92-07 175 Street
Queens, NY 11433BBL 4-10215-0001Map
Owner of record: NYC Department Of Education
92-07 175 Street is a school building built in 2001 in Queens, 11433. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 70
- ECB violations
- 42
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 70
- Elevator elevatorrequired
E-elevator elevatorrequired
Dec 20, 2019
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 6, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 6, 2016
Dob violation - resolved
Show 40 more ↓
- Residential elevator periodic inspection/test elevatorrequired
Failure to perform category 5 inspection
Jun 1, 2016
Dob violation - dismissed - Residential elevator periodic inspection/test elevatorrequired
Failure to perform category 5 inspection
Jun 1, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 18, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 18, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 2, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 2, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 22, 2010
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 3, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 3, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 25, 2006
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 25, 2006
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 1, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 1, 2005
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 21, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 19, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 19, 2002
Dob violation - dismissed - Marquee other required
Cmq-marquee other required
Jan 16, 2002
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 10, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Marquee other required
Cmq-marquee other required
Jan 13, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 20, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed
ECB violations · 42
- Class - 2
Re-issue #35725483j. failure to maintain building in code-compliant manner. noted: fpsc interior doors do not self-close properly when tested at penthouse 1-staircase "c". remedy: repair and/or replace.
May 28, 2026 · Penalty $3,125
Active - Class - 2
Re-issue #35725482h. failure to maintain building in code-compliant manner. noted: on staircase "c" between penthouse 1 and 2 there is plaster crumbling and cracks on the ceiling. remedy: repair and/or replace.
May 28, 2026 · Penalty $3,125
Active - Class - 2
Re-issue #35725481x. failure to maintain building in code-compliant manner. noted: penthouse 1 has (3)snow blowers being stored inside room which is not permitted. remedy: remove material.
May 28, 2026 · Penalty $3,125
Active - Class - 2
Exit door not self-closing. noted: exterior exit doors are not self-closing properly on the roof staircase "c" and cafeteria exit on the 1stfloor. remedy: repair/replace door.
May 28, 2026 · Penalty $625
Active - Class - 2
Incar emergency outside comm inoperative , repair
Dec 5, 2025 · Penalty $625
Resolve - Class - 1
Failure to maintain building in code-compliant manner. noted at penthouse #1, unlawful storage of (3)gas powered snow blowers with gas inside the tanks. gas powered equipment shall not be stored inside the scho
Sep 23, 2025 · Penalty $2,500
Active - Class - 2
Reissue #35692269k. failure to maintain building in code-compliant manner. noted crumbling and missing plaster or ceiling in stairwell "c" between penthouse level #1 and 2, leading to roof. remedy: repair and/o
Sep 23, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. noted interior fpsc doors not working properly at penthouse #1 stair c "mbi", 4th fl stair "a", 2nd fl autitorium entrance and auditorium stairwell"c". rem
Sep 23, 2025 · Penalty $1,250
Active - Class - 2
Reissue #35663562r. exit door not self-closing. noted exterior doors at cafeteria exits are corroded at the bottom and not properly self-closing. additionally interior fpsc doors at 4th fl stair a, 2nd fl audit
Oct 21, 2024 · Penalty $1,562
Resolve - Class - 2
Reissue #35663561p. failure to maintain building in code-compliant manner. noted stair a exterior glass panel cracked between 4th and 3rd floor. remedy: repair and/or replace,
Oct 21, 2024 · Penalty $1,562
Resolve
Show 32 more ↓
- Class - 2
Failure to maintain building in code-compliant manner. noted stair "c"has spalling and cracking/missing plaster on ceiling and landing underside between penthouse #1 and #2, leading to roof. remedy: repair and/
Oct 21, 2024 · Penalty $625
Active - Class - 2
Exit door not self-closing. noted: at exit #2, one door and cafeteria main entry/exit one door do not close properly. remedy: repair/replace door.
Jul 7, 2023 · Penalty $625
Resolve - Class - 2
Reissue #35654911l failure to maintain building in code-compliant manner. noted: at stairway both side, from 2nd floor to four floor, observed cracked glass window panel. remedy: repair/replace
Jul 7, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue#35577112z failure to maintain building in code-compliant manner.noted:observed at stwy-a between 4th flr & 3rd flr also between 3rd flr & 2nd flr,cracked/broken glass window panels.in addition observed
May 26, 2022 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:observed at(cellar level)electrical meter room/rm#c13 has an excessive amount ofstorage which include card board boxes,wooden pallet,large rugs and mi
May 26, 2022 · Penalty $625
Resolve - Class - 2
Gas connection is missing a shutoff valve and hard pipe to gas pressure gauge at top of burner/whisker switch is defective at air louver/vacuum tank vent is not piped down; correct violation and submit the c of
Jun 17, 2021 · Penalty $625
Resolve - Class - 2
Gas connection is missing a shutoff valve and hard pipe to gas pressure gauge at top of burner/whisker switch defective at air louver/chimney base door defective/boiler feed tank vent is not piped down/hwh draf
Jun 17, 2021 · Penalty $625
Resolve - Class - 2
Reissued#35495507y failure to maintain bldg in code compliant manner: noted: observed loose flashing at roof level,at various locations. remedy: repair &/or replace.
