175-15 149 Road

Queens, NY 11434BBL 4-13381-0001Map

Owner of record: Homes For The Homeless Institute INC

175-15 149 Road is a care facility built in 1963 in Queens, 11434. The owner of record is Homes For The Homeless Institute INC. HPD has recorded 9 housing violations here, most recently on November 27, 2023.

HPD violations
9
DOB violations
42
ECB violations
78
HPD complaints
77

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
Last violation Nov 27, 2023

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 9

  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 27, 2023

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Mar 8, 2022

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Mar 8, 2022

    Closed — Violation dismissed
  • A

    Post, in a form approved by the commissioner, and maintain a notice in a common area of the building regarding the procedures that should be followed when a gas leak is suspected at public hall, 1st story

    Oct 15, 2018

    Closed — Violation closed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Dec 6, 2017

    Closed — Violation dismissed
  • C

    Provide hot water at all hot water fixtures in the entire apartment located at apt 456, 4th story, 2nd apartment from north at east

    Jul 14, 2016 · Apt 456

    Closed — Violation closed
  • C

    Remove the illegal fastening double cylinder key operated lock at vestibule door 1st story public hall

    Sep 9, 2012

    Closed — Violation closed
  • C

    Remove the illegal fastening double cylinder key operated lock at street entrance door to building

    Sep 9, 2012

    Closed — Violation closed
  • C

    Provide hot water at all hot water fixtures ... in the bathroom located at apt 65, 6th story

    Feb 9, 2000 · Apt 65

    Closed — Violation closed

DOB building violations · 42

  • Hazardous condition (facade) facade required

    Cycle 9c unsafe report filed

    Nov 17, 2023

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Nov 13, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 11, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 11, 2018

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Aug 22, 2018

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Aug 22, 2018

    Dob violation - dismissed
  • Construction other optional

    Observed on uppermost floor of north building two pressure gauges valv es fittings and pipe installed on the fire sprinkler system dob record s do not indicate any permits/approvals issued for this work to be don e

    Nov 18, 2017

    Vpw*-violation unserved ecb-work without permit-dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 18, 2017

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 18, 2017

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 18, 2017

    Dob violation - dismissed
Show 32 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 10, 2017

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 6, 2017

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Nov 30, 2016

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Nov 30, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 27, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 27, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 21, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 21, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 12, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 12, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 2, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 2, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 30, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 30, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 7, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 7, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 17, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 17, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 26, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 26, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 31, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 31, 2006

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 2, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 2, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 28, 2003

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 28, 2003

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Elevator elevatorrequired

    (73)restore elevator to working order for the purpose of inspection

    Aug 29, 1989

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 2, 1989

    Dob violation - resolved
  • Elevator elevatorrequired

    51-restore elev to service for the purpose of inspection

    Feb 2, 1989

    Dob violation - resolved

ECB violations · 78

  • Class - 1

    Class 1 door zone restrictor inoperative. this is a safety feature which ensures passenger safety. remedy: to restore service, email the d.o.b. [email protected]. for a reinspection. class 2: hoistway drop

    Apr 3, 2026 · Penalty $1,280

    Resolve
  • Class - 1

    Failure to maintain complete drawings and inspection logs on site, no approved drawings for supported, or pipe scaffold , nor sidewalk shed, also noted that inspection documents filled out by persons no signed

    Mar 4, 2025 · Penalty $2,500

    Resolve
  • Class - 1

    I observed the failure to maintain the netting on the pipe ladder scaffolding at exposure #1 as required in bc 3309.1all netting shall be maintained in a safe manner with a daily inspection to ensure no defects

    Mar 4, 2025 · Penalty $10,000

    Resolve
  • Class - 1

    I observed the safety lines not installed as required, i noted them installed beneath debris , passing through the counterweight assembly of the supported scaffold, and in various locations over the parapet wal

