roofy

88-66 161 Street

Queens, NY 11432BBL 4-09764-0091Map

Owner of record: Hillside Avenue Development, LLC

88-66 161 Street is a hospital / health built in 1927 in Queens, 11432. It has 119 residential units across 7 floors. The owner of record is Hillside Avenue Development, LLC. HPD has recorded 89 housing violations here, most recently on June 26, 2026. 2 of the 50 most recent violations are still open.

HPD violations
89
DOB violations
61
ECB violations
99
HPD complaints
222

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Watch
Last violation Jun 26, 2026

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 89

  • A

    Post and maintain a proper sign on wall of entrance story showing the registration number assigned by the department and the address of the building., 1st story

    Jun 26, 2026

    Open — Nov sent out
  • A

    Post and maintain a proper notice on wall of the entrance story in english and spanish on the availability of the agencys housing information guide. a sample notice can be found at www.nyc.gov/hpd., 1st story

    Jun 26, 2026

    Open — Nov sent out
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    May 7, 2026

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 21, 2025

    Closed — Violation dismissed
  • C

    Remove the illegal fastening consisting of key operated double cylinder lock at 1st door from south at west leading to cafeteria at public hall, 6th story

    Oct 17, 2025

    Closed — Violation dismissed
  • C

    Replace or repair the self-closing doors that is missing or defective hinges, at east door to community water closet and shower stall at 10th door from west at north, to corridor rooms 623/624 , 6th story

    Oct 17, 2025

    Closed — Violation closed
  • C

    Replace or repair the self-closing doors that is missing or defective hinges, at west door to community wash basin at 10th door from west at north, to corridor rooms 623/624 , 6th story

    Oct 17, 2025

    Closed — Violation closed
  • C

    Replace or repair the self-closing doors that is missing or defective hinges at door in the 1st entrance from north located at b-room 323, 3rd story, 8th b-room from west at north , section ''323-324''

    Mar 2, 2025 · Apt 323

    Closed — Violation closed
  • C

    Properly repair or replace the broken or defective control valve at radiator in the bathroom located at b-room 323, 3rd story, 8th b-room from west at north , section ''323-324''

    Mar 2, 2025 · Apt 323

    Closed — Violation dismissed
  • C

    M/d law abate the nuisance consisting of hot water exceeding the maximum allowable temperature of 130 degress at hot water fixtures in the bathroom located at b-room 323, 3rd story, 8th b-room from west at north , section ''323-324''

    Mar 2, 2025 · Apt 323

    Closed — Violation dismissed
Show 40 more ↓
  • C

    M/d law abate the nuisance consisting of hot water exceeds the maximum temperature of 130 degrees at all fixtures in the entire apartment located at apt 706, 7th story, 4th apartment from east at south

    Apr 25, 2024 · Apt 706

    Closed — Violation dismissed
  • C

    Provide hot water at all hot water fixtures in the bathroom located at b-room 512, 5th story, 1st b-room from south at west

    Nov 7, 2023 · Apt 512

    Closed — Violation closed
  • C

    Abate the infestation consisting of roaches located at b-room bldg, 5th story, 1st b-room from south at west

    Nov 7, 2023 · Apt BLDG

    Closed — Violation dismissed
  • B

    Remove the accumulation of refuse and/or rubbish and maintain in a clean condition the consisting of garbage bags at rear yard yard

    Jul 26, 2023

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Mar 28, 2023

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Mar 4, 2022

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Apr 15, 2021

    Closed — Violation dismissed
  • C

    Arrange and make self-closing the doors door to fire stair, at north wall, at public hall, 1st story, section ''west''

    May 16, 2020

    Closed — Violation dismissed
  • B

    Replace with new the broken or defective ceramic floor tiles in the bathroom located at apt 201, 2nd story, 2nd apartment from north at east

    May 16, 2020 · Apt 201

    Closed — Violation dismissed
  • C

    Arrange and make self-closing the doors at entrance to apartment in the bathroom located at apt 201, 2nd story, 2nd apartment from north at east

    May 16, 2020 · Apt 201

    Closed — Violation dismissed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color ceiling in the bathroom located at b-room 311, 3rd story, 1st b-room from north at east

    Nov 1, 2018 · Apt 311

    Closed — Violation dismissed
  • B

    Properly repair the source and abate the evidence of a water leak ceiling in the bathroom located at b-room 311, 3rd story, 1st b-room from north at east