May 27, 2021 · Penalty $1,562
Resolve - Class - 1
Failure to maintain bldg walls or appurtenances: noted: observed loose& delaminating bricks at east elevation approx 30ft above kitchens exit door on the verge of falling,also cracked bricks at west elevation
May 27, 2021 · Penalty $2,500
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner: noted: observed cracke glass window panel at stair'a'between 3rd & 4th fl & stair'b'between 3rd & 2nd fl. remedy: repari &/or replace.
May 27, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: noted: observed at 4th fl room 415;spalling plaster within the closet due to water penetration. remedy: repair &/or replace.
May 27, 2021 · Penalty $625
Resolve - Class - 1
No door lock monitoring installed in this controller as per 3.10.12 of appendix k3 of the 2014 nycbc. remedy : install dlm and perform, and file test with nycdob.
Mar 24, 2021 · Penalty $1,250
Resolve - Class - 1
No door lock monitoring installed in this controller as per 3.10.12 of appendix k3 of the 2014 nycbc. remedy : install dlm and perform, and file test with nycdob. found improper fuse in elevator controller. one
Mar 24, 2021 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code compliant manner noted at roof level metal flashing in side the parapet loose and have fallen on the roof make necessary repairs
May 13, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner. staircase upperlevel to chill room area holes made in staircase walls to put beams tolift up parts for the chiller work is done walls were never fix, holes
Jun 7, 2019
Resolve - Class - 2
Reissue #35335270m failure to maintain building in code compliant manner. noted: roof exit, door have no push bar and library door miss ing door check. rmdy: make necessary repairs.
Oct 9, 2018
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: room #415, leak in the closet due to roof leak. mod built up observed. rmdy: make necessary repairs.
Oct 9, 2018
Resolve - Class - 2
Occupancy contrary to that allowed by the c of o or dob records. noted: @ time of insp observed room c-11, @ cellar level designated as fireholding area. said room is not an approved fdny fire holding area & is
Dec 19, 2016
Resolve - Class - 2
Reissue #35107194p failure to maintain bldg in code compliant manner. noted: water penetration into female locker room c28a,c28b. remedy: make necessary repairs.
Nov 9, 2016
Resolve - Class - 2
Illegal hardware noted @most classroom doors w/door stops @base of doors. remedy: remove hardware.
Aug 1, 2014
Resolve - Class - 2
Reissue 35027761m. water penetration into female locker rooms c28a, c28b. remedy: seal penetrations.
Aug 1, 2014
Resolve - Class - 2
Excessive storage of combustable materials computers,tables,chairs & other equipment stored in emergency generator room at cellar level obstructing access. remedy: remove all equipment - make accessable.
Jul 11, 2013
Resolve - Class - 2
Water penetration at cellar level foundation in female changing rm c28a,c28b. remedy: maintain water proofing.
Jul 11, 2013
Resolve - Class - 2
97b10 perform all necessary alterations to make 5yrs buffer test possible
Dec 23, 2009 · Penalty $2,500
Resolve - Non-hazardous
85u05/02l10/39o02/30b07/71b07. 02l10-emergency phone, 39o02-remove boxes not belonging there, 30b07-pin finals, 71b07-light guard.
May 1, 2006
Resolve - Non-hazardous
85u05/71b07/66q03. 71b07-under the car light guard, 66q03-sump pump cover.
May 1, 2006
Resolve - Non-hazardous
Occupancy contrary to that allowed by c of o #q196844 from catering facility on lot #1+9 to lot 1 only.remedy;amend c of o to show change.note lot number 9 sold unreal 5157 page 1913.
Jan 13, 1995
Resolve - Non-hazardous
Failure to provide panic hardware where required by law. required means of egress is obstructed. exit door swings against the flow of egress.
Jan 29, 1990 · Penalty $400
Resolve - Non-hazardous
Emergency lighting is inadequate. does not conform ot approved plans.
Jan 29, 1990
Resolve - Non-hazardous
Asystem of automatic sprinklers system not provided for the catering establishmnet with an occupant load of 300 or more persons accutal occupant load per plan with seperate room 1 floor total 815 and on second
Nov 14, 1989 · Penalty $200
Resolve - Non-hazardous
Pa contrary to approved plans inthat seperate rooms established without obtaining seperate pa permits for each remedy amend plan to show seperate use and obtain permits for each use
Nov 14, 1989
Resolve - Non-hazardous
Catering establishment and banquet halls with dancing with an occupant load of 300 or more persons lcctual occupant load per plan with seperate room 2 floor has 604 persons. remedy discontinue use until lawful
Nov 14, 1989 · Penalty $200
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 2001
- Floors
- 4
- Residential units
- —
- Building area
- 96,000 ft²
- Lot area
- 17,250 ft²
- Zoning
- R6A
- Community board
- 412
- Council district
- 27
- Block / lot
- 10215 / 1
- Assessed value
- $12,588,750
- Landmark / historic district
- No
Questions about 92-07 175 Street
Who owns 92-07 175 Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 92-07 175 Street have violations?
NYC HPD has no housing violations on record for this property.
Is 92-07 175 Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 92-07 175 Street built?
City records list 2001 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.