175-15 149 Road
Queens, NY 11434BBL 4-13381-0001Map
Owner of record: Homes For The Homeless Institute INC
175-15 149 Road is a care facility built in 1963 in Queens, 11434. The owner of record is Homes For The Homeless Institute INC. HPD has recorded 9 housing violations here, most recently on November 27, 2023.
- HPD violations
- 9
- DOB violations
- 42
- ECB violations
- 78
- HPD complaints
- 77
What to know
No open immediately-hazardous violations among recent records.
Date of the most recent HPD inspection that found a problem.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 9
- IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 27, 2023
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Mar 8, 2022
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Mar 8, 2022
Closed — Violation dismissed - ANon-hazardous
Post, in a form approved by the commissioner, and maintain a notice in a common area of the building regarding the procedures that should be followed when a gas leak is suspected at public hall, 1st story
Oct 15, 2018
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Dec 6, 2017
Closed — Violation dismissed - CImmediately hazardous
Provide hot water at all hot water fixtures in the entire apartment located at apt 456, 4th story, 2nd apartment from north at east
Jul 14, 2016 · Apt 456
Closed — Violation closed - CImmediately hazardous
Remove the illegal fastening double cylinder key operated lock at vestibule door 1st story public hall
Sep 9, 2012
Closed — Violation closed - CImmediately hazardous
Remove the illegal fastening double cylinder key operated lock at street entrance door to building
Sep 9, 2012
Closed — Violation closed - CImmediately hazardous
Provide hot water at all hot water fixtures ... in the bathroom located at apt 65, 6th story
Feb 9, 2000 · Apt 65
Closed — Violation closed
DOB building violations · 42
- Hazardous condition (facade) facade required
Cycle 9c unsafe report filed
Nov 17, 2023
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 13, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 11, 2018
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 11, 2018
Dob violation - resolved - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Aug 22, 2018
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Aug 22, 2018
Dob violation - dismissed - Construction other optional
Observed on uppermost floor of north building two pressure gauges valv es fittings and pipe installed on the fire sprinkler system dob record s do not indicate any permits/approvals issued for this work to be don e
Nov 18, 2017
Vpw*-violation unserved ecb-work without permit-dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 18, 2017
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 18, 2017
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 18, 2017
Dob violation - dismissed
Show 32 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Oct 10, 2017
Dob violation - resolved - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Sep 6, 2017
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 30, 2016
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 30, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 27, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 27, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 21, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 21, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 12, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 12, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 2, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 2, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 30, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 30, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 7, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 7, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 17, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 17, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 26, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 26, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 31, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 31, 2006
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 2, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 2, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 28, 2003
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 28, 2003
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Elevator elevatorrequired
(73)restore elevator to working order for the purpose of inspection
Aug 29, 1989
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 2, 1989
Dob violation - resolved - Elevator elevatorrequired
51-restore elev to service for the purpose of inspection
Feb 2, 1989
Dob violation - resolved
ECB violations · 78
- Class - 1
Class 1 door zone restrictor inoperative. this is a safety feature which ensures passenger safety. remedy: to restore service, email the d.o.b. [email protected]. for a reinspection. class 2: hoistway drop
Apr 3, 2026 · Penalty $1,280
Resolve - Class - 1
Failure to maintain complete drawings and inspection logs on site, no approved drawings for supported, or pipe scaffold , nor sidewalk shed, also noted that inspection documents filled out by persons no signed
Mar 4, 2025 · Penalty $2,500
Resolve - Class - 1
I observed the failure to maintain the netting on the pipe ladder scaffolding at exposure #1 as required in bc 3309.1all netting shall be maintained in a safe manner with a daily inspection to ensure no defects
Mar 4, 2025 · Penalty $10,000
Resolve - Class - 1
I observed the safety lines not installed as required, i noted them installed beneath debris , passing through the counterweight assembly of the supported scaffold, and in various locations over the parapet wal
Mar 4, 2025 · Penalty $10,000
Resolve - Class - 1
Observed excessive hole penetrations throughout building. primary in the mechanical rooms on each floor. potential fire hazard. ventilation system lead from mechanical room to clients apt is unpermitted., provi
Mar 4, 2025 · Penalty $2,500
Resolve - Class - 1
I observed the feeds for the scaffold motors passing the doorways of the electrical room, also passing unprotected through the wall of the building, wrapped around the pipe supports of the sidewalk shed and lay
Mar 4, 2025 · Penalty $1,600
Resolve - Class - 2
Observed quick disconnect piping to stationary gas equipment located in the kitchen. as per 411.1.1 of the fgc commercial cooking appliances. commercial cooking appliances installed on casters and appliances th
Mar 13, 2024 · Penalty $625
Resolve - Class - 2
Federal boiler model# fst-200. fouund fresh air fan interlock is bypassed and back flow preventer is leaking. correct violating conditions and submit a certificate of correction.