    Mar 4, 2025 · Penalty $10,000

    Resolve
  • Class - 1

    Observed excessive hole penetrations throughout building. primary in the mechanical rooms on each floor. potential fire hazard. ventilation system lead from mechanical room to clients apt is unpermitted., provi

    Mar 4, 2025 · Penalty $2,500

    Resolve
  • Class - 1

    I observed the feeds for the scaffold motors passing the doorways of the electrical room, also passing unprotected through the wall of the building, wrapped around the pipe supports of the sidewalk shed and lay

    Mar 4, 2025 · Penalty $1,600

    Resolve
  • Class - 2

    Observed quick disconnect piping to stationary gas equipment located in the kitchen. as per 411.1.1 of the fgc commercial cooking appliances. commercial cooking appliances installed on casters and appliances th

    Mar 13, 2024 · Penalty $625

    Resolve
  • Class - 2

    Federal boiler model# fst-200. fouund fresh air fan interlock is bypassed and back flow preventer is leaking. correct violating conditions and submit a certificate of correction.

    Mar 1, 2024

    Resolve
  • Class - 1

    At cellar level, recreation/class rooms (rm # 18,18, 19, 3 & 5) exit doors & exit passageway are being blocked by gates and stored materials., remove obstruction

    Nov 3, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    I observed in the main building the installation of conduits, sub-feeder wiring,circuit breaker panels, branch circuit wiring for the installation of heating units in the rooms. no permit on file in dob records

    Nov 3, 2022 · Penalty $800

    Resolve
Show 40 more ↓
  • Class - 2

    I observed in the laundry room two switches supplying power to the washing machines with the conductors passing from one switch to another without a proper junction box to separate the line and load conductors

    Nov 3, 2022 · Penalty $800

    Resolve
  • Class - 2

    Observed - at 6th fl, bank a &b, utilities rooms (from 2nd fl to 6th fl), at cellar level mb27 rm, exit door computer rm, recreation rooms, boiler rooms, laundry rooms, electrical rooms & corridors (from first

    Nov 3, 2022 · Penalty $625

    Resolve
  • Class - 2

    Observed: - at first fl, laundry room doors, at cellar level, smoke door near elevator, exit door between boiler and laundry rooms, employees lounge rm door & , mb-21 rm. doors do not close properly due differe

    Nov 3, 2022 · Penalty $312

    Resolve
  • Class - 2

    I observed on multiple floors in the main and new buildings the installation of new emergency lights with wiremold raceways running from existing junction boxes without proper fittings for termination. photos t

    Nov 3, 2022 · Penalty $600

    Resolve
  • Class - 2

    Brake maintenance tag expired on 10/28/21.

    Nov 3, 2022 · Penalty $312

    Resolve
  • Class - 2

    Observed: -at cellar level, exit door between boiler and laundry rooms illegal hardware also, at cellar level, recreation/class rooms (rm # 18,18, 19, 3 & 5) exit doors & exit passageway are being blocked by ga

    Nov 3, 2022 · Penalty $312

    Resolve
  • Class - 1

    I observed in the basement booster pump room conduits and flexible raceways broken with exposed energized conductors. also noted conduits unsupported in the laundry room and wster booster room. this is an immed

    Nov 3, 2022 · Penalty $1,600

    Resolve
  • Class - 1

    Door zone restrictor not working tampered with disabled(cu). brake maintenance tag expired on 10/28/21.

    Nov 3, 2022 · Penalty $312

    Resolve
  • Class - 3

    Sprinkler pipe on the 2nd fl in the staircase not supported correctly. sprinkler branch is being supported with band iron and not with a hanger. as per pc 308.4hangers and anchors shall be attached to the build

    Nov 3, 2022 · Penalty $250

    Resolve
  • Class - 2

    Observed: at exposure # 1&3, bbq area cmu retaining walls, external enclosure cmu walls/ (fence), also, at cellar level storage room bank b, near electrical rm, cmu walls several cracks in different locations,

    Nov 3, 2022 · Penalty $625

    Resolve
  • Class - 1

    Door zone restrictor not working tampered with.