    Nov 1, 2018 · Apt 311

    Closed — Violation dismissed
  • C

    Remove the illegal fastening double cylinder key operated locks installed at the doors of front building entrance at east & west

    Oct 23, 2018

    Closed — Violation closed
  • C

    M/d law abate the nuisance consisting of scalding hot water exceeding 130 deg f in the bathroom located at apt 210, 2nd story, 8th apartment from east at south

    Oct 20, 2018 · Apt 210

    Closed — Violation closed
  • B

    Properly repair the broken or defective door at entrance in the bathroom located at apt 405, 4th story

    Sep 29, 2015 · Apt 405

    Closed — Violation dismissed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color ceiling and walls in the bathroom located at apt 405, 4th story

    Sep 29, 2015 · Apt 405

    Closed — Violation dismissed
  • A

    Reset, so as to secure a proper and tight connection, the water closet bowl at south bathroom located at b-room 702, 7th story, 1st b-room from east at south

    May 26, 2015 · Apt 702

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color the ceiling in the bathroom located at b-room 507, 5th story, 5th b-room from east at south

    May 26, 2015 · Apt 507

    Closed — Violation closed
  • B

    Remove all obstructions and repair all defects in waisteline at washbasin in the bathroom located at b-room 618, 6th story, 3rd b-room from west at north

    May 26, 2015 · Apt 618

    Closed — Violation closed
  • B

    Remove all obstructions and repair all defects in waisteline at washbasin in the bathroom located at b-room 714, 7th story, 2nd b-room from south at west

    May 26, 2015 · Apt 714

    Closed — Violation closed
  • C

    Replace with new the broken or defective bottom sash glass window pane in the room located at b-room 719, 7th story, 4th b-room from west at north

    May 26, 2015 · Apt 719

    Closed — Violation closed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Feb 27, 2015

    Closed — Violation dismissed
  • B

    Properly secure the loose washbasin in the room located at b-room 504, 5th story, 2nd b-room from east at south

    Oct 21, 2014 · Apt 504

    Closed — Violation closed
  • B

    Repair the leaky and/or defective faucets at bathtub in the bathroom located at b-room 705, 7th story, 3rd b-room from east at south

    Oct 21, 2014 · Apt 705

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling in the room located at b-room 319, 3rd story, 4th b-room from west at north

    Oct 21, 2014 · Apt 319

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling in the room located at b-room 318, 3rd story, 3rd b-room from west at north

    Oct 21, 2014 · Apt 318

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling in the bathroom located at b-room 318, 3rd story, 3rd b-room from west at north

    Oct 21, 2014 · Apt 318

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at east wall in the room located at b-room 317, 3rd story, 2nd b-room from west at north

    Oct 21, 2014 · Apt 317

    Closed — Violation closed
  • B

    Trace and repair the source and abate the nuisance consisting of mold ... at ceiling in the bathroom located at b-room 312, 3rd story, 1st b-room from south at west

    Oct 21, 2014 · Apt 312

    Closed — Violation closed
  • A

    Paint with light colored paint to the satisfaction of this department at ceiling in the bathroom located at b-room 417, 4th story, 2nd b-room from west at north

    Oct 21, 2014 · Apt 417

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling in the bathroom located at b-room 409, 4th story, 7th b-room from east at south

    Oct 21, 2014 · Apt 409

    Closed — Violation closed
  • B

    Arrange and make self-closing the doors .. in the room located at b-room 521, 5th story, 6th b-room from west at north

    Oct 21, 2014 · Apt 521

    Closed — Violation closed
  • B

    Arrange and make self-closing the doors .. in the room located at b-room 517, 5th story, 2nd b-room from west at north

    Oct 21, 2014 · Apt 517

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at south wall in the room located at b-room 514, 5th story, 2nd b-room from south at west

    Oct 21, 2014 · Apt 514

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling in the bathroom located at b-room 514, 5th story, 2nd b-room from south at west

    Oct 21, 2014 · Apt 514

    Closed — Violation closed
  • B

    Remove all obstructions and repair all defects in washbasin in the bathroom located at b-room 507, 5th story, 5th b-room from east at south

    Oct 21, 2014 · Apt 507

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling in the bathroom located at b-room 207, 2nd story, 5th b-room from east at south

    Oct 21, 2014 · Apt 207

    Closed — Violation closed
  • A

    Paint with light colored paint to the satisfaction of this department at ceiling in the room located at b-room 504, 6th story, 2nd b-room from east at south