Mar 1, 2024
Resolve - Class - 1
At cellar level, recreation/class rooms (rm # 18,18, 19, 3 & 5) exit doors & exit passageway are being blocked by gates and stored materials., remove obstruction
Nov 3, 2022 · Penalty $1,250
Resolve - Class - 2
I observed in the main building the installation of conduits, sub-feeder wiring,circuit breaker panels, branch circuit wiring for the installation of heating units in the rooms. no permit on file in dob records
Nov 3, 2022 · Penalty $800
Resolve
Show 40 more ↓
- Class - 2
I observed in the laundry room two switches supplying power to the washing machines with the conductors passing from one switch to another without a proper junction box to separate the line and load conductors
Nov 3, 2022 · Penalty $800
Resolve - Class - 2
Observed - at 6th fl, bank a &b, utilities rooms (from 2nd fl to 6th fl), at cellar level mb27 rm, exit door computer rm, recreation rooms, boiler rooms, laundry rooms, electrical rooms & corridors (from first
Nov 3, 2022 · Penalty $625
Resolve - Class - 2
Observed: - at first fl, laundry room doors, at cellar level, smoke door near elevator, exit door between boiler and laundry rooms, employees lounge rm door & , mb-21 rm. doors do not close properly due differe
Nov 3, 2022 · Penalty $312
Resolve - Class - 2
I observed on multiple floors in the main and new buildings the installation of new emergency lights with wiremold raceways running from existing junction boxes without proper fittings for termination. photos t
Nov 3, 2022 · Penalty $600
Resolve - Class - 2
Brake maintenance tag expired on 10/28/21.
Nov 3, 2022 · Penalty $312
Resolve - Class - 2
Observed: -at cellar level, exit door between boiler and laundry rooms illegal hardware also, at cellar level, recreation/class rooms (rm # 18,18, 19, 3 & 5) exit doors & exit passageway are being blocked by ga
Nov 3, 2022 · Penalty $312
Resolve - Class - 1
I observed in the basement booster pump room conduits and flexible raceways broken with exposed energized conductors. also noted conduits unsupported in the laundry room and wster booster room. this is an immed
Nov 3, 2022 · Penalty $1,600
Resolve - Class - 1
Door zone restrictor not working tampered with disabled(cu). brake maintenance tag expired on 10/28/21.
Nov 3, 2022 · Penalty $312
Resolve - Class - 3
Sprinkler pipe on the 2nd fl in the staircase not supported correctly. sprinkler branch is being supported with band iron and not with a hanger. as per pc 308.4hangers and anchors shall be attached to the build
Nov 3, 2022 · Penalty $250
Resolve - Class - 2
Observed: at exposure # 1&3, bbq area cmu retaining walls, external enclosure cmu walls/ (fence), also, at cellar level storage room bank b, near electrical rm, cmu walls several cracks in different locations,
Nov 3, 2022 · Penalty $625
Resolve - Class - 1
Door zone restrictor not working tampered with.
Mar 2, 2020 · Penalty $1,250
Resolve - Class - 2
Noted: observed at main entrance and exit door, magnetic locking devices being use with a remote release switch approximately 6 feet away from door. premise is not a prison nor a bank, provide legal hardware
Feb 7, 2020
Resolve - Class - 2
Noted: building altered and occupied under alt-1 application #401685798 without obtaining a valid certificate of occupancy., obtain a valid c of o or discontinue illegal occupancy
Feb 7, 2020 · Penalty $1,250
Active - Class - 2
Noted: observed water penetrating into the electrical room at cellar from south exterior stairs., maintain exterior building wall
Feb 7, 2020
Resolve - Class - 2
Noted: observed at roof, loose/missing corrugated metal around bulkhead., repair and/or replace
Feb 7, 2020
Resolve - Class - 2
Noted: observed water penetrating into the electrical room at cellar from south exterior stairs., maintain exterior building wall
Feb 7, 2020
Resolve - Class - 1
I observed in the main electrical room located in the basement, the main copper detail, drilled multiple times to add additional lugs and wires, to tap electrical power for additional service switches. main cop
Feb 7, 2020 · Penalty $1,600
Resolve - Class - 1
Observed the installation of conductors from a 200 amp disconnect to a circuit breaker enclosure labeled "security" in the northside electrical room, these conductors are fused protected improperly at 150 amps
Jul 31, 2019 · Penalty $4,800
Resolve - Class - 2
Observed in northside building basement electrical meter room the installation of conduits, branch circuit wiring, over-current devices for a location labeled "security". also noted the installation of disconn
Jul 31, 2019 · Penalty $400
Resolve - Class - 2
North building main electrical room, large holes were cut in concrete ceiling for drain pipes from bathroom above, area is open and has not been fires top to match rating of the room. , provide/maintain fire st