    Mar 2, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Noted: observed at main entrance and exit door, magnetic locking devices being use with a remote release switch approximately 6 feet away from door. premise is not a prison nor a bank, provide legal hardware

    Feb 7, 2020

    Resolve
  • Class - 2

    Noted: building altered and occupied under alt-1 application #401685798 without obtaining a valid certificate of occupancy., obtain a valid c of o or discontinue illegal occupancy

    Feb 7, 2020 · Penalty $1,250

    Active
  • Class - 2

    Noted: observed water penetrating into the electrical room at cellar from south exterior stairs., maintain exterior building wall

    Feb 7, 2020

    Resolve
  • Class - 2

    Noted: observed at roof, loose/missing corrugated metal around bulkhead., repair and/or replace

    Feb 7, 2020

    Resolve
  • Class - 2

    Noted: observed water penetrating into the electrical room at cellar from south exterior stairs., maintain exterior building wall

    Feb 7, 2020

    Resolve
  • Class - 1

    I observed in the main electrical room located in the basement, the main copper detail, drilled multiple times to add additional lugs and wires, to tap electrical power for additional service switches. main cop

    Feb 7, 2020 · Penalty $1,600

    Resolve
  • Class - 1

    Observed the installation of conductors from a 200 amp disconnect to a circuit breaker enclosure labeled "security" in the northside electrical room, these conductors are fused protected improperly at 150 amps

    Jul 31, 2019 · Penalty $4,800

    Resolve
  • Class - 2

    Observed in northside building basement electrical meter room the installation of conduits, branch circuit wiring, over-current devices for a location labeled "security". also noted the installation of disconn

    Jul 31, 2019 · Penalty $400

    Resolve
  • Class - 2

    North building main electrical room, large holes were cut in concrete ceiling for drain pipes from bathroom above, area is open and has not been fires top to match rating of the room. , provide/maintain fire st

    Jul 31, 2019 · Penalty $625

    Resolve
  • Class - 2

    Observed in the northside building in the basement and halls on all floors the improper installation of emergency lights with exposed energized conductors, raceways terminated with no or improper fittings., pe

    Jul 31, 2019 · Penalty $250

    Resolve
  • Class - 1

    During my scheduled inspection i observed the violating conditions as stated in ecb # 35386386y issued on 02/07/2019 still in effect. in the c of c submitted on 04/15/2019 and notarized on 04/11/2019 stated

    Jul 31, 2019

    Resolve
  • Class - 2

    Ec 400.8 unpermitted uses of flexible cords. observed in osy closets on the 5th fl southside the connection of flexible cords to ceiling junction box to supply permanent power. remedy:comply w/ code/use flexibl

    Feb 7, 2019 · Penalty $400

    Resolve
  • Class - 2

    Electrical work w/o a permit. observed in elevator motor room the installation of fan unit for cooling,w/ compressor unit mounted on ledge above stairway bulkhead,branch ckt wiring and interconnect wiring also

    Feb 7, 2019 · Penalty $400

    Resolve
  • Class - 2

    Failure to comply w/ the commissioner's order contained in summons/violation#35346382k issued on 7/16/18 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. remedy:comply w/ commissio

    Feb 7, 2019 · Penalty $625

    Resolve
  • Class - 2

    Unapproved/unsafe/unsuitable electrical equipment,apparatus,materials,devices,appliances or wiring in use. observed in rear loading area sump pump cord passing through exterior wall,an extension cord passing th

    Feb 7, 2019 · Penalty $1,000

    Resolve
  • Class - 1

    59l10,78b14,80e10. 59l10-brake monitoring switch defective missing parts. 78b14-governor tension weight needs to be shorten. 80e10-loud banging noise coming from the counterweight between fifth and sixth

    Jan 8, 2019 · Penalty $1,250

    Resolve
  • Class - 1

    Cu5a10,cu59l10,78b14. 5a10-door zone restrictor not working tampered with. this is a safety device to ensure passenger; 59l10-brake monitoring switch defective missing contact and other parts. 78b14-governor

    Jan 8, 2019 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to comply with the commissioner's order contained in summons/violation# 35331054h issued on 11/18/17 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. work without a permit.