    Oct 21, 2014 · Apt 504

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling in the bathroom located at b-room 622, 6th story, 7th b-room from west at north

    Oct 21, 2014 · Apt 622

    Closed — Violation closed
  • B

    Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling in the room located at b-room 621, 6th story, 6th b-room from west at north

    Oct 21, 2014 · Apt 621

    Closed — Violation closed

DOB building violations · 61

  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jul 21, 2021

    Dob violation - dismissed
  • Construction other optional

    Emergency work:install sidewalk shed at exp 1 south elev and exp 4 east elev. at time of insp emergency work ftm facade observe such as at 7fl parapet masnory wall terra cotta/masonry facade are cracking/spalled & deterioated at multiple locations/exp cond. observe potential haz for public. rmedy:owner to immed install sidewalk shed

    Apr 19, 2021

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Dec 26, 2019

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Nov 27, 2019

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Nov 27, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 20, 2019

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Apr 17, 2019

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Apr 17, 2019

    Dob violation - dismissed
Show 40 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 19, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 19, 2018

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Aug 22, 2018

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 8a technical report by 02/21/2017

    May 31, 2018

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    May 30, 2018

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Apr 18, 2018

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2016 inspection report

    Apr 6, 2018

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 4, 2017

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 4, 2017

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 13, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 13, 2017

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Apr 5, 2017

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2015 inspection report

    Feb 24, 2017

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 1, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 1, 2016

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Dec 16, 2015

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 15, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 15, 2014

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 14, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 14, 2013

    Dob violation - resolved
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 7a technical report by 02/21/2012

    Jan 31, 2013

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 22, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 22, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 26, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 26, 2011

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 21, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 15, 2010

    Dob violation - resolved
  • Emergency power none

    Ll2604e-emergency power none

    Mar 31, 2008

    Dob violation - dismissed
  • Facade facade optional

    Ll1198-local law 11/98 - facade facade optional

    Nov 30, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 2, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 2, 2007

    Dob violation - resolved
  • Construction other optional

    C-construction other optional

    Apr 4, 2007

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 2, 2007

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 7, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 7, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 21, 2003

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 21, 2003

    Dob violation - resolved

ECB violations · 99

  • Class - 2

    Observed lack sprinkler coverage in lobby, lunchroom, kitchen and staircase going to the roof. also, in basement lack support on gas line which is contrary to codes sections fgc 407.2 and bc 403.3, repair and/o

    Sep 25, 2025 · Penalty $1,280

    Active
  • Class - 2

    Class 2 items: cat 1 tag missing, provide updated tag. landing signs (braille tags) missing in the basement, provide as needed. up direction hall button in the lobby jams in when pressed, repair. lobby up direc

    Sep 25, 2025 · Penalty $625

    Resolve
  • Class - 2

    Class 2 items: retainer (z)-bracket missing on the lobby door, install. cat 1 tag missing, provide updated tag. landing signs (braille tags) missing in the basement, provide as needed. up direction hall button

    Sep 25, 2025 · Penalty $625

    Resolve
  • Class - 2

    Observed throughout the building sprinkler heads obstructed. standpipe connections missing caps; fire department connection not properly capped. pvc piping installed on waste lines ejector pit missing cover pla

    Sep 25, 2025

    Resolve
  • Class - 2

    Exit door not self-closing. observed non self-closing doors (utility closets ) throughout the building. potentially fire or smoke hazard., repair/replace door

    Oct 23, 2024

    Resolve
  • Class - 1

    Class 1 cease use item: door zone restrictor inoperative. this is a safety feature which ensures passenger safety. remedy: to restore service, call or emailthe d.o.b. [email protected]. elevator division at

    Oct 21, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Class 2 items: in-car communication inoperative. category 1 test tag expired. provide an updated maintenance log. provide a maintenance program. clean remove old parts in machine room. clean entire pit area and

    Oct 21, 2024

    Resolve
  • Class - 1

    Device out of service restore to service immediately. you can contact nycdob at [email protected] for a complete inspection. cat five tag expired on 4/17.

    Apr 13, 2023 · Penalty $1,563

    Resolve
  • Class - 1

    Device out of service restore to service immediately. you can contact nycdob at [email protected] for a complete inspection.

