155-02 108 Avenue
Queens, NY 11433BBL 4-10144-0042Map
Owner of record: NYC Department Of Education
155-02 108 Avenue is a school building built in 1931 in Queens, 11433. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 12
- ECB violations
- 65
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 12
- Elevator elevatorrequired
E-elevator elevatorrequired
Oct 15, 2012
Dob violation - resolved - Construction other optional
C-construction other optional
May 8, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
Show 2 more ↓
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed
ECB violations · 65
- Class - 1
Reissue #35692271j. failure to maintain building in code-compliant manner. noted at exp #4(155 st.) decorative limestone at parapet wall level has cracks, spalling sections and top right center piece missing. p
Sep 19, 2025 · Penalty $2,500
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: at exp #4(155 street), rectangular decorative stone at parapet wall level has cracks. remedy: repair and/or replace.
Oct 21, 2024 · Penalty $625
Resolve - Class - 2
Reissue #35672307y. failure to maintain building in code-compliant manner. noted: interior fpsc doors not closing properly at 3rd fl classroom #327, 317 and 2nd fl #209 and 217. mentioned doors have defective h
Oct 21, 2024 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:class roomdoors#209,317,329,329 do not close properly.rem:repair/replace door.
May 25, 2023 · Penalty $625
Resolve - Class - 2
Exit door not self-closing.noted:at first floor,cafeteria main entrance,one door do not close properly.rem:repair/replace door.
May 25, 2023 · Penalty $625
Resolve - Class - 2
Reissue#35657757x failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at first floor cafeteria,4 emergency exits lighting
May 25, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue#35577303l failure to maintain building in code compliant manner.noted observed on the first floor in the cafeteria two emergency lights were not operational when tested.remedy:repair or replace lighting
May 26, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35577301h failure to maintain building in code compliant manner.no fire stopping per bc712.3;27-345.noted observed at cellar level in the electrical room there are holes around the pipes with no fire st
May 26, 2022 · Penalty $3,125
Resolve - Class - 2
Reissue35495500l failure to maintain bldg in codecompliant manner:no firestopping per bc712.3;27-345 observed:@cellar level,electricalrm pipes,cables penetrating thru block wall w/o firestopping provided.provid
May 20, 2021 · Penalty $3,125
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridor per bc1006.1;27-381.observed:@stairwaya light11,exit4 light1,cafeteria light3,@bsmt light14.existing emerg
May 20, 2021 · Penalty $625
Resolve
Show 40 more ↓
- Class - 2
Failure to maintain bldg in codecompliant manner.observed@2fl staira,3fl rm321 cracked&broken wire mesh glass.repair &/or replace.
May 20, 2021 · Penalty $625
Resolve - Class - 2
Reissue#35402223r failure to maintain bldg in code compliant manner: no fire stopping per 712.3;27-345. noted: at cellar at electrical room,big holes w/no fire stopping. remedy: provide/maintain fire stopping.
May 11, 2020 · Penalty $3,125
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted at 1st fl classrooms doors are installed kick down door holders at various classrooms.
May 11, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: at cellar atelectrical room,concrete ceiling w/approx 6'l crack. remedy: make necessary repairs.
May 11, 2020 · Penalty $625
Resolve - Class - 2
Reissue 35335315r. failure to maintain building in code-compliant manner; illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381 in cellar four light not working (emergency lights).
Jun 5, 2019
Resolve - Class - 2
Reissue #35326218k failure to maintain building in code compliant manner: no fire stopping per bc 712.3; 27-345. fire stop missing in main electrical room. large area above door open. rmdy: provide/maintain fi
Jun 5, 2019
Resolve - Class - 2
Re-issue #35271866n failure to maintain bldg in code compliant manner.noted:observed in rooms #309,312,317,321,323,327,325, also girls bathroom room 320, has cracks & plaster spalling.rem:repair &/or replace.