    Dec 17, 2018 · Penalty $1,250

    Resolve
  • Class - 1

    Failure to comply w/the comm's order contained in summons/vio#353310534 issued on 11/18/18 & to file a c of c pursuant to 28-201.1 & 1rcny 102-01. work w/o a permit. remedy: comply w/comm's order &/or file a c

    Oct 15, 2018

    Resolve
  • Class - 2

    Failure to comply with the commissioners order contained in summons/ violation #35331053h issued on 11/18/18 and to file a ceritificate of correction pursuant to 28-201.1 and 1rcny 102-01. work without a permi

    Aug 22, 2018 · Penalty $1,250

    Resolve
  • Class - 2

    Unapproved/unsafe/unsuitable electrical equipment,apparatus,materials,devices,appliances or wiring in use.observed in rear loading area sump cord passing through exterior wall;an extension cord passing through

    Jul 16, 2018 · Penalty $800

    Resolve
  • Class - 2

    Ec 408.4 failure to provide circuit directory or circuit identification observed throughout kitchen,boiler rooms, (2) halls-disconnect switches to pumps,equipment & exhaust fans,circuit breaker panels w/out cir

    Jul 16, 2018 · Penalty $400

    Resolve
  • Class - 2

    Failure to comply w/the comm's order contained in summons/vio #35272267x issued on 07/17/2017 & to file a cert of correction pursuant to 28-201.1 & 1rcny 102-01.for electrical work performed w/out permit.rem:co

    Jul 16, 2018 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to comply w/the comm's order contained in summons/vio #35272265m issued on 07/17/2017 & to file a cert of correction pursuant to 28-201.1 & 1rcny 102-01.rem:comply w/comm's order &/or file a cert of cor

    Jul 16, 2018 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to install ground fault circuit interrupter (gfci) protection as required. observed in commercial kitchen no gfci receptables as required also noted in dining room gfci receptacle defective (not working

    Jul 16, 2018 · Penalty $1,250

    Resolve
  • Class - 2

    Luminaires & lampholders not installed in an approved manner.observed in utility closets & throughout halls & stairways improperly installedlights (emergency type),ceiling lights supported by wire,ty-traps & ro

    Jul 16, 2018 · Penalty $250

    Resolve
  • Class - 2

    Failure to comply w/the comm's order contained in summons/vio #35272268h issued on 07/17/2017 & to file a cert of correction pursuant to 28-201.1 & 1rcny 102-01.for failing to label electrical equipment.rem:com

    Jul 16, 2018

    Resolve
  • Class - 2

    5:b254-5a)correct violating condition & submit a cert of correction.

    Apr 4, 2018

    Resolve
  • Class - 2

    Work without a permit.observed on uppermost floor of north buildng twopressure gauges,vavles,fitting and pipe installed on the fire sprinkler system.dob records do not indicate any permits/approvals being issue

    Nov 18, 2017 · Penalty $800

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Feb 12, 2026 · Apt 568

    Close
  • Heat/hot water

    Entire building

    Feb 9, 2026 · Apt 456

    Close
  • Heat/hot water

    Entire building

    Feb 9, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Feb 2, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Apartment only

    Jan 24, 2026 · Apt 560

    Close
  • Heat/hot water

    Entire building

    Dec 24, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 23, 2025 · Apt 265

    Close
  • Unsanitary condition

    Pests

    Aug 13, 2024 · Apt 368

    Close
  • Heat/hot water

    Entire building

    Apr 7, 2024 · Apt 356

    Close
  • Heat/hot water

    Entire building

    Mar 27, 2024 · Apt BLDG

    Close
Show 40 more ↓
  • Heat/hot water

    Entire building

    Oct 6, 2022 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Oct 4, 2022 · Apt 266