    Dec 28, 2022

    Resolve
  • Class - 2

    Failure to submit acceptable required cycle 9a report of critical examination documenting condition of exterior wall & appurtenances required by 28-302.4 for control #911619.remedy:submit acceptable required te

    Dec 9, 2022

    Resolve
Show 40 more ↓
  • Class - 2

    Repair and restore to service.

    Nov 9, 2022 · Penalty $625

    Resolve
  • Class - 2

    I observed in the electrical equipment room the removal of the temporary wiring as stated in ecb # 39064148m issued on 06/15/2022 without an electrical permit on file in dob records. as stated in the administra

    Oct 28, 2022 · Penalty $800

    Resolve
  • Class - 2

    I observe at exposure #1 the improper termination of flexible cords supplying power to the wall lights and a junction box without a cover allowing the conductors to be exposed. noted in the lobby entrance the i

    Oct 28, 2022 · Penalty $800

    Resolve
  • Class - 2

    I noted in dob records ecbs # 39064148m-49y-50l-51n-52p issued on 06/15/2022 with no certificate of correction nor with an electrical permit stating the purpose of correcting the abovementioned summonses. as pe

    Oct 28, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    I observed in the electrical closets on floors 2 thru 7 the electrical conduits connected to the existing panels in the stairwells not or improperly supported. also noted armored cabling not supported as well.

    Oct 28, 2022 · Penalty $500

    Resolve
  • Class - 2

    I observed on floors 2 thru 7 in the the electrical closets with the panels having open spaces allowing improper contact with the energized parts. this is an immediate shock/ safety hazard as the security offic

    Oct 28, 2022 · Penalty $2,000

    Resolve
  • Class - 2

    I observed in basement potable water line being supported incorrectly, as per 2.1.5.1 of the 2014 bc in buildings of types i and ii construction, hangers shall be attached to the structure of the building., rep

    Oct 17, 2022

    Resolve
  • Class - 2

    At first floor, lunch room and kitchen exit doors, at cellar level exit door near elevator room do not close properly when inspected, repair/replace door

    Oct 17, 2022 · Penalty $625

    Resolve
  • Class - 1

    Upon inspection device was found out of service. restore to service immediately and contact nycdob . at [email protected] for a complete inspection.

    Oct 12, 2022 · Penalty $625

    Resolve
  • Class - 1

    I observed in the basement along the floor outside the electrical room in the tank room temporary rubber cord wiring not supported as required. photos taken., protect temporary wiring

    Jun 15, 2022 · Penalty $1,600

    Resolve
  • Class - 1

    I observed in the basement electrical room the installation of temporary rubber cord wiring passing thru the bottom of the entrance door to the electrical equipment room. temp wiring must be protected from impr

    Jun 15, 2022 · Penalty $1,600

    Resolve
  • Class - 2

    I observed on floors 2 thru 7 the utility closets with the electrical panels with open spaces a;;owing access to the live energized parts by unauthorized personnel (the security officers stationed on the floors

    Jun 15, 2022 · Penalty $800

    Resolve
  • Class - 2

    I observed in the utility closets the installation of new junction boxes,cabling, and devices. no permit in dob records covers this work., obtain permit

    Jun 15, 2022 · Penalty $800

    Resolve
  • Class - 2

    I observed in the utility closets containing the electrical panels , the conduits connected to hallway panel not secured as required. photos taken., properly secure/support emt

    Jun 15, 2022 · Penalty $500

    Resolve
  • Class - 2

    Utility rooms from 7th fl to 2nd fl, several openings due pipes/ cables penetration through the ceiling & fireproof walls without fire stopping provided, provide/maintain fire stopping

    Jun 3, 2022 · Penalty $1,250

    Resolve
  • Class - 1

    At time of my inspection i observed in the cellar boiler room off the boiler a tee with a plug on the gas piping, that is a future connection and not code compliant., repair and/replace

    Apr 12, 2022 · Penalty $1,280

    Active
  • Class - 2

    Unapproved,unsafe,unsuitable electrical equipment,apparatus,materials devices,appliances in use i observed on all fls in utility closets,exposed live parts in electrical panels due to open spaces.also noted imp

    Dec 7, 2021 · Penalty $2,030

    Resolve
  • Class - 2

    Failure to comply w/commissioner's orders to file c/c w/dob as per ec39007446j issued8/9/19 stated improper support of bx cables,no illumination for electrical panel&exposed energized parts due to open spaces i