Jul 31, 2019 · Penalty $625
Resolve - Class - 2
Observed in the northside building in the basement and halls on all floors the improper installation of emergency lights with exposed energized conductors, raceways terminated with no or improper fittings., pe
Jul 31, 2019 · Penalty $250
Resolve - Class - 1
During my scheduled inspection i observed the violating conditions as stated in ecb # 35386386y issued on 02/07/2019 still in effect. in the c of c submitted on 04/15/2019 and notarized on 04/11/2019 stated
Jul 31, 2019
Resolve - Class - 2
Ec 400.8 unpermitted uses of flexible cords. observed in osy closets on the 5th fl southside the connection of flexible cords to ceiling junction box to supply permanent power. remedy:comply w/ code/use flexibl
Feb 7, 2019 · Penalty $400
Resolve - Class - 2
Electrical work w/o a permit. observed in elevator motor room the installation of fan unit for cooling,w/ compressor unit mounted on ledge above stairway bulkhead,branch ckt wiring and interconnect wiring also
Feb 7, 2019 · Penalty $400
Resolve - Class - 2
Failure to comply w/ the commissioner's order contained in summons/violation#35346382k issued on 7/16/18 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. remedy:comply w/ commissio
Feb 7, 2019 · Penalty $625
Resolve - Class - 2
Unapproved/unsafe/unsuitable electrical equipment,apparatus,materials,devices,appliances or wiring in use. observed in rear loading area sump pump cord passing through exterior wall,an extension cord passing th
Feb 7, 2019 · Penalty $1,000
Resolve - Class - 1
59l10,78b14,80e10. 59l10-brake monitoring switch defective missing parts. 78b14-governor tension weight needs to be shorten. 80e10-loud banging noise coming from the counterweight between fifth and sixth
Jan 8, 2019 · Penalty $1,250
Resolve - Class - 1
Cu5a10,cu59l10,78b14. 5a10-door zone restrictor not working tampered with. this is a safety device to ensure passenger; 59l10-brake monitoring switch defective missing contact and other parts. 78b14-governor
Jan 8, 2019 · Penalty $1,250
Resolve - Class - 2
Failure to comply with the commissioner's order contained in summons/violation# 35331054h issued on 11/18/17 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. work without a permit.
Dec 17, 2018 · Penalty $1,250
Resolve - Class - 1
Failure to comply w/the comm's order contained in summons/vio#353310534 issued on 11/18/18 & to file a c of c pursuant to 28-201.1 & 1rcny 102-01. work w/o a permit. remedy: comply w/comm's order &/or file a c
Oct 15, 2018
Resolve - Class - 2
Failure to comply with the commissioners order contained in summons/ violation #35331053h issued on 11/18/18 and to file a ceritificate of correction pursuant to 28-201.1 and 1rcny 102-01. work without a permi
Aug 22, 2018 · Penalty $1,250
Resolve - Class - 2
Unapproved/unsafe/unsuitable electrical equipment,apparatus,materials,devices,appliances or wiring in use.observed in rear loading area sump cord passing through exterior wall;an extension cord passing through
Jul 16, 2018 · Penalty $800
Resolve - Class - 2
Ec 408.4 failure to provide circuit directory or circuit identification observed throughout kitchen,boiler rooms, (2) halls-disconnect switches to pumps,equipment & exhaust fans,circuit breaker panels w/out cir
Jul 16, 2018 · Penalty $400
Resolve - Class - 2
Failure to comply w/the comm's order contained in summons/vio #35272267x issued on 07/17/2017 & to file a cert of correction pursuant to 28-201.1 & 1rcny 102-01.for electrical work performed w/out permit.rem:co
Jul 16, 2018 · Penalty $1,250
Resolve - Class - 2
Failure to comply w/the comm's order contained in summons/vio #35272265m issued on 07/17/2017 & to file a cert of correction pursuant to 28-201.1 & 1rcny 102-01.rem:comply w/comm's order &/or file a cert of cor
Jul 16, 2018 · Penalty $1,250
Resolve - Class - 2
Failure to install ground fault circuit interrupter (gfci) protection as required. observed in commercial kitchen no gfci receptables as required also noted in dining room gfci receptacle defective (not working
Jul 16, 2018 · Penalty $1,250
Resolve - Class - 2
Luminaires & lampholders not installed in an approved manner.observed in utility closets & throughout halls & stairways improperly installedlights (emergency type),ceiling lights supported by wire,ty-traps & ro
Jul 16, 2018 · Penalty $250
Resolve - Class - 2
Failure to comply w/the comm's order contained in summons/vio #35272268h issued on 07/17/2017 & to file a cert of correction pursuant to 28-201.1 & 1rcny 102-01.for failing to label electrical equipment.rem:com
Jul 16, 2018
Resolve - Class - 2
5:b254-5a)correct violating condition & submit a cert of correction.