Jun 21, 2018
Resolve - Class - 2
Re-issue #35271867p failure to maintain bldg wall(s) or appurtenances.noted:corner of 156 street & 108 avenue vertical cracks @exterior brick facade,between second & third fls.rem:maintain exterior bldg wall.
Jun 21, 2018
Resolve - Class - 2
Re-issue #35271868r failure to maintain bldg wall(s) or appurtenances.noted:@rooms 129,229,329,the exterior has become porous allowing moisture to enter.rem:comply w/code,waterproof exterior.
Jun 21, 2018
Resolve - Class - 3
Occupancy contrary to that allowed by the c of o or bldg dept records.noted:observed @rear of the bldg on 155 street side seven cars parked in the yard.rem:discontinue illegal use or amend c of o.
Jun 21, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.noted:in the cellar four of the emergency lights were not working when tested.rem
Jun 21, 2018
Resolve - Class - 2
Reissue#35216629h failure to maintain bldg in code compliant manner. cellar electrical room ceiling crack approx 12ft long. remedy: repair/replace.
Jul 7, 2017
Resolve - Class - 2
Reissue#35146697z failure to maintain bldg walls or appurtenances exiterior wall has become porous water penetration at rooms 129,229,329. remedy: maintain bldg walls.
Jul 7, 2017
Resolve - Class - 2
Reissue#35216630p exit door not self closing crossover door near rm#219 not operating when tested. remedy: repair/replace door.
Jul 7, 2017
Resolve - Class - 1
Failure to maintain bldg in code compliant manner-at cellar electrical room rain water traveling down from upper exterior damaged areas is casding down rear electrical box;continuing down wall to floor then poo
Jul 7, 2017
Resolve - Class - 2
Reissue#35216628x failure to maintain bldg walls or appurtenances. noted: spalling plaster,cracks at columns in room#325,329,313,320,229,129,from water penetration fronm facade of bldg. remedy: maintain bldg
Jul 7, 2017
Resolve - Class - 2
Reissue#35216628y failure to maintain bldg walls or appurtenances corner of 1567 st & 108 ave approx 101 vertical crack in exterior brick facaded 2nd to 3 fl. remedy: maintain bldg walls.
Jul 7, 2017
Resolve - Class - 2
Reissue #35099918y failure to maintain bldg in code compliant manner. noted: the concrete ceiling has a crack approx 12' long @ electrical room @ cellar. remedy: make necessary repairs.
Nov 10, 2016
Resolve - Class - 2
Reissue #35146697z failure to maintain bldg walls or appurtenances. noted: spalling plaster & cracks @ columns observed in room #325,329,313,320,229,129,due to water penetration through facade on west of bldg.
Nov 10, 2016
Resolve - Class - 2
Exit door not self closing. noted: cross corridor adjacent to room #219 is racked & not operating properly. remedy: repair &/or replace door.