    Dec 7, 2021 · Penalty $1,280

    Resolve
  • Class - 2

    Chimney base 1/2 full/discharge pipe missing at safety valve body drain/fresh air 1/2 blocked;correct violation and submit the certificate of correction

    Sep 23, 2021 · Penalty $625

    Active
  • Class - 1

    Failure to maintain exterior building facade and appurtenances.note:atthe time of inspection facade observe hazardous conditions at 7th floor window lintel through parapet masonry wall at multiple location at e

    Apr 19, 2021 · Penalty $2,530

    Resolve
  • Class - 2

    Failure to maintain exterior facade and appurtenances. note:at the time of inspection,observed south elevation exposure 1,deteriorating mortar joints,open joints,spalled bricks,broken/damaged bricks at 7th fl d

    Apr 2, 2021 · Penalty $1,280

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. remedy; file application, install dlm a

    Mar 9, 2021 · Penalty $1,250

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. remedy; file application, install dlm a

    Mar 9, 2021 · Penalty $1,250

    Resolve
  • Class - 1

    Elevator out of service for several months , elderly and handicaped people living in building restore to service immediatly and contact dob elevators for an inspection before going into service

    May 7, 2020

    Resolve
  • Class - 2

    Noted: observed emergency lights throughout common corridors and stairwells at each story were not operational when tested, due to defective wiring, ballast or test buttons. when test button was pressed all lig

    Jan 28, 2020 · Penalty $625

    Resolve
  • Class - 2

    I observed at exposure 1, en electric sliding gate that was installed without an electrical permit on file at the department of buildings, obtain permit

    Jan 28, 2020 · Penalty $800

    Resolve
  • Class - 1

    Cease use 5-a-10,door zone restrictor not working tampered with disable this is a safety device to ensure passengers safety

    Sep 30, 2019 · Penalty $1,250

    Resolve
  • Class - 1

    97-x-17=upon inspection device was found to beout of service restore to sevice immeidtaely and cont nyc dob in a completet inspection

    Sep 30, 2019 · Penalty $6,250

    Resolve
  • Class - 2

    97x17-upon inspection device was found to be out of service.restore toservice immediately and contact nycdob for a complete inspection.

    Sep 4, 2019 · Penalty $312

    Resolve
  • Class - 2

    97.x.17=one eevator of service in a duplex (bank) based upon my inspection the device is at of service creating a hazrdous condition this elevator provided service for manay elderly people as per 1rcny 11-02 re

    Aug 30, 2019 · Penalty $625

    Resolve
  • Class - 3

    I observed on all floors in the utility and stairwells (a) and (b) no panel directory for the branch circuits as required. photos taken., provide circuit directory/id

    Aug 9, 2019 · Penalty $230

    Resolve
  • Class - 2

    I observed on all floors in the utility closets, exposed live parts in electrical panels due to open spaces and missing covers. also noted improperly supported bx cables. also noted there was no illumination pr

    Aug 9, 2019 · Penalty $830

    Resolve
  • Class - 2

    No ventilation in the gas meter room , repair and/or replace

    Jul 22, 2019 · Penalty $655

    Resolve
  • Class - 2

    Staircase a skylight glass falling out, letting rain in to staircase. staircase b water leak coming from roof plaster falling , repair and/or replace

    Jul 22, 2019 · Penalty $312

    Resolve
  • Class - 2

    Fire stop missing in all utility closet on all floor, fire block foam used which does not have a 2hour rating., provide/maintain fire stopping

    Jul 22, 2019

    Resolve
  • Class - 2

    Pedestrian protection does not meet code specifications. @time of my inspection obsevred none active job site. the sidewalk shed light was not provided as required.the sidewalk @exp-4 under no light on and ped

    Jul 2, 2019

    Resolve
  • Class - 2

    Failure to comply with commissioners order contained in summons/viola ion#32097362j issued on 07/17/2018 and to file a certificate of corre tion pursuant to 28-201.1 and 1rcny 102-01(d)(2).an acceptible certif

    May 21, 2019 · Penalty $1,280

    Resolve
  • Class - 2

    Failure to comply with commissioners order contained in summons/violation#32097360x issued on 07/17/2018 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01(d)(2).an acceptible certifi

    May 21, 2019 · Penalty $1,280

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: observedwater penetration through skylight at stair b roof bulkhead and pooling on top landing. photos taken.

