Class - 2
Roof drain leak in custodian marked rm 12 remedy:repair/replace
Nov 19, 2008
Resolve - Class - 2
Main entrance door's vestibule hace chairs in exit passage & corridor off near cafeteria has furniture desk,chairs in a area 6' x 10' feet reducing width of corridor remedy:remove obstruction provide corridor
Nov 19, 2008
Resolve - Class - 2
34586215j block glass still broken in rm # 2 on 1st fl remedy:repair/ replace glass blocks
Nov 19, 2008
Resolve - Class - 2
Corridor on 1st fl near double corridor doors have desk in hallway w/chairs remedy:remove all items decreasing corridor width
Nov 19, 2008
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W3)
- Year built
- 1950
- Floors
- 2
- Residential units
- —
- Building area
- 54,635 ft²
- Lot area
- 46,000 ft²
- Zoning
- R3A
- Community board
- 414
- Council district
- 32
- Block / lot
- 15313 / 485
- Assessed value
- $5,416,200
- Landmark / historic district
- No
Questions about 196 Cross Bay Boulevard
Who owns 196 Cross Bay Boulevard?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 196 Cross Bay Boulevard have violations?
NYC HPD has no housing violations on record for this property.
Is 196 Cross Bay Boulevard rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 196 Cross Bay Boulevard built?
City records list 1950 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.