Apr 4, 2018
Resolve - Class - 2
Work without a permit.observed on uppermost floor of north buildng twopressure gauges,vavles,fitting and pipe installed on the fire sprinkler system.dob records do not indicate any permits/approvals being issue
Nov 18, 2017 · Penalty $800
Resolve
Complaints
- Heat/hot water
Entire building
Feb 12, 2026 · Apt 568
Close - Heat/hot water
Entire building
Feb 9, 2026 · Apt 456
Close - Heat/hot water
Entire building
Feb 9, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Feb 2, 2026 · Apt BLDG
Close - Heat/hot water
Apartment only
Jan 24, 2026 · Apt 560
Close - Heat/hot water
Entire building
Dec 24, 2025 · Apt BLDG
Close - Heat/hot water
Entire building
Dec 23, 2025 · Apt 265
Close - Unsanitary condition
Pests
Aug 13, 2024 · Apt 368
Close - Heat/hot water
Entire building
Apr 7, 2024 · Apt 356
Close - Heat/hot water
Entire building
Mar 27, 2024 · Apt BLDG
Close
Show 40 more ↓
- Heat/hot water
Entire building
Oct 6, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 4, 2022 · Apt 266
Close - Heat/hot water
Entire building
Feb 1, 2022 · Apt 318
Close - Heat/hot water
Entire building
Feb 1, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 31, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 31, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 16, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 11, 2022 · Apt BLDG
Close - Heat/hot water
Entire building
Dec 21, 2021 · Apt 266
Close - Heat/hot water
Entire building
Jan 31, 2021 · Apt 628
Close - Electric
Power outage
Nov 4, 2020 · Apt BLDG
Close - Heat/hot water
Entire building
Sep 20, 2020 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 13, 2019 · Apt 602
Close - Heat/hot water
Entire building
Oct 6, 2019 · Apt 609
Close - Heat/hot water
Entire building
Jun 7, 2019 · Apt 162
Close - Electric
Power outage
Apr 3, 2019 · Apt BLDG
Close - Heat/hot water
Entire building
Nov 11, 2018 · Apt 601
Close - Heat/hot water
Entire building
Nov 11, 2018 · Apt 601
Close - Heat/hot water
Entire building
Oct 14, 2018 · Apt 164
Close - Heat/hot water
Entire building
Jan 29, 2018 · Apt 1
Close - Heat/hot water
Entire building
Jan 8, 2018 · Apt 225
Close - Heat/hot water
Entire building
Oct 27, 2017 · Apt 615
Close - Plumbing
Water supply
Jun 20, 2017 · Apt 364
Close - Plumbing
Water supply
May 15, 2017 · Apt 205
Close - Heat/hot water
Entire building
May 15, 2017 · Apt 205
Close - Heat/hot water
Entire building
Mar 15, 2017 · Apt 129
Close - Heat/hot water
Entire building
Jan 25, 2017 · Apt 452
Close - Heat/hot water
Entire building
Jul 14, 2016 · Apt 456
Close - Heat/hot water
Apartment only
May 28, 2016 · Apt NA
Close - Heat/hot water
Apartment only
May 28, 2016 · Apt 361
Close - Heat/hot water
Entire building
Feb 28, 2016 · Apt 621
Close - Heat/hot water
Entire building
Feb 24, 2016 · Apt 628
Close - Heat/hot water
Entire building
Feb 23, 2016 · Apt 614
Close - Heat/hot water
Entire building
Feb 23, 2016 · Apt 617
Close - Heat/hot water
Entire building
Feb 15, 2016 · Apt BLDG
Close - Plumbing
Water supply
Nov 2, 2015 · Apt 608
Close - Heat/hot water
Entire building
Nov 2, 2015 · Apt 608
Close - Heat/hot water
Apartment only
Oct 30, 2015 · Apt 501
Close - Heat/hot water
Apartment only
Oct 4, 2015 · Apt 459
Close - Heat/hot water
Entire building
Jun 4, 2015 · Apt 421
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Care facility (N2)
- Year built
- 1963
- Floors
- 6
- Residential units
- —
- Building area
- 67,400 ft²
- Lot area
- 67,325 ft²
- Zoning
- M1-1
- Community board
- 413
- Council district
- 31
- Block / lot
- 13381 / 1
- Assessed value
- $7,386,300
- Landmark / historic district
- No
HPD registration #420414, last renewed Jul 23, 2025.
Questions about 175-15 149 Road
Who owns 175-15 149 Road?
The owner of record in NYC Department of City Planning PLUTO data is Homes For The Homeless Institute INC.
Does 175-15 149 Road have violations?
Yes. NYC HPD has recorded 9 housing violations at this property.
Is 175-15 149 Road rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 175-15 149 Road built?
City records list 1963 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.