    Jan 24, 2019 · Penalty $655

    Resolve
  • Class - 1

    110.11 nec electrical equipment and service conductors are subject to deteriorating agents.i observed in the main electrical room the service equipment and the service conductors not protected against deterior

    Jan 24, 2019

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Jun 24, 2026 · Apt 701-1

    Close
  • Heat/hot water

    Entire building

    Mar 11, 2026 · Apt 506

    Close
  • Heat/hot water

    Entire building

    Nov 2, 2025 · Apt 705

    Close
  • Heat/hot water

    Entire building

    Oct 16, 2025 · Apt 623

    Close
  • Heat/hot water

    Entire building

    Mar 6, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Mar 3, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Mar 3, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Mar 2, 2025 · Apt 323

    Close
  • Heat/hot water

    Entire building

    Feb 5, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Jan 22, 2025 · Apt BLDG

    Close
Show 40 more ↓
  • Heat/hot water

    Entire building

    Nov 21, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 19, 2024 · Apt 221

    Close
  • Heat/hot water

    Entire building

    Nov 18, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 17, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 17, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 12, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 12, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 1, 2024 · Apt 202

    Close
  • Heat/hot water

    Entire building

    Oct 31, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Jul 12, 2024 · Apt 422

    Close
  • Heat/hot water

    Entire building

    May 24, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    May 21, 2024 · Apt BLDG

    Close
  • Unsanitary condition

    Garbage/recycling storage

    May 2, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Apr 27, 2024 · Apt 220

    Close
  • Heat/hot water

    Entire building

    Apr 27, 2024 · Apt 319

    Close
  • Heat/hot water

    Entire building

    Apr 25, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Apr 18, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Apr 17, 2024 · Apt BLDG

    Close
  • General

    Ventilation system

    Mar 31, 2024 · Apt THEWHO

    Close
  • Unsanitary condition

    Pests

    Mar 31, 2024 · Apt THEWHO

    Close
  • Unsanitary condition

    Mold

    Mar 31, 2024 · Apt THEWHO

    Close
  • Paint/plaster

    Radiator

    Mar 31, 2024 · Apt THEWHO

    Close
  • Unsanitary condition

    Pests

    Mar 31, 2024 · Apt THEWHO

    Close
  • Heat/hot water

    Entire building

    Mar 22, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Feb 17, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Feb 16, 2024 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 24, 2023 · Apt 603

    Close
  • Heat/hot water

    Entire building

    Nov 3, 2023 · Apt BLDG

    Close
  • Unsanitary condition

    Pests

    Oct 31, 2023 · Apt ALL7FL

    Close
  • Plumbing

    Water supply

    Oct 31, 2023 · Apt ALL7FL

    Close
  • Paint/plaster

    Ceiling

    Oct 31, 2023 · Apt ALL7FL

    Close
  • Paint/plaster

    Wall

    Oct 31, 2023 · Apt ALL7FL

    Close
  • Plumbing

    Water supply

    Oct 31, 2023 · Apt BLDG

    Close
  • Unsanitary condition

    Pests

    Oct 31, 2023 · Apt ALL7FL

    Close
  • Unsanitary condition

    Pests

    Oct 31, 2023 · Apt ALL7FL

    Close
  • Unsanitary condition

    Mold

    Oct 31, 2023 · Apt ALL7FL

    Close
  • Unsanitary condition

    Pests

    Oct 31, 2023 · Apt ALL7FL

    Close
  • Heat/hot water

    Entire building

    Oct 31, 2023 · Apt ALL7FL

    Close
  • Plumbing

    Water supply

    Oct 31, 2023 · Apt ALL7FL

    Close
  • Heat/hot water

    Entire building

    Oct 31, 2023 · Apt BLDG

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Hospital / health (I7)
Year built
1927
Floors
7
Residential units
119
Building area
58,625 ft²
Lot area
9,525 ft²
Zoning
C4-4D
Community board
412
Council district
24
Block / lot
9764 / 91
Assessed value
$4,473,450
Landmark / historic district
No

HPD registration #419159, last renewed Nov 28, 2025.

Questions about 88-66 161 Street

Who owns 88-66 161 Street?

The owner of record in NYC Department of City Planning PLUTO data is Hillside Avenue Development, LLC.

Does 88-66 161 Street have violations?

Yes. NYC HPD has recorded 89 housing violations at this property.

Is 88-66 161 Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 88-66 161 Street built?

City records list 1927 as the year it was built.

How many apartments are in 88-66 161 Street?

It has 119 residential units.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.