    Close
  • Heat/hot water

    Entire building

    Feb 1, 2022 · Apt 318

    Close
  • Heat/hot water

    Entire building

    Feb 1, 2022 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Jan 31, 2022 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Jan 31, 2022 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Jan 16, 2022 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Jan 11, 2022 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 21, 2021 · Apt 266

    Close
  • Heat/hot water

    Entire building

    Jan 31, 2021 · Apt 628

    Close
  • Electric

    Power outage

    Nov 4, 2020 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Sep 20, 2020 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Oct 13, 2019 · Apt 602

    Close
  • Heat/hot water

    Entire building

    Oct 6, 2019 · Apt 609

    Close
  • Heat/hot water

    Entire building

    Jun 7, 2019 · Apt 162

    Close
  • Electric

    Power outage

    Apr 3, 2019 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 11, 2018 · Apt 601

    Close
  • Heat/hot water

    Entire building

    Nov 11, 2018 · Apt 601

    Close
  • Heat/hot water

    Entire building

    Oct 14, 2018 · Apt 164

    Close
  • Heat/hot water

    Entire building

    Jan 29, 2018 · Apt 1

    Close
  • Heat/hot water

    Entire building

    Jan 8, 2018 · Apt 225

    Close
  • Heat/hot water

    Entire building

    Oct 27, 2017 · Apt 615

    Close
  • Plumbing

    Water supply

    Jun 20, 2017 · Apt 364

    Close
  • Plumbing

    Water supply

    May 15, 2017 · Apt 205

    Close
  • Heat/hot water

    Entire building

    May 15, 2017 · Apt 205

    Close
  • Heat/hot water

    Entire building

    Mar 15, 2017 · Apt 129

    Close
  • Heat/hot water

    Entire building

    Jan 25, 2017 · Apt 452

    Close
  • Heat/hot water

    Entire building

    Jul 14, 2016 · Apt 456

    Close
  • Heat/hot water

    Apartment only

    May 28, 2016 · Apt NA

    Close
  • Heat/hot water

    Apartment only

    May 28, 2016 · Apt 361

    Close
  • Heat/hot water

    Entire building

    Feb 28, 2016 · Apt 621

    Close
  • Heat/hot water

    Entire building

    Feb 24, 2016 · Apt 628

    Close
  • Heat/hot water

    Entire building

    Feb 23, 2016 · Apt 614

    Close
  • Heat/hot water

    Entire building

    Feb 23, 2016 · Apt 617

    Close
  • Heat/hot water

    Entire building

    Feb 15, 2016 · Apt BLDG

    Close
  • Plumbing

    Water supply

    Nov 2, 2015 · Apt 608

    Close
  • Heat/hot water

    Entire building

    Nov 2, 2015 · Apt 608

    Close
  • Heat/hot water

    Apartment only

    Oct 30, 2015 · Apt 501

    Close
  • Heat/hot water

    Apartment only

    Oct 4, 2015 · Apt 459

    Close
  • Heat/hot water

    Entire building

    Jun 4, 2015 · Apt 421

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Care facility (N2)
Year built
1963
Floors
6
Residential units
—
Building area
67,400 ft²
Lot area
67,325 ft²
Zoning
M1-1
Community board
413
Council district
31
Block / lot
13381 / 1
Assessed value
$7,386,300
Landmark / historic district
No

HPD registration #420414, last renewed Jul 23, 2025.

Questions about 175-15 149 Road

Who owns 175-15 149 Road?

The owner of record in NYC Department of City Planning PLUTO data is Homes For The Homeless Institute INC.

Does 175-15 149 Road have violations?

Yes. NYC HPD has recorded 9 housing violations at this property.

Is 175-15 149 Road rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 175-15 149 Road built?

City records list 1963 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.