Nov 10, 2016
Resolve - Class - 2
Reissue #35147027y failure to maintain bldg walls or appurtenances. noted: at corner of 156 street & 108 ave approx 10' vertical crack in exterior brick facade from 2nd to 3rd fl. remedy: make necessary repairs
Nov 10, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.lack of emergency lighting per bc1006.1;27-542.noted @ 1st fl multi room inoperative emergency lighting w/ battery back up over exit doors #2 & 3.rem comply w/
Jul 21, 2015
Resolve - Class - 2
Exit doors not self closing.noted smoke doors adjacent to room 321,1st fl stair a,have defective &/or missing closers.rem comply w/ code
Jul 21, 2015
Resolve - Class - 2
Reissue 35099917m failure to maintain bldg exterior.noted @ rooms 129,229,329, the exterior wall has become porous allowing moisture to enter.rem comply w/ code,water proof exterior
Jul 21, 2015
Resolve - Class - 2
Failure to maintain bldg exterior.noted @ corner of 156 street & 108 ave,approx 10' vertical crack in exterior brick facade 2nd to 3rd fl.rem comply w/ code,repair or replace cracked brick masonry
Jul 21, 2015
Resolve - Class - 2
Failure to maintain bldg code compliant.no fire stopping per bc712.3;27-345.noted 2 rooms 218,318,no fire stopping w/ penetrations to concealed space above the adjacent corridor.rem comply w/ code,seal all pene
Jul 21, 2015
Resolve - Class - 2
27-371(b) non compliant vision panels per 27-371(b) noted @ 3rd fl stair a,1st fl stair a & smoke doors adjacent to room 321,thermoplastic vision panels installed.rem comply w/ code,provide code compliant visio
Jul 21, 2015
Resolve - Class - 2
Failure to maintain bldg code compliant.failure to provide vision panels per 27-371(b)noted:vision panels @ exit doors 3a,1a,& smoke doors adjacent to rm 321 are not equiped w/ wire glass as required.rem:comply
Jul 21, 2015
Resolve - Class - 2
Failure to maintain bldg code compliant.partial corridor obstruction per bc1016.2;27-369.noted @ main entry (exit1) 1 of 2 exit doors is jammed shut reducing the exit passageway 50%.rem comply w/ code
Jul 21, 2015
Resolve - Class - 2
Re-issue # 35027760k. water penetration into classroom 129,229,329,313, cellar foundation wall. remedy: seal penetration.
Jun 20, 2014
Resolve - Class - 2
Re-issue # 35027758l. spalling concrete at electrical room ceiling. remedy: repair ceiling.
Jun 20, 2014
Resolve - Class - 2
Water penetration located at cellar boiler room & classroom 129,229 & 329 due water entering foundation wall & facade on west side of bldg - plaster loose & missing. remedy: maintain - water proofing.
Jul 10, 2013
Resolve - Class - 2
Reissue 34954547m cracks located in ceiling of electrical room in various location & outside of doorway. remedy: repair defects.
Jul 10, 2013
Resolve - Class - 3
Cracks located in ceiling of electrical room in various locations rem: repair cracks
Apr 27, 2012
Resolve - Class - 2
Kick down door stops installed on door at various locations throughout bldg rem: remove door stops
Apr 27, 2012
Resolve - Class - 2
Reissue:34830881n.the concrete ceiling is cracked w/ an approx 8'long located in the electrical room @ bsmnt level.rem:repair &/or replace concrete ceiling.
Jun 29, 2011
Resolve - Class - 2
Reissue#34830880l.the electrical room is lacking fire.stopping above the doorway @ the bsmt.rem:provide maintain fire-stopping above the electrical room.
Jun 29, 2011
Resolve - Class - 2
Concrete ceiling is cracked & spalling located in the electrical room at cellar level. remedy: repair/replace concrete ceiling.
Mar 2, 2010
Resolve - Class - 2
Reissue: 34712511z. the electrical entrance/exit door is missing fire-stopping above door at cellar level. remedy: provide maintain fire-stopping.
Mar 2, 2010
Resolve - Class - 2
Failureafeguard all persons and property affected by construction operations observed smoking w/ in contruction site in vio of nyc fire code 1404.1 smokung observed 20' inside from main gate remedy:ensure that
Jun 17, 2009 · Penalty $1,200
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1931
- Floors
- 4
- Residential units
- —
- Building area
- 35,450 ft²
- Lot area
- 28,010 ft²
- Zoning
- R4A
- Community board
- 412
- Council district
- 28
- Block / lot
- 10144 / 42
- Assessed value
- $3,427,650
- Landmark / historic district
- INDIVIDUAL LANDMARK
Questions about 155-02 108 Avenue
Who owns 155-02 108 Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 155-02 108 Avenue have violations?
NYC HPD has no housing violations on record for this property.
Is 155-02 108 Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 155-02 108 Avenue built?
City records list 1931 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.